| Product type | Transformers and power supplies |
| Product group | Components for panels and boxes |
| Series | Modicon Switchmode ABLU |
| Primary voltage AC | 48 |
| Current | 20 A |
| Phase | 3 pcs |
| REACH SVHC substance above 0.1% | Lead, Lead-monoxide |
| Carbon footprint (EPD) | 37.2016 kg CO2e per pcs |
| Country of origin | Thailand |
| Customs tariff code (EU CN) | 85044095 |
| HS code | 8504.40 |
| Manufacturer part number | ABLU3A48200 |
| Range of product | Modicon Power Supply |
| Product or component type | Power supply |
| Power supply type | Regulated switch mode |
| Variant option | Universal |
| Enclosure material | Metal |
| Nominal input voltage | 380...500 V AC three phase |
| Rated power in W | 960 W |
| Output voltage | 48 V DC |
| Power supply output current | 20 A |
| Permissible temporary current boost | 1.5 x In (for 5 seconds) |
| Input voltage limits | 320...575 V AC 3 phases |
| Nominal network frequency | 50…60 Hz |
| Network system compatibility | TN; TT; IT |
| Maximum leakage current | 2 mA 500 V AC |
| Input protection type | Integrated fuse (not interchangeable) 3.15 A; External protection (recommended) |
| Inrush current | 35 A at 380 V; 35 A at 500 V |
| Power factor | 0.90 at 380 V AC; 0.90 at 500 V AC |
| Efficiency | 95 % at 380 V AC; 95 % at 500 V AC |
| Output voltage adjustment | 48…56 V |
| Power dissipation in W | 49 W |
| Current consumption | < 1.9 A 380 V AC; < 1.7 A 500 V AC |
| Turn-on time | < 2 s |
| Holding time | > 20 ms 380 V AC; > 20 ms 500 V AC |
| Startup with capacitive loads | 200000 µF |
| Residual ripple | < 200 mV |
| Meantime between failure [MTBF] | 912400 h at 25 °C, full load conforming to SR 332; 382500 h at 55 °C, 80 % load conforming to SR 332 |
| Output protection type | Against overload and short-circuits, protection technology: manual or automatic reset by switch; Against over temperature, protection technology: automatic reset; Against overvoltage, protection technology: manual reset |
| Connections - terminals | Screw connection: 4 x 10 mm², (12 AWG...8 AWG) with wire end ferrule for output; Screw connection: 4...16 mm², (12 AWG...6 AWG) without wire end ferrule for output; Screw connection: 0.75…6 mm², (18 AWG...10 AWG) without wire end ferrule for input; Screw connection: 0.75...4 mm², (18 AWG...12 AWG) with wire end ferrule for input; Cage clamp: 0.2...1.5 mm², (22 AWG...16 AWG) without wire end ferrule for diagnostic relay; Cage clamp: 0.2...1.5 mm², (22 AWG...16 AWG) without wire end ferrule for shut down input; Cage clamp: 0.2...0.75 mm², (22 AWG...18 AWG) with wire end ferrule for diagnostic relay; Cage clamp: 0.2...0.75 mm², (22 AWG...18 AWG) with wire end ferrule for shut down input |
| Line and load regulation | < 0.17 % at 100 % load in line at 25 °C; < 0.6 % +/- 0.5 % at 100 % load at 25 °C for single mode; 4 % at 150 % load at 25 °C for parallel mode |
| Status LED | 1 LED (green and red) product status |
| Depth | 128.7 mm |
| Height | 124 mm |
| Width | 110 mm |
| Product weight | 2.29 kg |
| Output coupling | Single/parallel by switch |
| Marking | CE; UKCA |
| Mounting support | Top hat type TH35-15 rail conforming to IEC 60715; Top hat type TH35-7.5 rail conforming to IEC 60715; Double-profile DIN rail |
| Supply | SELV conforming to IEC 60950-1; SELV conforming to IEC 60204-1; SELV conforming to IEC 60364-4-41 |
| Dielectric strength | 4000 V AC with input to output; 2000 V AC with input to ground; 1500 V AC with output to ground; 4000 V AC with input to diagnostic relay; 500 V AC with output to diagnostic relay; 1500 V AC with diagnostic relay to ground; 4000 V AC with shutdown input to input; 1500 V AC with shutdown input to ground; with shutdown input not isolated from output |
| Shutdown input | Non isolated input, dry contact 0.3 mA 4 V |
| Diagnostic relay | Electromechanical relay 1000.0 mA 30 V |
| Service life | 10 year(s) 40 °C 80 % load |
| Overvoltage category | III; II |
| Standards | IEC 62368-1; EN/IEC 61204-3; IEC 61000-6-1; IEC 61000-6-2; IEC 61000-6-3; IEC 61000-6-4; IEC 61000-3-2; EN 61000-3-3; UL 62368-1; CSA C22.2 No 62368-1; CSA C22.2 No 107.1 |
| Product certifications | CE; CUL listed; CUL recognized; RCM; CB Scheme; EAC; KC; UKCA; CURus |
| Operating altitude | < 5000 m overvoltage category III; overvoltage category II |
| Shock resistance | 150 m/s² for 11 ms |
| IP degree of protection | IP20 |
| Ambient air temperature for operation | -25…55 °C without current derating mounting position A < 2000 m; 55…70 °C with current derating of 3.3 % per °C mounting position A < 2000 m |
| Electrical shock protection class | Class I |
| Pollution degree | 2 |
| Vibration resistance | 3.5 mm (f= 3…11.9 Hz) conforming to IEC 60068-2-6; 20 m/s² (f= 11.9…150 Hz) conforming to IEC 60068-2-6 |
| Electromagnetic immunity | Immunity to electrostatic discharge - test level: 8 kV (contact discharge) conforming to IEC 61000-4-2; Immunity to electrostatic discharge - test level: 15 kV (air discharge) conforming to IEC 61000-4-2; Immunity to conducted RF disturbances - test level: 15 V/m (80 MHz...2 GHz) conforming to IEC 61000-4-3; Immunity to conducted RF disturbances - test level: 5 V/m (2...2.7 GHz) conforming to IEC 61000-4-3; Immunity to conducted RF disturbances - test level: 5 V/m (2.7...6 GHz) conforming to IEC 61000-4-3; Immunity to fast transients - test level: 4 kV (on input-output) conforming to IEC 61000-4-4; Surge immunity test - test level: 4 kV (between power supply and earth) conforming to IEC 61000-4-5; Surge immunity test - test level: 3 kV (between phases) conforming to IEC 61000-4-5; Immunity to conducted RF disturbances - test level: 15 V (0.15...80 MHz) conforming to IEC 61000-4-6; Immunity to magnetic fields - test level: 30 A/m (50...60 Hz) conforming to IEC 61000-4-8; Immunity to voltage dips conforming to IEC 61000-4-11; Disturbing field emission conforming to EN 55016-2-3; Limits for harmonic current emissions conforming to IEC 61000-3-2; conforming to EN 55016-1-2; conforming to EN 55016-2-1 |
| Electromagnetic emission | Conducted emissions conforming to IEC 61000-6-3; Radiated emissions conforming to IEC 61000-6-4 |
| Number of Units in Package 1 | 1 |
| Number of Units in Package 2 | 2 |
| Number of Units in Package 3 | 48 |
| Warranty (in months) | 18 |
| EAN | 3606482185289 |