Schneider Electric energy sensor, PowerTag Flex 160A 3P/3P+N top and bottom position A9MEM1580

Schneider Electric · Sensors & Instrumentation · Energy Meters · France · se.com
Part Number
A9MEM1580  ·  HS 9030.33
Schneider Electric energy sensor, PowerTag Flex 160A 3P/3P+N top and bottom position A9MEM1580

Schneider Electric A9MEM1580 PowerTag - 3P - Universal - Max.. 160 A - Wireless - Energisensor.

Technical Specifications

Manufacturer part number (MPN)A9MEM1580
EAN / GTIN3606481595270
Sales unitpcs
Package quantity24 pcs
Rated current160 A
Number of poles3P
Range of productPowerLogic
Product namePowerTag F160
Product or component typeEnergy sensor
Poles3P; 3P + N
Maximum current [Imax]160 A
[Ib] Basic current25 A
Starting current100 mA
Saturation current320 A
Product specific applicationEnergy management; Overload alarm; Power factor; Load monitoring; Circuit monitoring
Concentrator compatibilityEcoStruxure Panel Server Entry; EcoStruxure Panel Server Universal; EcoStruxure Panel Server Advanced; Harmony Hub; Acti9 PowerTag Link; Acti9 PowerTag Link HD
Range compatibilityActi9 Acti9 C120; Acti9 Acti9 NG125; ComPacT ComPact NSXm; TeSys TeSys GV4; ComPacT ComPacT INS; Acti9 Acti9 iSW; Acti9 Acti9 iSW-NA; Acti9 Acti9 iID; PowerPact PowerPact B
Type of measurementActive and reactive energy; Apparent energy; Active and reactive power; Apparent power; Current; Voltage; Power factor; Internal temperature; Frequency
Accuracy classClass 1 active energy conforming to IEC 61557-12; Class 2 reactive energy conforming to IEC 61557-12; Class 2 apparent energy conforming to IEC 61557-12; Class 1 active power conforming to IEC 61557-12; Class 2 reactive power conforming to IEC 61557-12; Class 2 apparent power conforming to IEC 61557-12; Class 1 current conforming to IEC 61557-12; Class 0.5 voltage conforming to IEC 61557-12; Class 1 power factor conforming to IEC 61557-12; Class 0.5 frequency conforming to IEC 61557-12
Metering typeActive energy E -a- IN/OUT 0...281 x 10exp(9) kWh at total per phase; Active energy E -a- IN/OUT 0...281 x 10exp(9) kWh at partial per phase; Active energy E -a- IN/OUT 0...281 x 10exp(9) kWh at 3-phase total; Active energy E -a- IN/OUT 0...281 x 10exp(9) kWh at 3-phase partial; Reactive energy E -rA- IN/OUT 0...281 x 10exp(9) kVARh at total per phase; Reactive energy E -rA- IN/OUT 0...281 x 10exp(9) kVARh at partial per phase; Reactive energy E -rA- IN/OUT 0...281 x 10exp(9) kVARh at 3-phase total; Reactive energy E -rA- IN/OUT 0...281 x 10exp(9) kVARh at 3-phase partial; Apparent energy E -apA- 0...281 x 10exp(9) kVAh at total per phase; Apparent energy E -apA- 0...281 x 10exp(9) kVAh at partial per phase; Apparent energy E -apA- 0...281 x 10exp(9) kVAh at 3-phase total; Apparent energy E -apA- 0...281 x 10exp(9) kVAh at 3-phase partial; Active power P, P1, P2, P3; Reactive power Q, Q1, Q2, Q3; Apparent power S, S1, S2, S3; Current I1, I2, I3; Calculated neutral current; Voltage U12, U23, U31; Voltage V1N, V2N, V3N; Frequency 45...65 Hz; Power factor at per phase; Power factor at total
Mounting locationTop or bottom
Mounting supportCables
Connection pitch27 mm
Product destinationSwitchboard
Event managementVoltage loss with measured current at voltage loss
Transmission support mediumRadio frequency 2.4…2.4835 GHz conforming to IEEE 802.15.4
Emission power10 mW
Form factorFlex
Mounting modeFree mounting
Electrical connection (voltage sensing & power supply)Removable spring terminal block
Cable cross section1 rigid cable 0.2…1.5 mm² without cable end; 1 stranded cable 0.2…2.5 mm² without cable end; 1 stranded cable 0.25…1.5 mm² with cable end
Wire stripping length11 mm
max power cable diameter17 mm
supply voltage100...277 V AC, +/- 20 %, phase to neutral; 173...480 V AC, +/- 20 %, phase to phase
Network frequency50 Hz; 60 Hz
Maximum power consumption3 VA
StandardsIEC 61557-12; IEC 61010-1; ETSI EN 301 489-1; IEC 61010-2-030; IEC 61326-1; ETSI EN 300 328
Product certificationsUL listed; IEC; DNV Marine
Height39 mm
Width91 mm
Depth62 mm
Product weight80 g
ColourWhite (RAL 9003)
Quality labelsCE
Directives2014/53/EU - radio equipment directive
Operating altitude0...2000 m
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-50…85 °C
Overvoltage categoryIV conforming to IEC 61010-1
Measurement categoryCategory IV conforming to IEC 61010-2-030
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK05
Pollution degree3
Relative humidity0…95 % at 55 °C conforming to IEC 60721-3-3
Vibration resistance3M4 conforming to IEC 60721-3-3
Electromagnetic compatibilityIndustrial electromagnetic environment conforming to IEC 61326-1; Radiated EMC conforming to ETSI EN 301 489-17; Electromagnetic emission conforming to IEC 62311
environmental characteristicsIndoor use
Country of originLV
Warranty (in months)18
Mounting methodPlug-in technique
ModelDirect measurement
Suitable forPurchase
Type of indicationNone
Power consumption3 W
Max. current (Imax)160 A
Width in number of modular spacings5
Type of meterElectronic
Degree of protection (IP)IP20
Energy typeEffective power and reactive power
Tariff typeOne-tariff
Escapement mechanismNo
CalibratedYes
ApprovalDomestic
Pulse outputNone
Pole typeFour conductor
Measurement type load profileNo
EEC40 signatureNo
With lock codeNo
Nominal current (In)160 A

Properties

MOQ1