| Manufacturer part number (MPN) | A9MEM3555 |
| EAN / GTIN | 3606480845246 |
| Sales unit | pcs |
| Range | Acti9 |
| range of product | Acti9 iEM3000 |
| Product or component type | Energy meter |
| Device short name | iEM3555 |
| Market segment | Buildings small building cost management: billing: main incomer; Buildings small building cost management: billing: sub feeder; Buildings small building cost management: billing: panelboard; Buildings medium building cost management: billing: main incomer; Buildings medium building cost management: billing: sub feeder; Buildings medium building cost management: billing: panelboard; Buildings large building cost management: billing: main incomer; Buildings large building cost management: billing: sub feeder; Buildings large building cost management: billing: panelboard; Buildings multi-site cost management: billing: main incomer; Buildings multi-site cost management: billing: sub feeder; Buildings multi-site cost management: billing: panelboard; Data center cost management: billing; Healthcare cost management: billing; Industry cost management: billing; Buildings small building cost management: cost allocation: main incomer; Buildings small building cost management: cost allocation: sub feeder; Buildings small building cost management: cost allocation: panelboard; Buildings medium building cost management: cost allocation: main incomer; Buildings medium building cost management: cost allocation: sub feeder; Buildings medium building cost management: cost allocation: panelboard; Buildings large building cost management: cost allocation: main incomer; Buildings large building cost management: cost allocation: sub feeder; Buildings large building cost management: cost allocation: panelboard; Buildings multi-site cost management: cost allocation: main incomer; Buildings multi-site cost management: cost allocation: sub feeder; Buildings multi-site cost management: cost allocation: panelboard; Data center cost management: cost allocation; Healthcare cost management: cost allocation; Industry cost management: cost allocation |
| Poles description | 3P; 3P + N; 1P + N |
| Type of measurement | Active and reactive energy; Active and reactive power; Current; Voltage |
| Metering type | Active, reactive, apparent energy (signed, four quadrant) |
| Device application | Multi-tariff; Partial meter; Sub billing |
| Accuracy class | Class 0.5S active energy conforming to IEC 62053-22; Class 0.5S active energy conforming to ANSI C12.20 |
| input type | Rogowski coil 50...5000 A |
| Rated voltage | 100…277 V +/- 20 %; 173…480 V +/- 20 % |
| Network frequency | 50 Hz; 60 Hz |
| Technology type | Electronic |
| Display type | LCD display |
| Sampling rate | 32 samples/cycle |
| Measurement current | 50…5000 A |
| Maximum value measured | 99999999.9 kWh; 99999999 MWh |
| tariff input | Tariff (4) |
| Communication port protocol | Modbus RTU at 9.6, 19.2 and 38.4 kbauds even/odd or none |
| Communication port support | Screw terminal block: RS485 |
| Local signalling | Green indicator light: power ON; Yellow flashing LED: accuracy checking; alarm: overload; Yellow indicator light: communications are active on the Modbus port (Modbus) |
| Number of inputs | 1 digital 0...5 V/11...40 V 24 V DC |
| Number of outputs | 1 digital (static) |
| Output voltage | 5...40 V DC@50 mA |
| mounting mode | Clip-on |
| Mounting support | DIN rail |
| Connections - terminals | Current circuit: screw terminals 6 mm² cable(s) ; Voltage circuit: screw terminals 2.5 mm² cable(s) ; Input/output circuit: screw terminals 1.5 mm² cable(s) ; Communication: screw terminals 2.5 mm² cable(s) |
| Tightening torque | Input/output circuit: 0.5 N.m Philips screwdriver ; Voltage circuit: 0.5 N.m Philips screwdriver ; Current circuit: 0.8 N.m pozidriv screwdriver ; Communication: 0.5 N.m Philips screwdriver |
| Wire stripping length | Input/output circuit: 6 mm; Voltage circuit: 8 mm; Current circuit: 8 mm; Communication: 7 mm |
| Standards | BS EN 61326-1; IEC 61326-1; EN 61326-1; BS EN 61010-1:2010; EN 61010-1:2010; IEC 61010-1:2010; UL 61010-1:2010; BS EN 61010-2-30; IEC 61010-2-30; EN 61010-2-30; UL 61010-2-30; ANSI C12.20 |
| Product certifications | CE conforming to IEC 61010-1 (safety); CE conforming to EN 61557-12 (power monitor); CE conforming to EN/IEC 61326-1 (EMC); UKCA conforming to BS EN 61010-1 (safety); UKCA conforming to BS EN 61557-12 (power monitor); UKCA conforming to BS EN 61326-1 (EMC); CULus conforming to UL 61010-1 (safety); CULus conforming to EN 61010-1 (safety); KZ; RCM |
| Compatibility code | IEM3555 |
| IP degree of protection | IP40 front panel: conforming to IEC 60529; IP20 body: conforming to IEC 60529 |
| IK degree of protection | IK08 |
| Pollution degree | 2 |
| Relative humidity | 5…95 % at 36 °C |
| Ambient air temperature for operation | -25…70 °C - IEC |
| Ambient air temperature for storage | -40…85 °C |
| Operating altitude | < 3000 m |
| Colour | White |
| 9 mm pitches | 10 |
| Width | 90 mm |
| Height | 87 mm |
| Depth | 69 mm |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 8.700 cm |
| Package 1 Width | 9.600 cm |
| Package 1 Length | 10.600 cm |
| Package 1 Weight | 328.000 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 30 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 10.310 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 240 |
| Package 3 Height | 80.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 100.364 kg |
| Country of origin | CN |
| Warranty (in months) | 18 |
| Mounting method | DRA (DIN-rail adaptor) |
| Model | Measurement transformer |
| Suitable for | Purchase/supply |
| Type of indication | Digital |
| Width in number of modular spacings | 5 |
| Number of positions total (counter) | 9 |
| Type of meter | Electronic |
| Degree of protection (IP) | IP20 |
| Type of interface | RS-485 |
| Energy type | Effective power and reactive power |
| Tariff type | Multi-tariff |
| Tariff control | Internal/external |
| Escapement mechanism | No |
| Calibrated | No |
| Approval | Domestic |
| Pulse output | Electrical |
| Pulse type | D0 |
| Pole type | Three conductor/four conductor |
| Measurement type load profile | No |
| EEC40 signature | No |
| With lock code | No |