Schneider Electric standard analog input kit STB - 4..20 mA - 4 I - 15 bits + sign STBACI8320K

Schneider Electric · Tools · Hand Tools · France · se.com
Part Number
STBACI8320K  ·  HS 8538.90
Schneider Electric standard analog input kit STB - 4..20 mA - 4 I - 15 bits + sign STBACI8320K

Schneider Electric STBACI8320K STB kit 4 in analog, 4-20mA, 16bit.

Technical Specifications

Manufacturer part number (MPN)STBACI8320K
EAN / GTIN3595863948745
Sales unitpcs
Output signal4–20 mA
Range of productModicon STB distributed I/O solution
Product or component typeStandard analog input kit
Kit compositionSTBACI8320 module; STBXBA2000 base; STBXTS1100, 6-terminal screw type connector; STBXTS2100, 6-terminal spring clamp connector
Product compatibilityPower distribution module STBPDT3100/3105; Mounting base STBXBA2000
Analogue input number4
Type of filterSingle low pass input filter 985 Hz
Analogue output number0
Absolute maximum input25 mA/50 V
Cold swappingYes
Data formatIEC 61131-2; EN 61131-2
Update time80 ms
Integral linearity+/- 0.05 %FS
Differential linearityMonotonic
Maximum supply current for sensors25 mA per input channels
Absolute accuracy error+/- 0.4 % of full scale 25 °C
Addressing requirement8 input words
SupplyPower distribution module
Analogue input typeCurrent 0...20 mA; Current 4...20 mA
Analogue input resolution15 bits + sign
Input impedance250 Ohm
Input protection typeProtected against short-circuit
Temperature drift+/-0.005 %/°C
Typical current consumption95 mA at 5 V DC for logic bus
Isolation between channels and bus1780 Vrms for 1 minute
Hot swapping fallbackYes for standard NIMs
Local signalling1 LED green for module status (RDY); 1 LED red for module error (ERR)
Height18.4 mm
Width128.3 mm
Depth70 mm
Overvoltage categoryII
IP degree of protectionIP20
MarkingCE
Product certificationsCSA; C-Tick; ATEX Cat 3G; FM Class 1 Division 2; UL
Ambient air temperature for operation-25…70 °C (without derating)
Ambient air temperature for storage-40…85 °C without derating
Relative humidity95 % at 60 °C without condensation
Operating altitude2000 m
Pollution degree2
Vibration resistance+/-0.35 mm (f = 10…58 Hz); 3 gn (f = 58…150 Hz) on 35 mm DIN rail; 5 gn (f = 58…150 Hz) on 35 mm DIN rail
Shock resistance30 gn for 11 ms conforming to IEC 88 reference 2-27
Number of Units in Package 11
Number of Units in Package 228
Number of Units in Package 3448
Country of originID
Warranty (in months)18
Certified for UL hazardous location division 1No
Certified for UL hazardous location division 2No
Certified for UL hazardous location group A (acetylene)No
Certified for UL hazardous location group B (hydrogen)No
Certified for UL hazardous location group C (ethylene)No
Certified for UL hazardous location group D (propane)No
Certified for UL hazardous location group E (metal dusts)No
Certified for UL hazardous location class INo
Certified for UL hazardous location class IINo
Certified for UL hazardous location class IIINo
Supporting protocol for EtherCATNo
Supply voltage DC24 V
Voltage type (supply voltage)AC/DC
Input, currentYes
Input, voltageNo
Input, resistorNo
Input, resistance thermometerNo
Input, thermocoupleNo
Input signal, configurableYes
Resolution of the analogue inputs15 Bit
Output, currentNo
Output, voltageNo
Output signal configurableNo
Resolution of the analogue outputs15 Bit
Number of analogue inputs4
Analogue inputs configurableYes
Analogue outputs configurableNo
Supporting protocol for TCP/IPNo
Supporting protocol for PROFIBUSNo
Supporting protocol for CANNo
Supporting protocol for INTERBUSNo
Supporting protocol for ASINo
Supporting protocol for KNXNo
Supporting protocol for ModbusNo
Supporting protocol for Data-HighwayNo
Supporting protocol for DeviceNetNo
Supporting protocol for SUCONETNo
Supporting protocol for LONNo
Supporting protocol for PROFINET IONo
Supporting protocol for PROFINET CBANo
Supporting protocol for SERCOSNo
Supporting protocol for Foundation FieldbusNo
Supporting protocol for EtherNet/IPNo
Supporting protocol for AS-Interface Safety at WorkNo
Supporting protocol for DeviceNet SafetyNo
Supporting protocol for INTERBUS-SafetyNo
Supporting protocol for PROFIsafeNo
Supporting protocol for SafetyBUS pNo
Supporting protocol for other bus systemsNo
Radio standard BluetoothNo
Radio standard WLAN 802.11No
Radio standard GPRSNo
Radio standard GSMNo
Mobile communications standard 3G (UMTS)No
IO link masterNo
System accessoryYes
Degree of protection (IP)IP20
Type of electric connectionScrew connection
Fieldbus connection over separate bus coupler possibleYes
Suitable for rail mountingYes
Wall mounting/direct mountingNo
Front built-in possibleNo
Rack-assembly possibleYes
Suitable for safety functionsNo
SIL according to IEC 61508None
Performance level according to EN ISO 13849-1None
Appendant operation agent (Ex ia)No
Explosion safety category for gasATEX gas-ex-protection, Cat. 3G

Properties

MOQ1

Cross-References

Attached Documents