| Manufacturer part number (MPN) | 170AAI14000 |
| EAN / GTIN | 3595861147690 |
| Sales unit | pcs |
| Package quantity | 10 pcs |
| Output signal | 4–20 mA |
| Range of product | Modicon Momentum automation platform |
| Product or component type | Analogue input base |
| Analogue input number | 16 |
| Type of filter | Low pass input filter 10 kHz |
| Data format | Full 16 bits signed |
| Absolute accuracy error | +/- 0.15 % of full scale 25 °C +/- 10 V; +/- 0.15 % of full scale 25 °C +/- 5 V; +/- 0.25 % full scale 25 °C 4...20 mA; +/- 0.25 % full scale 60 °C +/- 10 V; +/- 0.25 % full scale 60 °C +/- 5 V; +/- 0.45 % full scale 60 °C 4...20 mA |
| Full scale | 10 V +/- 10 V; 16 mA 4...20 mA; 5 V +/- 5 V |
| Update time | 25 ms |
| Permissible common mode voltage | 100 V 47...63 Hz DC between channels to ground; 250 V 47...63 Hz AC between channels to ground |
| External power requirement | +/- 30 V DC |
| Reverse polarity protection | Internal |
| Analogue input type | Single ended 4...20 mA; Single ended +/- 10 V; Single ended +/- 5 V |
| Analogue input resolution | 12 bits 4...20 mA; 12 bits + sign +/- 10 V; 12 bits + sign +/- 5 V |
| Input impedance | 2200 kOhm |
| Temperature drift | 30 %oFS/°C +/- 10 V; 60 %oFS/°C 4...20 mA |
| Typical current consumption | 305 mA at 24 V DC |
| Power dissipation in W | 5.55 W |
| Isolation between channels and ground | 1780 V AC |
| Electrical connection | 2 connectors for removable terminal blocks |
| Protection type | Internal 2 A slow-blow |
| Associated fuse rating | 500 mA, fast blow |
| Local signalling | 16 LEDs for channel status |
| Height | 125 mm |
| Width | 141.5 mm |
| Depth | 47.5 mm |
| Product weight | 0.215 kg |
| Protective treatment | TC |
| Marking | CE |
| Product certifications | UL; FM Class 1 Division 2; CSA |
| Ambient air temperature for operation | 0…60 °C |
| Ambient air temperature for storage | -40…85 °C |
| Relative humidity | 0…95 % without condensation |
| Operating altitude | <= 5000 m |
| Number of Units in Package 1 | 1 |
| Number of Units in Package 2 | 10 |
| Country of origin | ID |
| Warranty (in months) | 18 |
| Power consumption | 1.1 W |
| Certified for UL hazardous location division 1 | No |
| Certified for UL hazardous location division 2 | No |
| Certified for UL hazardous location group A (acetylene) | No |
| Certified for UL hazardous location group B (hydrogen) | No |
| Certified for UL hazardous location group C (ethylene) | No |
| Certified for UL hazardous location group D (propane) | No |
| Certified for UL hazardous location group E (metal dusts) | No |
| Certified for UL hazardous location class I | No |
| Certified for UL hazardous location class II | No |
| Certified for UL hazardous location class III | No |
| Supporting protocol for EtherCAT | No |
| Supply voltage DC | 24 V |
| Voltage type (supply voltage) | DC |
| Input, current | Yes |
| Input, voltage | Yes |
| Input, resistor | No |
| Input, resistance thermometer | No |
| Input, thermocouple | No |
| Input signal, configurable | Yes |
| Resolution of the analogue inputs | 12 Bit |
| Output, current | No |
| Output, voltage | No |
| Output signal configurable | No |
| Number of analogue inputs | 16 |
| Analogue inputs configurable | Yes |
| Analogue outputs configurable | No |
| Supporting protocol for TCP/IP | No |
| Supporting protocol for PROFIBUS | No |
| Supporting protocol for CAN | No |
| Supporting protocol for INTERBUS | No |
| Supporting protocol for ASI | No |
| Supporting protocol for KNX | No |
| Supporting protocol for Modbus | No |
| Supporting protocol for Data-Highway | No |
| Supporting protocol for DeviceNet | No |
| Supporting protocol for SUCONET | No |
| Supporting protocol for LON | No |
| Supporting protocol for PROFINET IO | No |
| Supporting protocol for PROFINET CBA | No |
| Supporting protocol for SERCOS | No |
| Supporting protocol for Foundation Fieldbus | No |
| Supporting protocol for EtherNet/IP | No |
| Supporting protocol for AS-Interface Safety at Work | No |
| Supporting protocol for DeviceNet Safety | No |
| Supporting protocol for INTERBUS-Safety | No |
| Supporting protocol for PROFIsafe | No |
| Supporting protocol for SafetyBUS p | No |
| Supporting protocol for other bus systems | No |
| Radio standard Bluetooth | No |
| Radio standard WLAN 802.11 | No |
| Radio standard GPRS | No |
| Radio standard GSM | No |
| Mobile communications standard 3G (UMTS) | No |
| IO link master | No |
| System accessory | Yes |
| Degree of protection (IP) | IP20 |
| Type of electric connection | Screw connection |
| Fieldbus connection over separate bus coupler possible | Yes |
| Suitable for rail mounting | Yes |
| Wall mounting/direct mounting | Yes |
| Front built-in possible | Yes |
| Rack-assembly possible | Yes |
| Suitable for safety functions | No |
| SIL according to IEC 61508 | None |
| Performance level according to EN ISO 13849-1 | None |
| Appendant operation agent (Ex ia) | No |
| Explosion safety category for gas | None |
| Explosion safety category for dust | None |