cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider Electric TPRAN2X1 Analog IO module, TeSys island, 2 inputs, 1 output

Schneider Electric · Electrical Components · France · se.com
Part Number
TPRAN2X1  ·  HS 8536.50
Schneider Electric TPRAN2X1 Analog IO module, TeSys island, 2 inputs, 1 output

Schneider Electric TPRAN2X1 — Analog IO module, TeSys island, 2 inputs, 1 output.

Technical Specifications

Manufacturer part number (MPN)TPRAN2X1
EAN / GTIN3606489832902
Sales unitpcs
Package quantity16 pcs
RangeTeSys
Product nameTeSys island
Device short nameTPRAN
Product or component typeAnalog IO module
Device presentationIO module providing 2 analog inputs and 1 analog output; Enabling advanced control functions in a TeSys island system; Operational only when connected to a bus coupler TPRBC
Function of moduleMeasurement of voltage, current or temperature on 2 configurable analog inputs; Driving voltage or current source on 1 configurable analog output
Product compatibilityTPRBC bus coupler
Analogue input number2 isolated with common point
Analogue input typeCurrent 4...20 mA; Current 0...20 mA; Voltage 0...10 V; Voltage - 10...10 V; Temperature probe - 60...180 °C temperature probe: Ni 100; Temperature probe - 60...180 °C temperature probe: Ni 1000; Temperature probe -200...+850 °C temperature probe: Pt 100; Temperature probe - 200...600 °C temperature probe: Pt 1000; Thermocouple - 200...1000 °C thermocouple J; Thermocouple - 200...1300 °C thermocouple K; Thermocouple 0...1760 °C thermocouple R; Thermocouple 0...1760 °C thermocouple S; Thermocouple 0...1820 °C thermocouple B; Thermocouple - 200...400 °C thermocouple T; Thermocouple - 200...1300 °C thermocouple N; Thermocouple - 200...800 °C thermocouple E; Thermocouple 0...2315 °C thermocouple C
Measurement accuracy+/- 0.1 % of full scale voltage 25 °C; +/- 0.1 % of full scale current 25 °C; +/- 0.1 % of full scale temperature probe 25 °C; +/- 0.1 % of full scale in positive temperature range thermocouple 25 °C; +/- 0.4 % of full scale in negative temperature range thermocouple 25 °C
Analogue input resolution15 bits + sign full scale
Input impedance= 1 MOhm voltage; >= 1 MOhm thermocouple; >= 1 MOhm temperature probe
Analogue output number1 isolated
Analogue output typeCurrent 4...20 mA; Current 0...20 mA; Voltage 0...10 V; Voltage - 10...10 V
Analogue output resolution12 bits, 4...20 mA full scale; 12 bits, 0...20 mA full scale; 12 bits, 0...10 V full scale; 11 bits + sign, - 10...10 V full scale
Type of cableTwisted shielded pairs cable <30 m for input/output circuit
Local signalling1 LED (green/red) for DS (device status)
[Us] rated supply voltage24 V DC supplied by the bus coupler
Current consumption160 mA
Power dissipation in W0.5 W maximum
[Uimp] rated impulse withstand voltage0.5 kV conforming to IEC 61010-1
StandardsIEC 61010-2-201; UL 61010-2-201; CSA C22.2 No 61010-2-201
Product certificationsCSA; UL; EAC (pending)
Mounting modeHorizontal and vertical (35 mm symmetrical rail)
Connections - terminalsInput/output circuit: removable spring terminal block 8 cable(s) 0.2…2.5 mm² (24 AWG...14 AWG) rigid; Input/output circuit: removable spring terminal block 8 cable(s) 0.2…2.5 mm² (24 AWG...14 AWG) flexible without cable end; Input/output circuit: removable spring terminal block 8 cable(s) 0.25…2.5 mm² (22 AWG...14 AWG) flexible with cable end
Width25 mm
Height118 mm
Depth114 mm
Product weight0.172 kg
Ambient air temperature for storage-25…70 °C
Ambient air temperature for operation-10…60 °C
Relative humidity5…95 %
Operating altitude0...2000 m without derating
IP degree of protectionIP20
Pollution degree2
Protective treatmentTC
Fire resistance960 °C conforming to UL 94
Shock resistance15 gn (duration = 11 ms) conforming to IEC 60068-2-27
Vibration resistance1.5 mm peak to peak (f= 3…13 Hz) conforming to IEC 60068-2-6; 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6
Electromagnetic compatibilityElectrostatic discharge immunity test, level 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2; Radiated RF fields, level 3, 10 V/m, conforming to EN/IEC 61000-4-3; Fast transients immunity test, level 3, 2 kV, conforming to EN/IEC 61000-4-4; Surge immunity test (common mode), level 3, 2 kV, conforming to EN/IEC 61000-4-5
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height6.500 cm
Package 1 Width13.500 cm
Package 1 Length15.500 cm
Package 1 Weight245.000 g
Unit Type of Package 2S03
Number of Units in Package 216
Package 2 Height30.000 cm
Package 2 Width30.000 cm
Package 2 Length40.000 cm
Package 2 Weight4.654 kg
Country of originID
Warranty (in months)18
Certified for UL hazardous location division 1No
Certified for UL hazardous location division 2No
Certified for UL hazardous location group A (acetylene)No
Certified for UL hazardous location group B (hydrogen)No
Certified for UL hazardous location group C (ethylene)No
Certified for UL hazardous location group D (propane)No
Certified for UL hazardous location group E (metal dusts)No
Certified for UL hazardous location class INo
Certified for UL hazardous location class IINo
Certified for UL hazardous location class IIINo
Supporting protocol for EtherCATNo
Voltage type (supply voltage)DC
Input, currentYes
Input, voltageYes
Input, resistorNo
Input, resistance thermometerYes
Input, thermocoupleYes
Input signal, configurableYes
Resolution of the analogue inputs16 Bit
Output, currentYes
Output, voltageYes
Output signal configurableYes
Resolution of the analogue outputs12 Bit
Number of analogue inputs2
Number of analogue outputs1
Analogue inputs configurableYes
Analogue outputs configurableYes
Number of HW-interfaces other2
Supporting protocol for TCP/IPNo
Supporting protocol for PROFIBUSNo
Supporting protocol for CANNo
Supporting protocol for INTERBUSNo
Supporting protocol for ASINo
Supporting protocol for KNXNo
Supporting protocol for ModbusNo
Supporting protocol for Data-HighwayNo
Supporting protocol for DeviceNetNo
Supporting protocol for SUCONETNo
Supporting protocol for LONNo
Supporting protocol for PROFINET IONo
Supporting protocol for PROFINET CBANo
Supporting protocol for SERCOSNo
Supporting protocol for Foundation FieldbusNo
Supporting protocol for EtherNet/IPNo
Supporting protocol for AS-Interface Safety at WorkNo
Supporting protocol for DeviceNet SafetyNo
Supporting protocol for INTERBUS-SafetyNo
Supporting protocol for PROFIsafeNo
Supporting protocol for SafetyBUS pNo
Supporting protocol for other bus systemsYes
Radio standard BluetoothNo
Radio standard WLAN 802.11No
Radio standard GPRSNo
Radio standard GSMNo
Mobile communications standard 3G (UMTS)No
IO link masterNo
System accessoryYes
Degree of protection (IP)IP20
Type of electric connectionPlug-in connection
Fieldbus connection over separate bus coupler possibleYes
Suitable for rail mountingYes
Wall mounting/direct mountingNo
Front built-in possibleNo
Rack-assembly possibleNo
Suitable for safety functionsNo
SIL according to IEC 61508None
Performance level according to EN ISO 13849-1None
Appendant operation agent (Ex ia)No
Explosion safety category for gasNone
Explosion safety category for dustNone

Properties

MOQ1

Cross-References