| Manufacturer part number (MPN) | TM3XTYS4 |
| EAN / GTIN | 3606480611636 |
| Sales unit | pcs |
| Package quantity | 42 pcs |
| Range of product | Modicon TM3 |
| Product or component type | Parallel interface module |
| Product specific application | TeSys U |
| [Us] rated supply voltage | 24 V DC by external supply (- 15...20 %) |
| Number of input channels | 12 |
| Number of output channels | 8 |
| Range compatibility | Modicon M221; Modicon M251; Modicon M241; Modicon M262 |
| Current consumption | 5 mA at 5 V DC via bus connector at state on; 35 mA at 5 V DC via bus connector at state off; 0 mA at 24 V DC via bus connector at state on; 10 mA at 24 V DC via bus connector at state off; 1200 mA at 24 V DC external power supply at state on |
| Input voltage limits | 19.2...28.8 V per input |
| Input current limits | 5 mA per input |
| Response time | < 10 ms turn-on for input; < 10 ms turn-off for input |
| Output voltage | 24 V DC for transistor output |
| Maximum load current | 800 mA per channel in starting mode during 100 ms; 300 mA per channel in normal mode |
| Insulation | Between the RJ45 connectors and internal logic at 500 V AC; Non-insulated between RJ45 connectors |
| Output protection type | Against overload, protection technology: current limiter |
| Reset | Automatic reset |
| Local signalling | 3 LEDs green for input status per channel; 2 LEDs green for output status per channel |
| Electrical connection | 3 x 2.5 mm² removable screw terminal block with pitch 5.08 mm adjustment for connecting the 24 V DC power supply; 4 RJ45 connectors for connecting the motor starters |
| Mounting support | Top hat type TH35-15 rail conforming to IEC 60715; Top hat type TH35-7.5 rail conforming to IEC 60715; plate or panel with fixing kit |
| Height | 90 mm |
| Depth | 85 mm |
| Width | 30 mm |
| Product weight | 0.115 kg |
| DC supply voltage | 24 V |
| Product certifications | CE; cULus; UKCA; RCM; EAC |
| Marking | CE |
| Resistance to electrostatic discharge | 8 kV in air conforming to EN/IEC 61000-4-2; 4 kV on contact conforming to EN/IEC 61000-4-2 |
| Resistance to electromagnetic fields | 10 V/m 80 MHz...1 GHz conforming to EN/IEC 61000-4-3; 3 V/m 1.4 GHz...2 GHz conforming to EN/IEC 61000-4-3; 1 V/m 2 GHz...3 GHz conforming to EN/IEC 61000-4-3 |
| Resistance to magnetic fields | 30 A/m 50/60 Hz conforming to EN/IEC 61000-4-8 |
| Resistance to fast transients | 1 kV for input conforming to EN/IEC 61000-4-4; 1 kV for output conforming to EN/IEC 61000-4-4 |
| Surge withstand | 1 kV input common mode conforming to EN/IEC 61000-4-5; 1 kV output common mode conforming to EN/IEC 61000-4-5 |
| Resistance to conducted disturbances | 10 V 0.15...80 MHz conforming to EN/IEC 61000-4-6; 3 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL) |
| Electromagnetic emission | Radiated emissions - test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz conforming to EN/IEC 55011; Radiated emissions - test level: 47 dBμV/m QP class A ( 10 m) at 230…1000 MHz conforming to EN/IEC 55011 |
| Ambient air temperature for operation | -10…35 °C vertical installation; -10…55 °C horizontal installation |
| Ambient air temperature for storage | -25…70 °C |
| Relative humidity | 10…95 %, without condensation (in operation); 10…95 %, without condensation (in storage) |
| IP degree of protection | IP20 with protective cover in place |
| Pollution degree | 2 |
| Operating altitude | 0...2000 m |
| Storage altitude | 0…3000 m |
| Vibration resistance | 3.5 mm at 5…8.4 Hz on DIN rail; 3 gn at 8.4…150 Hz on DIN rail; 3.5 mm at 5…8.4 Hz on panel; 3 gn at 8.4…150 Hz on panel |
| Shock resistance | 15 gn for 11 ms |
| Number of Units in Package 1 | 1 |
| Number of Units in Package 2 | 42 |
| Number of Units in Package 3 | 504 |
| Country of origin | TW |
| Warranty (in months) | 18 |
| Redundancy | No |
| Suitable for counting | No |
| Suitable for weighing | No |
| Suitable for temperature control | No |
| Suitable for welding control | No |
| Suitable for pressure control | No |
| Suitable for NC | No |
| Suitable for electronic positioning | No |
| Suitable for CNC | No |
| Suitable for SSI | No |
| Suitable for incremental data detection | No |
| Suitable for detection absolute value | No |
| Suitable for flux controller | No |
| Suitable for flux measurement | No |
| Suitable for path controller | No |
| Suitable for cam controller | No |
| Suitable for multi-axis control | No |
| Suitable for single-axis controller | No |
| Suitable for multi-axis positioning | No |
| Suitable for single-axis positioning | No |
| Suitable for safety functions | No |
| SIL according to IEC 61508 | None |
| Performance level according to EN ISO 13849-1 | None |
| Appendant operation agent (Ex ia) | No |
| Explosion safety category for gas | None |
| Explosion safety category for dust | None |