| Manufacturer part number (MPN) | STBDDO3705KS |
| EAN / GTIN | 3595863932638 |
| Sales unit | pcs |
| Package quantity | 34 pcs |
| Voltage | 24 V DC |
| Range of product | Modicon STB distributed I/O solution |
| Product or component type | Basic digital output kit |
| Kit composition | STBDDO3705 module; STBXBA3000 base; STBXTS1180, 18-terminal screw type connector |
| Product compatibility | Power distribution module STBPDT3100/3105; I/O base STBXBA3000 |
| Range compatibility | Logic/motion controller - Modicon M262; Modicon M580; Third party |
| Device application | Industrial application |
| Discrete output number | 16 |
| Discrete output logic | Positive logic (source) |
| Discrete output voltage | 24 V DC for solid state |
| Discrete output current | 500 mA |
| Response time on output | < 10 ms off to on; < 10 ms on to off |
| Maximum leakage current | 0.4 mA 30 V DC at state 0 |
| Typical current consumption | 135 mA at 5 V DC |
| Electrical connection | Screw terminal |
| Height | 13.9 mm |
| Width | 128.3 mm |
| Depth | 70 mm |
| Product weight | 0.086 kg |
| IP degree of protection | IP20 |
| Marking | CE |
| Product certifications | UL; CSA; FM Class 1 Division 2 |
| Standards | IEC 61131-2 |
| Relative humidity | 95 % at 60 °C without condensation |
| Operating altitude | <= 2000 m |
| Pollution degree | 2 |
| Shock resistance | 30 gn for 11 ms conforming to IEC 88 reference 2-27 |
| Number of Units in Package 1 | 1 |
| Number of Units in Package 2 | 20 |
| Number of Units in Package 3 | 320 |
| Country of origin | ID |
| Warranty (in months) | 18 |
| Certified for UL hazardous location division 1 | No |
| Certified for UL hazardous location division 2 | No |
| Certified for UL hazardous location group A (acetylene) | No |
| Certified for UL hazardous location group B (hydrogen) | No |
| Certified for UL hazardous location group C (ethylene) | No |
| Certified for UL hazardous location group D (propane) | No |
| Certified for UL hazardous location group E (metal dusts) | No |
| Certified for UL hazardous location class I | No |
| Certified for UL hazardous location class II | No |
| Certified for UL hazardous location class III | No |
| Supporting protocol for EtherCAT | No |
| Supply voltage DC | 24 V |
| Voltage type (supply voltage) | DC |
| Number of digital outputs | 16 |
| Digital inputs configurable | No |
| Digital outputs configurable | Yes |
| Input current at signal 1 | 0.4 mA |
| Permitted voltage at input | 19.2–30 V |
| Type of voltage (input voltage) | DC |
| Output current | 0.5 A |
| Permitted voltage at output | 24 V |
| Type of output voltage | DC |
| Short-circuit protection, outputs available | Yes |
| With optical interface | No |
| Supporting protocol for TCP/IP | Yes |
| Supporting protocol for PROFIBUS | Yes |
| Supporting protocol for CAN | Yes |
| Supporting protocol for INTERBUS | Yes |
| Supporting protocol for ASI | No |
| Supporting protocol for KNX | No |
| Supporting protocol for Modbus | Yes |
| Supporting protocol for Data-Highway | No |
| Supporting protocol for DeviceNet | Yes |
| Supporting protocol for SUCONET | No |
| Supporting protocol for LON | No |
| Supporting protocol for PROFINET IO | No |
| Supporting protocol for PROFINET CBA | No |
| Supporting protocol for SERCOS | No |
| Supporting protocol for Foundation Fieldbus | No |
| Supporting protocol for EtherNet/IP | Yes |
| Supporting protocol for AS-Interface Safety at Work | No |
| Supporting protocol for DeviceNet Safety | No |
| Supporting protocol for INTERBUS-Safety | No |
| Supporting protocol for PROFIsafe | No |
| Supporting protocol for SafetyBUS p | No |
| Supporting protocol for other bus systems | No |
| Radio standard Bluetooth | No |
| Radio standard WLAN 802.11 | No |
| Radio standard GPRS | No |
| Radio standard GSM | No |
| Mobile communications standard 3G (UMTS) | No |
| IO link master | No |
| System accessory | Yes |
| Degree of protection (IP) | IP20 |
| Type of electric connection | Screw connection |
| Time delay at signal change | 2 ms |
| Fieldbus connection over separate bus coupler possible | Yes |
| Suitable for rail mounting | No |
| Wall mounting/direct mounting | No |
| Front built-in possible | No |
| Rack-assembly possible | Yes |
| Suitable for safety functions | No |
| SIL according to IEC 61508 | None |
| Performance level according to EN ISO 13849-1 | None |
| Appendant operation agent (Ex ia) | No |
| Explosion safety category for gas | None |
| Explosion safety category for dust | None |