| Manufacturer part number (MPN) | BK325I |
| EAN / GTIN | 0731304120506 |
| Sales unit | pcs |
| Voltage | 230 V |
| Main input voltage | 230 V AC 1 phase |
| Input connection | IEC 60320 C14 |
| Maximum input current | 7 A |
| Switching current capacity | 7 A |
| Efficiency at full load | 180...266 V |
| Input frequency | 50/60 Hz +/- 3 Hz auto-sensing |
| Output voltage | 230 V AC 1 phase |
| Rated power in W | 195 W |
| Rated power in VA | 325 VA |
| Output connection | 3 IEC 60320 C13; 1 IEC 60320 C13 surge; 2 IEC 60320 |
| Type of USB power supply | None |
| Maximum configurable power in VA | 350 VA |
| Maximum configurable power in W | 210 W |
| Transfer time | 6 ms typical : 10 ms maximum |
| UPS topology | Standby |
| Waveform type | Stepped approximation to a sinewave |
| Output frequency | 47...63 Hz sync to mains; 50/60 Hz +/- 1 Hz unsynchronised |
| Replacement battery | RBC2 |
| Run Time | View Runtime Graph |
| Efficiency | View Efficiency Graph |
| Battery capacity | 7.0 Ah |
| Battery type | Lead-acid internal included |
| Control panel | LED Status display with on line : on battery |
| Alarm | Alarm when on battery : distinctive low battery alarm : overload continuous tone alarm |
| UPS connectivity | USB port |
| Surge energy rating | 310 J |
| Noise filtering | Full time multi-pole noise filtering : 5% IEEE surge light-through : zero clamping response time : meets UL 1449 |
| Number of rack unit | 0U |
| Number of cables | 1 |
| Color | Beige |
| Height | 165 mm |
| Width | 91 mm |
| Depth | 284 mm |
| Product weight | 5.73 kg |
| Mounting location | Front |
| Mounting preference | No preference |
| Mounting mode | Not rack-mountable |
| Two post mountable | 0 |
| USB compatible | Yes |
| Provided equipment | 2 x detachable IEC C13 to IEC C14 power cords; User manual |
| Number of power module filled slots | 0 |
| Number of power module free slots | 0 |
| Redundant | No |
| Range of product | Back-UPS |
| Product or component type | Uninterruptible power supply (UPS) |
| Product certification | C-Tick; CE; GOST; VDE |
| Standard | EN/IEC 62040-1:2019/A11:2021; EN/IEC 62040-2:2006/AC:2006; EN/IEC 62040-2:2018 |
| Ambient air temperature for operation | 0…40 °C |
| Ambient air temperature for storage | -15…45 °C |
| Storage altitude | 0…15240 m |
| Relative humidity | 0…95 % |
| Storage relative humidity | 0…95 % |
| Heat dissipation | 19 Btu/h |
| Operating altitude | 0...10000 ft |
| Battery voltage | 12 V |
| Extendable runtime | 0 |
| Included battery module | 0 |
| Empty battery slot | 0 |
| Typical recharge time | 6 h |
| RBC quantity | 1 |
| Battery life | 4…6 year(s) |
| Battery charging power | 14 W rated |
| Number of Units in Package 1 | 1 |
| Number of Units in Package 2 | 2 |
| Number of Units in Package 3 | 8 |
| Country of origin | PH |
| Warranty (in months) | 24 UPS|12 Battery |