| Manufacturer part number (MPN) | 33392 |
| EAN / GTIN | 3303430333920 |
| Sales unit | pcs |
| Number of poles | 3P |
| Range | ComPacT |
| Range of product | ComPacT NS630b...1600 new generation |
| Device short name | Compact NS1000L |
| Product or component type | Basic frame |
| Device application | Distribution |
| [In] rated current | 1000 A at 50 °C |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| Network type | AC |
| Network frequency | 50/60 Hz |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
| Utilisation category | Category A |
| Breaking capacity | 150 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 150 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 130 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 100 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 |
| Breaking capacity code | L 150 kA 415 V AC |
| Control type | Electrically operated; Motor mechanism with external connector |
| mounting mode | Drawout |
| [Ui] rated insulation voltage | 1000 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947-2 |
| [Ics] rated service breaking capacity | 150 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 (electrical operation); 150 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 (electrical operation); 130 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 (electrical operation); 100 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 (electrical operation) |
| Mechanical durability | 10000 cycles conforming to IEC 60947-2 |
| Electrical durability | 2000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2; 3000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2; 3000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2; 4000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2 |
| Power losses | 77 W |
| Mounting support | Backplate |
| Connection pitch | 70 mm |
| Protection type | Without protection |
| Height (H) | 327 mm |
| Width (W) | 210 mm |
| Depth (D) | 147 mm |
| Standards | IEC 60947-2 |
| Product certifications | ASTA; LCIE; ASEFA |
| Overvoltage category | III |
| Electrical shock protection class | Class II on front face |
| Pollution degree | 3 conforming to IEC 60947 |
| IP degree of protection | IP40 conforming to IEC 60529 |
| IK degree of protection | IK07 conforming to EN 50102 |
| Ambient air temperature for storage | -50…85 °C |
| Ambient air temperature for operation | -25…70 °C |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 36.0 cm |
| Package 1 Width | 40.0 cm |
| Package 1 Length | 23.0 cm |
| Package 1 Weight | 16.664 kg |
| Warranty (in months) | 18 |
| Rated permanent current Iu | 1000 A |
| With integrated under voltage release | No |
| Rated voltage | 690 V |
| Power loss | 231 W |
| Degree of protection (IP) | IP40 |
| Position of connection for main current circuit | Front side |
| Motor drive integrated | Yes |
| Type of electrical connection of main circuit | Bolt connection |
| Type of control element | Push button |
| With switched-off indicator | Yes |
| Rated short-circuit breaking capacity Icu at 400 V, 50 Hz | 150 kA |
| Suitable for DIN rail (top hat rail) mounting | No |
| Integrated earth fault protection | No |
| Motor drive optional | No |
| Device construction | Built-in device slide-in technique (withdrawable) |
| DIN rail (top hat rail) mounting optional | No |
| Complete device with protection unit | No |
| Country of origin | France |