cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider Electric LV434063 Enerlin'X I/O application module

Schneider Electric · Electrical Components · France · se.com
Part Number
LV434063  ·  HS 8538.90
Schneider Electric LV434063 Enerlin'X I/O application module

Schneider Electric LV434063 — Enerlin'X I/O application module.

Technical Specifications

Manufacturer part number (MPN)LV434063
EAN / GTIN3606480631146
Sales unitpcs
Package quantity24 pcs
Device short nameI/O
Product or component typeI/O module
Range compatibilityMasterpact MasterPact MTZ; Masterpact MasterPact NT; Masterpact MasterPact NW; ComPact ComPact NSX; ComPact ComPact NS630b...1600; ComPact ComPact NS1600b...3200; PowerPact PowerPact J; PowerPact PowerPact L; PowerPact PowerPact H; PowerPact PowerPact P; PowerPact PowerPact R
Product nameEnerlin'X IO
Communication network typeUniversal Logic Plug on 2 RJ45 connectors
[Us] rated supply voltage24 V DC - 20...10 %
Current consumption165 mA
Electromagnetic compatibilityElectrostatic discharge immunity test conforming to EN/IEC 61000-4-2; Immunity to radiated fields 10 V/m conforming to EN/IEC 61000-4-3; Surge immunity test conforming to EN/IEC 61000-4-5
Number of inputs6 digital; 1 analog
Input typeDigital at state 1: 19.8…25.2 V - DC - 6.1…8.8 mA; Digital at state 0: 0…19.8 V - DC - 0 mA
Number of outputs3 digital
Output typeDigital: 250 V - AC - 5 A
Cable length10 m
mounting modeBy clips
Mounting support35 mm DIN rail
Control typeBy software
Time delay0...20 s
Vibration frequency5…8.4 Hz
Connections - terminalsScrew terminal block
Product certificationsFCC; GOST; CE; cULus
StandardsIEC 60947-6-2; UL 60950; IEC 60950; UL 508
Depth70.6 mm
Height116 mm
Width71.7 mm
Product weight229.5 g
Relative humidity5…85 %
IP degree of protectionIP2X connectors: ; IP4X front panel: ; IP3x other parts:
Ambient air temperature for operation-20…70 °C
Ambient air temperature for storage-40…85 °C
Pollution degree3
Flame retardanceV0 conforming to UL
Shock resistance1000 m/s²
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height9.000 cm
Package 1 Width8.800 cm
Package 1 Length12.500 cm
Package 1 Weight271.000 g
Unit Type of Package 2S03
Number of Units in Package 224
Package 2 Height30.000 cm
Package 2 Width30.000 cm
Package 2 Length40.000 cm
Package 2 Weight6.995 kg
Unit Type of Package 3P06
Number of Units in Package 3192
Package 3 Height75.000 cm
Package 3 Width60.000 cm
Package 3 Length80.000 cm
Package 3 Weight71.228 kg
Country of originID
Warranty (in months)18
Certified for UL hazardous location division 1No
Certified for UL hazardous location division 2No
Certified for UL hazardous location group A (acetylene)No
Certified for UL hazardous location group B (hydrogen)No
Certified for UL hazardous location group C (ethylene)No
Certified for UL hazardous location group D (propane)No
Certified for UL hazardous location group E (metal dusts)No
Certified for UL hazardous location class INo
Certified for UL hazardous location class IINo
Certified for UL hazardous location class IIINo
Supporting protocol for EtherCATNo
Number of analogue inputs1
Analogue inputs configurableYes
Analogue outputs configurableNo
Number of digital inputs6
Number of digital outputs3
Digital inputs configurableYes
Digital outputs configurableYes
Supply voltage AC 50 Hz0–24 V
Supply voltage AC 60 Hz0–24 V
Supply voltage DC19.2–26.4 V
Voltage type (supply voltage)DC
Input current at signal 16.1 mA
Permitted voltage at input19.8–25.2 V
Type of voltage (input voltage)DC
Output current at digital output5 A
Output voltage at digital output250 V
Type of output voltageAC
Short-circuit protection, digital outputs availableYes
Analogue input, currentNo
Analogue input, voltageNo
Analogue input, resistorNo
Analogue input, resistor temperatureYes
Analogue input, thermocoupleYes
Analogue input signal configurableYes
Analogue output, currentNo
Analogue output, voltageNo
Analogue output signal configurableNo
Number of HW-interfaces other2
With optical interfaceNo
Supporting protocol for TCP/IPNo
Supporting protocol for PROFIBUSNo
Supporting protocol for CANNo
Supporting protocol for INTERBUSNo
Supporting protocol for ASINo
Supporting protocol for KNXNo
Supporting protocol for ModbusNo
Supporting protocol for Data-HighwayNo
Supporting protocol for DeviceNetNo
Supporting protocol for SUCONETNo
Supporting protocol for LONNo
Supporting protocol for PROFINET IONo
Supporting protocol for PROFINET CBANo
Supporting protocol for SERCOSNo
Supporting protocol for Foundation FieldbusNo
Supporting protocol for EtherNet/IPYes
Supporting protocol for AS-Interface Safety at WorkNo
Supporting protocol for DeviceNet SafetyNo
Supporting protocol for INTERBUS-SafetyNo
Supporting protocol for PROFIsafeNo
Supporting protocol for SafetyBUS pNo
Supporting protocol for other bus systemsNo
Radio standard BluetoothNo
Radio standard WLAN 802.11No
Radio standard GPRSNo
Radio standard GSMNo
Mobile communications standard 3G (UMTS)No
IO link masterYes
System accessoryNo
Degree of protection (IP)IP2X
Type of electric connectionScrew connection
Time delay at signal change0–20 ms
Fieldbus connection over separate bus coupler possibleNo
Suitable for rail mountingYes
Wall mounting/direct mountingNo
Front built-in possibleNo
Rack-assembly possibleNo
SIL according to IEC 61508None
Suitable for safety functionsNo
Appendant operation agent (Ex ia)No