| Manufacturer part number (MPN) | ABL8BUF24400 |
| EAN / GTIN | 3389119406819 |
| Sales unit | pcs |
| Package quantity | 60 pcs |
| Rated current | 40 A |
| Range of product | Phaseo |
| Product or component type | Buffer module |
| Input voltage | 24...28.8 V DC |
| Output voltage | (Uin-0.25) V in nominal mode DC; (Uin-1) V in buffer mode DC |
| Maximum output current | 40 A |
| Holding time | 0.1 s at 40 A; 6 s at 0.5 A |
| Input voltage limits | 22...30 V |
| Maximum power dissipation in W | 15 W |
| Activation threshold | (Uin-1) V and 22 V min |
| Charging time | 25 s |
| Number of output channels | 1 |
| Current consumption | 0.6 A on load; 0.1 mA no load; <= 40.6 A |
| Output protection type | Against overload, protection technology: > 45 A; Against short-circuits, protection technology: power-supplied mode, automatic reset; Against undervoltage, protection technology: tripping if U < 19 V |
| Connections - terminals | For input connection: screw type terminals, connection capacity: 2 x 0.5...2 x 10 mm² 20 AWG...8 AWG; For output connection: screw type terminals, connection capacity: 2 x 0.5...2 x 10 mm² 20 AWG...8 AWG; For diagnostic relay: removable screw terminal block, connection capacity: 1 x 2.5 mm² 14 AWG |
| Fixing mode | By clips on 35 mm symmetrical DIN rail, operating position: horizontal; By clips on 35 mm symmetrical DIN rail, operating position: vertical |
| Output coupling | Parallel |
| Operating altitude | 2000 m |
| Marking | CE |
| Name of test | Electrostatic discharges conforming to IEC 61000-4-2; Emission conforming to IEC 61000-6-3; Induced electromagnetic field conforming to IEC 61000-4-6 level 3; Radiated electromagnetic field conforming to IEC 61000-4-3 level 3; Rapid transient conforming to IEC 61000-4-4 level 3; Surge conforming to IEC 61000-4-5 level 2; Conducted/radiated emissions conforming to EN 55022 class B, 20 % |
| Local signalling | 1 LED (green) for buffer ready; 1 relay for buffer ready |
| Product weight | 1.2 kg |
| Product certifications | RCM; EAC |
| Standards | UL 508; CSA C22.2 No 60950-1 |
| Ambient air temperature for operation | -25…60 °C |
| Ambient air temperature for storage | -40…85 °C |
| Environmental characteristic | EMC conforming to IEC 61000-6-3; EMC conforming to IEC 61000-6-2; Safety conforming to IEC 60950-1; Safety conforming to EN/IEC 61204-3 |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Dielectric strength | 500 V between input and ground; 500 V between output and ground |
| Overvoltage category | Class II conforming to VDE 0106-1 |
| Relative humidity | 0…90 % during operation; 0…95 % during storage |
| MTBF reliability | 1119603 H at 24 V DC with UTE C80-810 calculation method |
| Vibration resistance | 2 gn (f= 11.9…150 Hz) conforming to IEC 61131-2; 3.5 mm (f= 3…11.9 Hz) conforming to IEC 61131-2 |
| Number of Units in Package 1 | 1 |
| Number of Units in Package 2 | 60 |
| Country of origin | PH |
| Warranty (in months) | 18 |