| Manufacturer part number (MPN) | TM3TM3 |
| EAN / GTIN | 3606480649042 |
| Sales unit | pcs |
| Package quantity | 42 pcs |
| Range of product | Modicon TM3 |
| Product or component type | Input/output analog module |
| Range compatibility | Modicon M221; Modicon M241; Modicon M251; Modicon M262 |
| Analogue input number | 2 |
| Analogue output number | 1 |
| Analogue input type | Current 4...20 mA; Current 0...20 mA; Voltage 0...10 V; Voltage - 10...10 V; Thermocouple - 200...1000 °C thermocouple J; Thermocouple - 200...1300 °C thermocouple K; Thermocouple 0...1760 °C thermocouple R; Thermocouple 0...1760 °C thermocouple S; Thermocouple 0...1820 °C thermocouple B; Thermocouple - 200...400 °C thermocouple T; Thermocouple - 200...1300 °C thermocouple N; Thermocouple - 200...800 °C thermocouple E; Thermocouple 0...2315 °C thermocouple C; Temperature probe - 60...180 °C Ni 100/Ni 1000; Temperature probe - 200...850 °C Pt 100; Temperature probe - 200...600 °C Pt 1000 |
| Analogue input resolution | 16 bits; 15 bits + sign |
| Permissible continuous overload | 13 V, analogue input type: voltage; 40 mA, analogue input type: current |
| Stabilisation time | 1 ms |
| Input impedance | = 1 MOhm |
| Sampling duration | 10 ms |
| Analogue output type | Current: 4...20 mA; Current: 0...20 mA; Voltage: 0...10 V; Voltage: - 10...10 V |
| Conversion time | 100 ms + 100 ms per channel + 1 controller cycle time for analogue input thermocouple |
| Absolute accuracy error | +/- 6 °C at 25 °C for thermocouple R, S 0...200 °C; +/- 0.4 % of full scale at 25 °C for thermocouple K - 200...0 °C; +/- 0.4 % of full scale at 25 °C for thermocouple J - 200...0 °C; +/- 0.4 % of full scale at 25 °C for thermocouple E - 200...0 °C; +/- 0.4 % of full scale at 25 °C for thermocouple T - 200...0 °C; +/- 0.4 % of full scale at 25 °C for thermocouple N - 200...0 °C; +/- 0.1 % of full scale at 25 °C for analogue input voltage/current; +/- 0.1 % of full scale at 25 °C for thermocouple C 0...2315 °C; +/- 0.1 % of full scale at 25 °C for Pt 100/Pt 1000, Ni 100/ Ni 1000 temperature probe; +/- 0.1 % of full scale at 25 °C for thermocouple R, S 200...1760 °C; +/- 0.1 % of full scale at 25 °C for thermocouple B 300...1820 °C; +/- 0.1 % of full scale at 25 °C for thermocouple K 0...1300 °C; +/- 0.1 % of full scale at 25 °C for thermocouple J 0...1000 °C; +/- 0.1 % of full scale at 25 °C for thermocouple E 0...800 °C; +/- 0.1 % of full scale at 25 °C for thermocouple T 0...400 °C; +/- 0.1 % of full scale at 25 °C for thermocouple N 0...1300 °C; +/- 0.1 % of full scale at 25 °C for analogue output voltage/current |
| Repeat accuracy | +/-0.5 %FS for input |
| Output ripple | 20 mV |
| Cross talk | <= 1 LSB |
| Type of cable | Twisted shielded pairs cable <30 m for input/output circuit |
| Electrical connection | 11 x 2.5 mm² removable screw terminal block with pitch 5.08 mm adjustment for inputs, outputs and supply |
| LSB value | 0.15 mV, 0...10 V; 0.30 mV, - 10...10 V; 0.30 µA, 0...20 mA; 0.244 µA, 4...20 mA; 0.1 °C; 2.44 mV, 0...10 V; 4.88 mV, - 10...10 V; 4.88 µA, 0...20 mA; 3.91 µA, 4...20 mA |
| Insulation | Between input and supply at 1500 V AC; Between input and internal logic at 500 V AC; Between output and supply at 1500 V AC; Between output and internal logic at 500 V AC |
| Immunity to microbreaks | 10 ms |
| Load impedance ohmic | 1 kOhm voltage; 300 Ohm current |
| load type | Resistive |
| Temperature drift | +/- 0.006 %FS/°C |
| Non-linearity | +/- 0.01 %FS, analogue output type: analog output; +/- 0.1 %FS, analogue input type: analog input |
| Typical current consumption | 55 mA at 24 V DC no load; 55 mA at 5 V DC no load; 60 mA at 5 V DC full load; 80 mA at 24 V DC full load |
| Local signalling | 1 LED green for PWR |
| Mounting support | Top hat type TH35-15 rail conforming to IEC 60715; Top hat type TH35-7.5 rail conforming to IEC 60715; plate or panel with fixing kit |
| Height | 90 mm |
| Width | 23.6 mm |
| Depth | 70 mm |
| Product weight | 0.115 kg |
| IP degree of protection | IP20 |
| Marking | CE |
| Product certifications | CE; UKCA; RCM; EAC; CULus; CULus HazLoc |
| Standards | IEC 61131-2 |
| Electromagnetic emission | Radiated emissions - test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz conforming to IEC 55011; Radiated emissions - test level: 47 dBμV/m QP class A ( 10 m) at 230…1000 MHz conforming to IEC 55011 |
| Ambient air temperature for operation | -10…55 °C (horizontal installation); -10…35 °C (vertical installation) |
| Ambient air temperature for storage | -25…70 °C |
| Relative humidity | 10…95 % without condensation |
| Operating altitude | 0...2000 m |
| Pollution degree | 2 |
| Vibration resistance | 3.5 mm (f = 5…8.4 Hz) on DIN rail; 3 gn (f = 8.4…150 Hz) on DIN rail |
| Shock resistance | 15 gn for 11 ms |
| Number of Units in Package 1 | 1 |
| Number of Units in Package 2 | 42 |
| Number of Units in Package 3 | 504 |
| Country of origin | JP |
| Warranty (in months) | 18 |
| Power consumption | 1.1 W |
| Number of analogue inputs | 2 |
| Number of analogue outputs | 1 |
| Analogue inputs configurable | Yes |
| Analogue outputs configurable | No |
| Input, current | Yes |
| Input, voltage | Yes |
| Input, resistor | Yes |
| Input, resistance thermometer | No |
| Input, thermocouple | Yes |
| Input signal, configurable | No |
| Resolution of the analogue inputs | 16 Bit |
| Output, current | Yes |
| Output, voltage | Yes |
| Output signal configurable | No |
| Resolution of the analogue outputs | 12 Bit |
| Type of electric connection | Screw connection |
| Suitable for safety functions | No |
| SIL according to IEC 61508 | None |
| Performance level according to EN ISO 13849-1 | None |
| Appendant operation agent (Ex ia) | No |
| Explosion safety category for gas | None |
| Explosion safety category for dust | None |