| Manufacturer part number (MPN) | VW3A5504 |
| EAN / GTIN | 3606485435794 |
| Sales unit | pcs |
| Product or component type | Common mode output filter |
| Range compatibility | Altivar Process ATV600; Altivar Process ATV900 |
| Value of inductance | 180 µH |
| Product compatibility | Variable speed drive ATV630 wall mount, 15…90 kW, 380...480 V; Variable speed drive ATV650 wall mount, 15…90 kW, 380...480 V; Variable speed drive ATV930 wall mount, 15…90 kW, 380...480 V; Variable speed drive ATV950 wall mount, 15…90 kW, 380...480 V; Variable speed drive ATV630 wall mount, 7.5…45 kW, 200...240 V; Variable speed drive ATV930 wall mount, 7.5…45 kW, 200...240 V |
| Maximum motor cable length | 150 m(shielded cable) motor: 30…90 kW 380...480 V, with 1 filter; 300 m(unshielded cable) motor: 15…90 kW 380...480 V, with 1 filter; 300 m(shielded cable) motor: 30…90 kW 380...480 V, with 1 filter + VW3A5503; 500 m(unshielded cable) motor: 30…90 kW 380...480 V, with 1 filter + VW3A5503; 500 m(shielded cable) motor: 15…22 kW 380...480 V, with 1 filter + VW3A5503; 500 m(shielded cable) motor: 30…90 kW 380...480 V, with 2 filter; 1000 m(unshielded cable) motor: 15…22 kW 380...480 V, with 1 filter + VW3A5503; 1000 m(unshielded cable) motor: 30…90 kW 380...480 V, with 2 filter; 150 m(shielded cable) motor: 15…45 kW 200...240 V, with 1 filter; 300 m(unshielded cable) motor: 7.5…45 kW 200...240 V, with 1 filter; 300 m(shielded cable) motor: 15…45 kW 200...240 V, with 1 filter + VW3A5503; 500 m(unshielded cable) motor: 15…45 kW 200...240 V, with 1 filter + VW3A5503; 500 m(shielded cable) motor: 7.5…11 kW 200...240 V, with 1 filter + VW3A5503; 500 m(shielded cable) motor: 15…45 kW 200...240 V, with 2 filter; 1000 m(unshielded cable) motor: 7.5…11 kW 200...240 V, with 1 filter + VW3A5503; 1000 m(unshielded cable) motor: 15…45 kW 200...240 V, with 2 filter |
| Saturation current | 2.2 A |
| internal diameter | 76 mm for 3-phase cable inside; 76 mm for PE cable outside |
| Electrical insulation class | Class I |
| Mechanical robustness | Shocks class 3M4 conforming to IEC 60721-3-3; Vibrations class 3M4 conforming to IEC 60721-3-3 |
| Switching frequency | <= 10 kHz |
| Maximum output frequency | 100 Hz |
| Height | 210 mm |
| Width | 127.5 mm |
| Depth | 127.5 mm |
| Product weight | 2.96 kg |
| Relative humidity | 5…95 % without condensation |
| Ambient air temperature for operation | -15…60 °C |
| Ambient air temperature for storage | -40…70 °C |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 17.000 cm |
| Package 1 Width | 27.700 cm |
| Package 1 Length | 18.200 cm |
| Package 1 Weight | 3.328 kg |
| Unit Type of Package 2 | P06 |
| Number of Units in Package 2 | 24 |
| Package 2 Height | 75.000 cm |
| Package 2 Width | 60.000 cm |
| Package 2 Length | 80.000 cm |
| Package 2 Weight | 92.872 kg |
| Country of origin | TH |
| Warranty (in months) | 18 |
| Suitable as sinus filter | No |
| Suitable as du/dt-filter | No |
| Suitable as radio interference suppression filter | No |
| Suitable as audio frequency blockage | No |
| Number of poles, primary side | 3 |
| Rated clock frequency | 10 kHz |
| Rated operating frequency | 50–60 Hz |
| Max. rated operation voltage Ue | 480 V |
| Rated current AC | 2.2 A |