Schneider Electric Circuit breaker basic frame, ComPacT NSX100S DC, 100KA/750VDC, 3 poles, 100A frame rating, without trip unit C10S3D

Schneider Electric · Electrical Components · Moulded Case Circuit Breakers · France · se.com
Part Number
C10S3D  ·  HS 8536.90
Schneider Electric Circuit breaker basic frame, ComPacT NSX100S DC, 100KA/750VDC, 3 poles, 100A frame rating, without trip unit C10S3D

Schneider Electric C10S3D Circuit breaker ComPacT switch base NSX100S DC 3P 100kA/750VDC -without protection.

Technical Specifications

Manufacturer part number (MPN)C10S3D
EAN / GTIN3606481994783
HS code8536.90
Sales unitpcs
Number of poles3P
Breaking capacity100 kA
RangeComPacT
Product nameComPacT NSX DC
Device short nameNSX100S DC
Product or component typeBasic frame
Device applicationDistribution
Poles description3P
[In] rated current100 A at 40 °C
[Ue] rated operational voltage750 V DC conforming to IEC 60947-2
Network typeDC
Suitability for isolationYes conforming to EN/IEC 60947-2
Utilisation categoryCategory A
Breaking capacity codeS 100 kA 750 V DC
Control typeToggle
mounting modeFixed
[Ui] rated insulation voltage750 V DC conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage8 kV conforming to IEC 60947-2
[Ics] rated service breaking capacity100 kA at 250 V DC conforming to IEC 60947-2 (1P); 100 kA at 24...125 V DC conforming to IEC 60947-2 (1P); 100 kA at 500 V DC conforming to IEC 60947-2 (2P); 100 kA at 750 V DC conforming to IEC 60947-2 (3P)
Maximum breaking time10 ms
Mechanical durability10000 cycles conforming to IEC 60947-2
Electrical durability10000 cycles 250 V DC In/2 conforming to IEC 60947-2; 10000 cycles 500 V DC In/2 conforming to IEC 60947-2; 10000 cycles 750 V DC In/2 conforming to IEC 60947-2; 5000 cycles 250 V DC In conforming to IEC 60947-2; 5000 cycles 500 V DC In conforming to IEC 60947-2; 5000 cycles 750 V DC In conforming to IEC 60947-2
Mounting supportBackplate
Upside connectionFront
Downside connectionFront
Connection pitch35 mm
Protection typeWithout protection
Width (W)105 mm
Height (H)161 mm
Depth (D)86 mm
StandardsEN/IEC 60947-2
Overvoltage categoryIII
Electrical shock protection classClass II on front face
Pollution degree3 conforming to IEC 60664-1
IP degree of protectionIP40 conforming to IEC 60529
IK degree of protectionIK07 conforming to EN 50102
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-50…85 °C
Warranty (in months)18