Schneider Electric Trip unit MicroLogic 6.2EM, ComPacT NSX160/250, 3 poles, basic and ground fault protections, motor, energy meter, 150A C1636M150

Schneider Electric · Electrical Components · Circuit Breaker Accessories · France · se.com
Part Number
C1636M150  ·  HS 8536.90
Schneider Electric Trip unit MicroLogic 6.2EM, ComPacT NSX160/250, 3 poles, basic and ground fault protections, motor, energy meter, 150A C1636M150

Schneider Electric C1636M150 Electronic protection for ComPacT NSX circuit breaker-Micrologic 6.2 EM 3P 150A.

Technical Specifications

Manufacturer part number (MPN)C1636M150
EAN / GTIN3606482000469
HS code8536.90
Sales unitpcs
Package quantity11 pcs
Number of poles3P
RangeComPacT
Range of productComPacT NSX100...250
Product or component typeTrip unit
Trip unit nameMicroLogic 6.2 E-M
Trip unit technologyElectronic
Range compatibilityComPacT NSX160; ComPacT NSX250
Device applicationMotor
Poles description3P
Protected poles description3D
Trip unit protection functionsLSIG
Protection typeL : for overload protection (long time); S : for short time short-circuit protection with fixed delay; I : for instantaneous short-circuit protection; G : for ground fault protection
Trip unit rating150 A at 65 °C
[Ue] rated operational voltage690 V AC 50/60 Hz
Network typeAC
Network frequency50/60 Hz
Circuit breaker mounting modeFixed
Motor tripping class10; 30; 5; 20
Complementary motor protectionProtracted starting time; Stalled rotor; Current unbalance; Underload
Long-time pick-up adjustment type Ir (thermal protection)Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range70...150 A
Long-time protection delay adjustment type trAdjustable
[tr] long-time protection delay adjustment range120 s at 1.5 x Ir for trip class 5; 6.5 s at 6 x Ir for trip class 5; 5 s at 7.2 x Ir for trip class 5; 240 s at 1.5 x Ir for trip class 10; 13.5 s at 6 x Ir for trip class 10; 10 s at 7.2 x Ir for trip class 10; 480 s at 1.5 x Ir for trip class 20; 26 s at 6 x Ir for trip class 20; 20 s at 7.2 x Ir for trip class 20; 720 s at 1.5 x Ir for trip class 30; 38 s at 6 x Ir for trip class 30; 30 s at 7.2 x Ir for trip class 30
Thermal memory20 minutes before and after tripping
Short-time protection pick-up adjustment type IsdAdjustable 9 settings
[Isd] Short-time protection pick-up adjustment range5...13 x Ir
Short-time protection delay adjustment type tsdFixed
Instantaneous protection pick-up adjustment type IiFixed
[Ii] instantaneous protection pick-up adjustment range2250 A
Ground-fault protection pick-up adjustment type IgAdjustable
[Ig] ground-fault protection pick-up adjustment range0.2...1 x In for In = 50 A; Ig enable on/off
Ground-fault protection time delay adjustment type tgAdjustable
[tg] ground-fault protection time delay adjustment range0…0.4 s
Earth-leakage protectionWithout
Zone selective interlocking ZSIWith
Local signallingFlashing LED (green) for ready to operate; LED 95 % Ith (red) for temperature over set point
Display typeLCD display
Type of measurementEnergy meter
Communication of dataEnergy metering; Protection and alarm settings; Time-stamped histories and event tables; Instantaneous and demand values; Maintenance indicators; Demand current and power; Power quality; Maximeters/minimeters
Electrical data recordingMaintenance indicators
StandardsEN/IEC 60947-2
Electrical shock protection classClass II
Pollution degree3 conforming to IEC 60947-1
IP degree of protectionIP40 conforming to IEC 60529
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-40…85 °C
Warranty (in months)18