Schneider Electric Circuit breaker frame, ComPacT NS1250H, 70KA at 415VAC, 1250A, 4P, drawout, manually operated, without control unit C125H4WM

Schneider Electric · Electrical Components · Moulded Case Circuit Breakers · France · se.com
Part Number
C125H4WM  ·  HS 8536.20
Schneider Electric Circuit breaker frame, ComPacT NS1250H, 70KA at 415VAC, 1250A, 4P, drawout, manually operated, without control unit C125H4WM

Schneider Electric C125H4WM Circuit Breaker Base-ComPacT NS1250H-withdrawable-4p-manual-without protection-1250A-85kA/230VAC-70kA/400/440VAC.

Technical Specifications

Manufacturer part number (MPN)C125H4WM
EAN / GTIN3606482238244
Sales unitpcs
RangeComPacT
Range of productComPacT NS630b...1600 new generation
Product or component typeBasic frame
Device applicationDistribution
Number of poles4P
Neutral positionLeft
[In] rated current1250 A at 50 °C
[Ue] rated operational voltage690 V AC 50/60 Hz
Network typeAC
Network frequency50/60 Hz
Suitability for isolationYes conforming to EN/IEC 60947-2
Utilisation categoryCategory B
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2; 42 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH 70 kA 415 V AC
Control typeManually operated
mounting modeWithdrawable
[Ui] rated insulation voltage800 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage8 kV conforming to IEC 60947-2
[Ics] rated service breaking capacity52 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 52 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 48 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2; 37 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2; 31 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
[Icw] rated short-time withstand current19.2 kA 1 s conforming to IEC 60947-2
Integral instant protection40 kA
Mechanical durability10000 cycles conforming to IEC 60947-2
Electrical durability2000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2; 3000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2; 4000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2; 5000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2
Power losses84 W
Mounting supportBackplate
Connection pitch70 mm
Protection typeWithout protection
Height (H)260 mm
Width (W)306 mm
Depth (D)147 mm
StandardsIEC 60947-2
Product certificationsIECEE CB Scheme
Overvoltage categoryIII
Electrical shock protection classClass II on front face
Pollution degree3 conforming to IEC 60947
IP degree of protectionIP40 conforming to IEC 60529
IK degree of protectionIK07 conforming to EN 50102
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-50…85 °C
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height2.0 cm
Package 1 Width1.0 cm
Package 1 Length2.0 cm
Package 1 Weight10.0 g
Country of originIT
Warranty (in months)18
Rated permanent current Iu1250 A
With integrated under voltage releaseNo
Rated voltage690 V
Power loss336 W
Degree of protection (IP)IP40
Position of connection for main current circuitConnection at separate chassis part
Motor drive integratedNo
Type of electrical connection of main circuitScrew connection
Type of control elementRocker lever
With switched-off indicatorYes
Rated short-circuit breaking capacity Icu at 400 V, 50 Hz70 kA
Suitable for DIN rail (top hat rail) mountingNo
Integrated earth fault protectionNo
Motor drive optionalYes
Device constructionBuilt-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optionalNo
Complete device with protection unitNo