| Manufacturer part number (MPN) | METSEPM8244 |
| EAN / GTIN | 3606480701979 |
| Sales unit | pcs |
| Range | PowerLogic |
| Product name | PowerLogic PM8000 |
| Product or component type | Power meter |
| Device short name | PM8244 |
| Market segment | Buildings large building cost management: billing: sub feeder; Buildings small building network management: main incomer; Buildings medium building network management: main incomer; Buildings large building network management: main incomer; Buildings large building network management: sub feeder; Buildings multi-site network management: main incomer; Buildings multi-site network management: sub feeder; Data center network management: main incomer; Data center network management: sub feeder; Healthcare network management: main incomer; Healthcare network management: sub feeder; Industry network management: main incomer; Industry network management: sub feeder; Utility: sub feeder |
| model type | Standard |
| Power quality analysis | conforming to EN 50160: 2010 compliance report; conforming to IEEE 519: 2014 compliance report; conforming to IEC 61000-4-30: class S power quality measurement; up to the 63rd harmonic; harmonic distortion; waveform capture; voltage sag and swell detection; programmablity (logic and math functions); conforming to IEC 62586 power quality monitoring; disturbance direction detection; rapid voltage change |
| Device application | WAGES metering; Power monitoring |
| Type of measurement | Current; Voltage; Frequency; Active and reactive power total; Apparent power total; Power factor total; Active and reactive power per phase, rms; Apparent power per phase, rms; Power factor per phase, rms |
| supply voltage | 90...415 V AC 45...65 Hz +/- 10 %; 110...415 V DC +/- 10 % |
| Network frequency | 50 Hz; 60 Hz |
| [In] rated current | 10 A; 5 A; 1 A |
| Poles description | 3P; 1P + N; 3P + N |
| Power consumption in VA | 16 VA at 230 V AC |
| Display type | Remote LCD display |
| Display resolution | 320 x 240 pixels QVGA |
| Sampling rate | 256 samples/cycle |
| Measurement current | 50…10000 mA |
| Analogue input type | Voltage (impedance 5 MOhm); Current (impedance 0.3 mOhm) |
| Measurement voltage | 57…400 V AC 42...69 Hz between phase and neutral; 100…690 V AC 42...69 Hz between phases |
| Frequency measurement range | 42…69 Hz |
| Number of inputs | 3 digital 30 V AC; 3 digital 60 V DC |
| Measurement accuracy | Current +/- 0.1 %; Voltage +/- 0.1 %; Active energy +/- 0.2 % |
| Accuracy class | Class 0.2S active energy conforming to IEC 62053-22; Class 0.2 active energy conforming to ANSI C12.20; Class 0.2 active power conforming to IEC 61557-12; Class 0.5S reactive energy conforming to IEC 62053-24; Class 0.5 power factor conforming to IEC 61557-12; Class 0.2 voltage conforming to IEC 61557-12; Class 0.2 current conforming to IEC 61557-12 |
| Number of outputs | 1 pulse |
| Information displayed | Voltage; Current; Frequency; Power; Energy consumption; Harmonic distortion |
| Communication port protocol | Modbus RTU at 115 kbauds - 2-wire; ION at 115 kbauds - 2-wire; DNP3; IEC 61850; Modbus TCP/IP; Ethernet Modbus TCP/IP daisy chain at 10/100 Mbit/s; RSTP 801.1d 2004 |
| Communication port support | ETHERNET; Screw terminal block: RS485 |
| Communication network type | IPv6 (internet protocol) |
| Data recording | Sequence of event recording; Event logs; Min/max of instantaneous values; Harmonics logs; Alarm logs; GPS synchronisation; Waveform logs; Data logs; Time stamping; Trending/forecasting; Sag and swell logs; 50 data recorders |
| Memory capacity | 512 MB |
| Web services | Customizable home page; File upload/download via FTP; File upload/download via SFTP; Web server; Alarm notification by e-mail; Viewing of captured waveform (FTP); Viewing of captured waveform (web); HTTPS server |
| Communication service | SMTP e-mail notification; RSTP support; NTP time synchronization; DHCP; PTP time synchronization |
| Cybersecurity | Password protection; Syslog protocol support; Port hardening; Robust security logs; Enable/disable communication ports |
| mounting mode | Flush-mounted; Clip-on |
| Mounting support | DIN rail meter device; Framework remote display |
| Provided equipment | Remote display |
| Installation category | III |
| Safety Construction | III400…690 V conforming to IEC 61010-1:ed. 3; III400…690 V conforming to EN 61010-1:ed. 3; III347…600 V conforming to UL 61010-1:ed. 3; III347…600 V conforming to CSA C22.2 No 61010-1:ed. 3 |
| Standards | IEC 62053-22; IEC 62053-24; IEC 62052-11; IEC 61557-12; IEEE 1588; IEC 62586-2; IEC 61326-1 |
| Product certifications | CE; CULus; N998 |
| Width | 90.5 mm |
| Depth | 90.8 mm |
| Height | 90.5 mm |
| Product weight | 528 g |
| Electromagnetic compatibility | Electrostatic discharge conforming to IEC 61000-4-2; Radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3; Electrical fast transient/burst immunity test conforming to IEC 61000-4-4; Surge immunity test conforming to IEC 61000-4-5; Conducted RF disturbances conforming to IEC 61000-4-6; Magnetic field at power frequency conforming to IEC 61000-4-8; Voltage dips and interruptions immunity test conforming to IEC 61000-4-11; Immunity to impulse waves conforming to IEC 61000-4-12; Conducted and radiated emissions conforming to EN 55022; Conducted and radiated emissions conforming to EN 55011; Conducted and radiated emissions conforming to FCC part 15; Conducted and radiated emissions conforming to ICES-003; Conducted RF disturbances (2...150 Hz) conforming to CLC/TR 50579; Surge withstand conforming to IEEE C37.90.1 |
| IP degree of protection | IP30 conforming to IEC 60529 |
| Relative humidity | 5…95 % |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -40…85 °C |
| Operating altitude | 3000 m |
| Compatibility code | PM8244 |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 13.800 cm |
| Package 1 Width | 14.000 cm |
| Package 1 Length | 36.800 cm |
| Package 1 Weight | 1.305 kg |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 4 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 6.212 kg |
| Unit Type of Package 3 | P12 |
| Number of Units in Package 3 | 32 |
| Package 3 Height | 45.000 cm |
| Package 3 Width | 80.000 cm |
| Package 3 Length | 120.000 cm |
| Package 3 Weight | 61.696 kg |
| Country of origin | CA |
| Warranty (in months) | 18 |
| Measured value memory | Yes |
| Power factor | Yes |
| Suitable for RJ plug | Yes |
| Step angle (cos phi) | Yes |
| Harmonics measurement | Yes |
| Pulse output | Electrical |
| Calibrated | Yes |
| Max. current (Imax) | 20 A |
| Measurement type load profile | Yes |
| With communication interface KNX | No |
| With communication interface M-Bus | No |
| With communication interface RS-485 | Yes |
| Model | Measurement transformer |
| Mounting method | DIN rail |
| Nominal current (In) | 5 A |
| Pole type | Three conductor/four conductor |
| Apparent power | Yes |
| Connectable conductor cross section solid-core | 1.31–5.26 mm² |
| Ampere meter | Yes |
| Reactive power meter | Yes |
| With rotational speed meter | No |
| Frequency meter | Yes |
| Pulse counter | No |
| Voltmeter | Yes |
| Effective power measurement device | Yes |
| Accuracy class active energy according to IEC 62053-22 | 0.2S |
| Sampling frequency | 25600 Hz |
| Number of voltage measurement inputs | 4 |
| Number of current measurement inputs | 8 |
| Voltage type (supply voltage) | AC/DC |
| Supply voltage AC 50 Hz | 90–415 V |
| Supply voltage AC 60 Hz | 90–415 V |
| Supply voltage DC | 110–415 V |
| Measuring range for frequency | 42–69 Hz |
| Display | None |
| Remote display | Yes |
| Number of digital inputs | 3 |
| Number of digital outputs | 1 |
| Number of Ethernet connections | 2 |
| Supporting protocol for IEC 61850 Ethernet | Yes |
| Supporting protocol for OPC UA PubSub | No |
| Supporting protocol for PROFIBUS | No |
| Supporting protocol for Modbus | Yes |
| Supporting protocol for PROFINET IO | No |
| Supporting protocol for other bus systems | Yes |
| With audit logging (audit log) | Yes |
| With firmware signature | No |
| With logging of security events (security event log) | Yes |
| With Role Based Access Control (RBAC) | No |
| Web server with HTTPS transfer protocol | Yes |