Schneider Electric trip unit MicroLogic 5.0, ComPact NS630B to NS3200 fixed and drawout, selective protections 33511

Schneider Electric · Electrical Components · Circuit Breaker Accessories · France · se.com
Part Number
33511  ·  HS 8536.30
Schneider Electric trip unit MicroLogic 5.0, ComPact NS630B to NS3200 fixed and drawout, selective protections 33511

Schneider Electric 33511 Micrologic 5.0.

Technical Specifications

Manufacturer part number (MPN)33511
EAN / GTIN3303430335115
Sales unitpcs
RangeComPacT
Range of productComPacT NS630b...1600 new generation
Product or component typeTrip unit
Trip unit nameMicroLogic 5.0
Trip unit technologyElectronic
Range compatibilityComPacT NS630b...1600
Device applicationDistribution
Number of poles4P; 3P
Protected poles description3t; 3t + N/2; 4t
Trip unit protection functionsSelective protection
Protection typefor short time short-circuit protection; for overload protection (long time); for instantaneous short-circuit protection
Trip unit rating630 A at 50 °C; 800 A at 50 °C; 1000 A at 50 °C; 1250 A at 50 °C; 1600 A at 50 °C; 2000 A at 50 °C; 2500 A at 50 °C; 3200 A at 50 °C
Network typeAC
Network frequency50/60 Hz
Circuit breaker mounting modeDrawout; Fixed
Long-time pick-up adjustment type Ir (thermal protection)Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range0.4...1 x In
Long-time protection delay adjustment type trAdjustable 9 settings
[tr] long-time protection delay adjustment range0.7…16.6 s at 7.2 x Ir; 0.5…24 s at 6 x Ir; 12.5…600 s at 1.5 x Ir
Thermal memory20 mn
Short-time protection pick-up adjustment type IsdAdjustable 9 settings
[Isd] Short-time protection pick-up adjustment range1.5...10 x Ir
Short-time protection delay adjustment type tsdAdjustable
[tsd] Short-time protection delay adjustment range0…0.4 s I²t=off; 0.1…0.4 s I²t=on
Instantaneous protection pick-up adjustment type IiAdjustable 9 settings
[Ii] instantaneous protection pick-up adjustment range2...15 x In; Off
Earth-leakage protectionWithout
Zone selective interlocking ZSIWithout
Local signalling3 LEDs (red) for electrical fault; 1 LED (red) for internal error
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-50…85 °C
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height6.9 cm
Package 1 Width8.0 cm
Package 1 Length21.5 cm
Package 1 Weight190.0 g
Country of originFR
Warranty (in months)18
Width53.6 mm
Height199.5 mm
Depth67.5 mm
Rated permanent current Iu3200 A
Short-circuit release functionDelayed
Overload release current setting252–3200 A
External power supply requiredNo
Voltage type (operating voltage)AC
With ground fault protection functionNo
Rated switch current3200 A
End value adjustment range undelayed short-circuit release48000 A
Operating voltage AC 50 Hz690 V
Operating voltage AC 60 Hz690 V
Type of motor protectionElectronic release
Voltage type for actuatingSelf powered
Current setting undelayed short-circuit release6400–48000 A
Current setting delayed short-circuit release378–32000 A