| Manufacturer part number (MPN) | SR3XT43BD |
| EAN / GTIN | 3389119203968 |
| Sales unit | pcs |
| Package quantity | 48 pcs |
| Voltage | 24 V DC |
| Range of product | Zelio Logic |
| Product or component type | Analogue I/O extension module |
| Analogue input number | 2 |
| Analogue input type | Common mode |
| Analogue input range | 0...10 V; 0...20 mA; -25...125 °C |
| Temperature probe type | Pt 100, 3-wire conforming to IEC 751 |
| Maximum permissible voltage | 30 V for analogue input circuit |
| [Imp] maximum permanent current | 30 mA for analogue input circuit |
| Analogue input resolution | 10 bits on the input range |
| Input impedance | 18 kOhm, input range: 0...10 V for analogue input circuit; 247 Ohm, input range: 0...20 mA for analogue input circuit |
| Analogue output number | 2 |
| Analogue output range | 0...10 V |
| Analogue output resolution | 10 bits on the output range |
| Load type | Resistive load for analogue output |
| Maximum load current | 10 mA for analogue output |
| Short-circuit protection | With analogue output |
| LSB value | 0.15 °C, - 25...125 °C for analogue input circuit; 20 µA, 0...20 mA for analogue input circuit; 9.8 mV, 0...10 V for analogue input circuit; 9.8 mV, 0...10 V for analogue output |
| Conversion time | Smart relay cycle time for analogue input circuit; Smart relay cycle time for analogue output |
| Conversion error | +/- 1 % of the full scale value, input range: 0...10 V (25 °C) for analogue output; +/- 1 % of the full scale value, input range: 0...10 V (55 °C) for analogue output; +/- 1 %, input range: 0...10 V (25 °C) for analogue input circuit; +/- 1 %, input range: 0...10 V (55 °C) for analogue input circuit; +/- 1 %, input range: 0...20 mA (25 °C) for analogue input circuit; +/- 1 %, input range: 0...20 mA (55 °C) for analogue input circuit; +/- 1.5 °C, input range: - 25...125 °C (25 °C) for analogue input circuit; +/- 1.5 °C, input range: - 25...125 °C (55 °C) for analogue input circuit |
| Repeat accuracy | < +/- 0.3 °C, input range: - 25...125 °C at 25 °C for analogue input circuit; <= +/- 1 %, input range: 0...10 V at 25 °C for analogue input circuit; <= +/- 1 %, input range: 0...10 V at 55 °C for analogue output; <= +/- 1 %, input range: 0...20 mA at 25 °C for analogue input circuit |
| Operating distance | 10 m with screened cable for analogue input circuit; 10 m with screened cable for analogue output |
| Reverse polarity protection | Analogue input circuit: with |
| Connections - terminals | Screw terminals, 1 x 0.25...1 x 2.5 mm² (24 AWG...14 AWG) semi-solid; Screw terminals, 1 x 0.25...1 x 2.5 mm² (24 AWG...14 AWG) solid; Screw terminals, 2 x 0.25...2 x 1.5 mm² (23 AWG...16 AWG) solid; Screw terminals, 1 x 0.25...1 x 2.5 mm² (24 AWG...14 AWG) flexible with cable end; Screw terminals, 2 x 0.25...2 x 0.75 mm² (24 AWG...18 AWG) flexible with cable end |
| Tightening torque | 0.5 N.m |
| Product weight | 0.11 kg |
| Product certifications | GOST; UL; C-Tick; CSA |
| Standards | IEC 61000-4-12; IEC 61000-4-5; IEC 61000-4-3; IEC 61000-4-4 level 3; IEC 61000-4-6 level 3; IEC 61000-4-2 level 3; IEC 60068-2-6 Fc; IEC 61000-4-11; IEC 60068-2-27 Ea |
| IP degree of protection | IP20 (terminal block) conforming to IEC 60529; IP40 (front panel) conforming to IEC 60529 |
| Environmental characteristic | EMC directive conforming to IEC 61000-6-2; EMC directive conforming to IEC 61000-6-3; EMC directive conforming to IEC 61000-6-4; EMC directive conforming to IEC 61131-2 zone B; Low voltage directive conforming to IEC 61131-2 |
| Disturbance radiated/conducted | Class B conforming to IEC 55022-11 Group 1 |
| Pollution degree | 2 conforming to IEC 61131-2 |
| Ambient air temperature for operation | -20…40 °C conforming to IEC 60068-2-1 and IEC 60068-2-2; -20…55 °C conforming to IEC 60068-2-1 and IEC 60068-2-2 |
| Ambient air temperature for storage | -40…70 °C |
| Operating altitude | 2000 m |
| Maximum altitude transport | 3048 m |
| Relative humidity | 95 % without condensation or dripping water |
| Number of Units in Package 1 | 1 |
| Number of Units in Package 2 | 48 |
| Country of origin | FR |
| Warranty (in months) | 18 |
| Power consumption | 1.1 W |
| Certified for UL hazardous location division 1 | No |
| Certified for UL hazardous location division 2 | No |
| Certified for UL hazardous location group A (acetylene) | No |
| Certified for UL hazardous location group B (hydrogen) | No |
| Certified for UL hazardous location group C (ethylene) | No |
| Certified for UL hazardous location group D (propane) | No |
| Certified for UL hazardous location group E (metal dusts) | No |
| Certified for UL hazardous location class I | No |
| Certified for UL hazardous location class II | No |
| Certified for UL hazardous location class III | No |
| Supporting protocol for EtherCAT | No |
| Supply voltage DC | 24 V |
| Voltage type (supply voltage) | DC |
| Switching current | 0.02 A |
| Number of analogue inputs | 2 |
| Number of analogue outputs | 1 |
| With relay output | No |
| With optical interface | No |
| Supporting protocol for TCP/IP | No |
| Supporting protocol for PROFIBUS | No |
| Supporting protocol for CAN | No |
| Supporting protocol for INTERBUS | No |
| Supporting protocol for ASI | No |
| Supporting protocol for KNX | No |
| Supporting protocol for Modbus | No |
| Supporting protocol for Data-Highway | No |
| Supporting protocol for DeviceNet | No |
| Supporting protocol for SUCONET | No |
| Supporting protocol for LON | No |
| Supporting protocol for PROFINET IO | No |
| Supporting protocol for PROFINET CBA | No |
| Supporting protocol for SERCOS | No |
| Supporting protocol for Foundation Fieldbus | No |
| Supporting protocol for EtherNet/IP | No |
| Supporting protocol for AS-Interface Safety at Work | No |
| Supporting protocol for DeviceNet Safety | No |
| Supporting protocol for INTERBUS-Safety | No |
| Supporting protocol for PROFIsafe | No |
| Supporting protocol for SafetyBUS p | No |
| Supporting protocol for other bus systems | No |
| Radio standard Bluetooth | No |
| Radio standard WLAN 802.11 | No |
| Radio standard GPRS | No |
| Radio standard GSM | No |
| Mobile communications standard 3G (UMTS) | No |
| IO link master | No |
| Redundancy | No |
| With display | No |
| Degree of protection (IP) | IP20 |
| Basic device | Yes |
| Expandable | No |
| Expansion device | Yes |
| With time switch clock | No |
| Suitable for rail mounting | Yes |
| Wall mounting/direct mounting | Yes |
| Front built-in possible | Yes |
| Rack-assembly possible | No |
| Suitable for safety functions | No |
| SIL according to IEC 61508 | None |
| Performance level according to EN ISO 13849-1 | None |
| Appendant operation agent (Ex ia) | No |
| Explosion safety category for gas | None |
| Explosion safety category for dust | None |
| Width | 35 mm |
| Height | 90 mm |
| Depth | 59.5 mm |