Zelio Logic SR3 Modbus slave m (SR3MBU01BD)

Schneider Electric · Control & Automation · PLCs · France · se.com
Part Number
SR3MBU01BD  ·  HS 8538.90
Zelio Logic SR3 Modbus slave m (SR3MBU01BD)

Schneider Electric SR3MBU01BD Zelio Logic SR3 Modbus slave module.

Technical Specifications

Manufacturer part number (MPN)SR3MBU01BD
EAN / GTIN3389110840339
Sales unitpcs
Package quantity48 pcs
Range of productZelio Logic
Product or component typeModbus slave communication module
Wiring mode2 or 4 wires
Product compatibilityAll modules with 24 V supply SR3 B...BD
Communication port protocolModbus
Communication port supportRS485
Electrical connection1 connector RJ45
Transmission frameRTU; ASCII
Transmission rate1200 bauds; 9600 bauds; 38400 bauds; 19200 bauds; 57600 bauds; 28800 bauds; 2400 bauds; 4800 bauds
ParityNo; Odd; Even
Number of addresses1…247
Programming languageFBD; Ladder
Connections - terminalsScrew terminals, 1 x 0.25...1 x 2.5 mm² (24 AWG...14 AWG) semi-solid; Screw terminals, 1 x 0.25...1 x 2.5 mm² (24 AWG...14 AWG) solid; Screw terminals, 2 x 0.25...2 x 1.5 mm² (23 AWG...16 AWG) solid; Screw terminals, 1 x 0.25...1 x 2.5 mm² (24 AWG...14 AWG) flexible with cable end; Screw terminals, 2 x 0.25...2 x 0.75 mm² (24 AWG...18 AWG) flexible with cable end
Tightening torque0.5 N.m
Local signalling1 LED for communication; 1 LED for power ON
Product weight0.11 kg
Product certificationsGOST; CSA; GL; C-Tick; UL
StandardsIEC 60068-2-27 Ea; IEC 61000-4-3; IEC 61000-4-4 level 3; IEC 61000-4-2 level 3; IEC 61000-4-5; IEC 60068-2-6 Fc
IP degree of protectionIP20 (terminal block) conforming to IEC 60529; IP40 (front panel) conforming to IEC 60529
Environmental characteristicEMC directive conforming to IEC 61000-6-2; EMC directive conforming to IEC 61000-6-3; EMC directive conforming to IEC 61000-6-4; EMC directive conforming to IEC 61131-2 zone B; Low voltage directive conforming to IEC 61131-2
Disturbance radiated/conductedClass B conforming to EN 55022-11 group 1
Pollution degree2 conforming to IEC 61131-2
Ambient air temperature for operation-20…40 °C conforming to IEC 60068-2-1 and IEC 60068-2-2; -20…55 °C conforming to IEC 60068-2-1 and IEC 60068-2-2
Ambient air temperature for storage-40…70 °C
Operating altitude2000 m
Maximum altitude transport3048 m
Relative humidity95 % without condensation or dripping water
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height6.000 cm
Package 1 Width6.500 cm
Package 1 Length11.000 cm
Package 1 Weight102.000 g
Unit Type of Package 2S03
Number of Units in Package 248
Package 2 Height30.000 cm
Package 2 Width30.000 cm
Package 2 Length40.000 cm
Package 2 Weight5.470 kg
Country of originFR
Warranty (in months)18
Power consumption1.1 W
Certified for UL hazardous location division 1No
Certified for UL hazardous location division 2No
Certified for UL hazardous location group A (acetylene)No
Certified for UL hazardous location group B (hydrogen)No
Certified for UL hazardous location group C (ethylene)No
Certified for UL hazardous location group D (propane)No
Certified for UL hazardous location group E (metal dusts)No
Certified for UL hazardous location class INo
Certified for UL hazardous location class IINo
Certified for UL hazardous location class IIINo
Supporting protocol for EtherCATNo
Supply voltage DC24 V
Voltage type (supply voltage)DC
Switching current8 A
With relay outputNo
With optical interfaceNo
Supporting protocol for TCP/IPYes
Supporting protocol for PROFIBUSNo
Supporting protocol for CANNo
Supporting protocol for INTERBUSNo
Supporting protocol for ASINo
Supporting protocol for KNXNo
Supporting protocol for ModbusYes
Supporting protocol for Data-HighwayNo
Supporting protocol for DeviceNetNo
Supporting protocol for SUCONETNo
Supporting protocol for LONNo
Supporting protocol for PROFINET IONo
Supporting protocol for PROFINET CBANo
Supporting protocol for SERCOSNo
Supporting protocol for Foundation FieldbusNo
Supporting protocol for EtherNet/IPNo
Supporting protocol for AS-Interface Safety at WorkNo
Supporting protocol for DeviceNet SafetyNo
Supporting protocol for INTERBUS-SafetyNo
Supporting protocol for PROFIsafeNo
Supporting protocol for SafetyBUS pNo
Supporting protocol for other bus systemsNo
Radio standard BluetoothNo
Radio standard WLAN 802.11No
Radio standard GPRSNo
Radio standard GSMNo
Mobile communications standard 3G (UMTS)No
IO link masterNo
RedundancyNo
With displayNo
Degree of protection (IP)IP20
Basic deviceYes
ExpandableNo
Expansion deviceYes
With time switch clockNo
Suitable for rail mountingYes
Wall mounting/direct mountingNo
Front built-in possibleYes
Rack-assembly possibleNo
Suitable for safety functionsNo
SIL according to IEC 61508None
Performance level according to EN ISO 13849-1None
Appendant operation agent (Ex ia)No
Explosion safety category for gasNone
Explosion safety category for dustNone
Width35 mm
Height90 mm
Depth57 mm

Properties

MOQ1