| Manufacturer part number (MPN) | A9C32216 |
| EAN / GTIN | 3606480091940 |
| Sales unit | pcs |
| Package quantity | 8 pcs |
| Voltage | 48 V AC |
| Contact configuration | 2 NO |
| range of product | Acti9 |
| Product or component type | Extension for impulse relay |
| Device short name | iETL iTL 16 |
| Relay application | Remote control |
| Poles description | 2P |
| Pole contact composition | 1 C/O + 1 NO |
| [In] rated current | 16 A |
| Network type | AC |
| Network frequency | 50/60 Hz |
| [Ue] rated operational voltage | 415 V AC 50/60 Hz |
| Control type | Remote control; Toggle |
| Control signal type | Impulse |
| Switching frequency | 5 switching operations/minute |
| Impulse duration | 50 ms |
| Remote control type | Illuminated push-button 3 mA |
| Local signalling | ON/OFF indication |
| [Uc] control circuit voltage | 48 V AC 50/60 Hz; 24 V DC |
| Supply inrush power | 19 VA |
| mounting mode | Fixed, on right side of TL |
| Mounting support | 35 mm symmetrical DIN rail |
| 9 mm pitches | 2 |
| Height | 60 mm |
| Width | 18 mm |
| Depth | 84 mm |
| Colour | White |
| Electrical durability | AC-21: 200000 cycles; AC-22: 100000 cycles |
| Connections - terminals | Tunnel type terminals - <= 6 mm² |
| Auxiliary connection terminal | Tunnel type terminals control circuit in 0.5…6 mm² |
| Range compatibility | Acti9 iTL; Acti9 iTLi |
| Product compatibility | ITL 16A |
| Standards | EN 669-2-2; EN 669-1 |
| Product certifications | GOST |
| Quality labels | VDE; NF; IMQ; KEMA; CEBEC |
| Noise level | 60 dB |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Pollution degree | 3 |
| Tropicalisation | 2 conforming to IEC 60068-1 |
| Relative humidity | 95 % at 55 °C |
| Ambient air temperature for operation | -20…50 °C |
| Ambient air temperature for storage | -40…70 °C |
| Country of origin | BE |
| Warranty (in months) | 18 |
| Function | Mechanical |
| Mounting method | DIN rail |
| Width in number of modular spacings | 1 |
| Built-in depth | 84 mm |
| Number of contacts as normally open contact | 1 |
| Number of contacts as change-over contact | 1 |
| Control voltage 1 | 48 V |
| Type of control voltage 1 | AC |
| Frequency control voltage 1 | 50–60 Hz |
| Control voltage 2 | 24 V |
| Type of control voltage 2 | DC |
| Rated current | 16 A |
| Supply voltage | 24–250 V |
| Voltage type (supply voltage) | AC |
| Max. incandescent lamp load | 1600 W |
| Max. load fluorescent lamp | 1300 VA |
| Max. switching current (cos phi = 0.6) | 16 A |