cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider Electric Trip unit MicroLogic 2.3, ComPacT NSX630, 3 poles, electronic basic protections, 630A rating C6332D630

Schneider Electric · Electrical Components · Circuit Breaker Accessories · France · se.com
Part Number
C6332D630  ·  HS 8536.30
Schneider Electric Trip unit MicroLogic 2.3, ComPacT NSX630, 3 poles, electronic basic protections, 630A rating C6332D630

Schneider Electric C6332D630 Electronic protection for ComPacT NSX630-Micrologic 2.3 3P 630A.

Technical Specifications

Manufacturer part number (MPN)C6332D630
EAN / GTIN3606482003033
Sales unitpcs
Package quantity4 pcs
Rated current630 A
Number of poles3P
RangeComPacT
Range of productComPacT NSX400...630
Product or component typeTrip unit
Trip unit nameMicroLogic 2.3
Trip unit technologyElectronic
Range compatibilityComPacT NSX630
Device applicationDistribution
Poles description3P
Protected poles description3D
Trip unit protection functionsLSoI
Protection typeL : for overload protection (long time); So : for short time short-circuit protection with fixed delay; I : for instantaneous short-circuit protection
Trip unit rating630 A at 40 °C
[Ue] rated operational voltage690 V AC 50/60 Hz
Network typeAC
Network frequency50/60 Hz
Circuit breaker mounting modeFixed
Long-time pick-up adjustment type Ir (thermal protection)Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range250...630 A
Long-time protection delay adjustment type trFixed
[tr] long-time protection delay adjustment range11 s at 7.2 x Ir; 16 s at 6 x Ir; 400 s at 1.5 x Ir
Thermal memory20 minutes before and after tripping
Short-time protection pick-up adjustment type IsdAdjustable 9 settings
[Isd] Short-time protection pick-up adjustment range1.5...10 x Ir
Short-time protection delay adjustment type tsdFixed
Instantaneous protection pick-up adjustment type IiFixed
[Ii] instantaneous protection pick-up adjustment range6900 A
Earth-leakage protectionWithout
Zone selective interlocking ZSIWithout
Local signallingFlashing LED (green) for ready to operate; LED 105 % Ir (red) for overload; LED 90 % Ir (orange) for overload
StandardsEN/IEC 60947-2
Electrical shock protection classClass II
Pollution degree3 conforming to IEC 60947-1
IP degree of protectionIP40 conforming to IEC 60529
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-50…85 °C
Warranty (in months)18
Width139.7 mm
Height94.6 mm
Depth112.6 mm
Rated permanent current Iu630 A
Short-circuit release functionDelayed
Overload release current setting250–630 A
External power supply requiredNo
Voltage type (operating voltage)AC
With ground fault protection functionNo
Rated switch current630 A
End value adjustment range undelayed short-circuit release6900 A
Operating voltage AC 50 Hz690 V
Operating voltage AC 60 Hz690 V
Type of motor protectionElectronic release
Voltage type for actuatingAC
Current setting undelayed short-circuit release6900 A
Current setting delayed short-circuit release375–6300 A
Country of originFrance

Properties

MOQ1

Cross-References

Attached Documents