Schneider Electric LRD365 — TeSys thermal overload relay. Bimetallic thermal overload relay for motor protection. Thermal protection, series D. Up to 150 A (0.06 - 75 kW) for both AC and DC motor controls. Integrated manual/automatic reset.
| Manufacturer part number (MPN) | LRD365 EAN / GTIN: 3389119215510 HS code: 8536.90 Sales unit: pcs Package quantity: 13 pcs Setting range: 48-65 A Range: TeSys; TeSys Deca Product name: TeSys LRD; TeSys Deca Product or component type: Differential thermal overload relay Device short name: LRD Relay application: Motor protection Product compatibility: LC1D65A; LC1D50A Network type: DC; AC Thermal overload class: Class 10A conforming to IEC 60947-4-1 Thermal protection adjustment range: 48…65 A [Ui] rated insulation voltage: Power circuit: 600 V conforming to CSA; Power circuit: 600 V conforming to UL; Power circuit: 690 V conforming to IEC 60947-4-1 Network frequency: 0...400 Hz Mounting support: Plate, with specific accessories; Rail, with specific accessories; Under contactor Tripping threshold: 1.14 +/- 0.06 Ir conforming to IEC 60947-4-1 Auxiliary contact composition: 1 NO + 1 NC [Ith] conventional free air thermal current: 5 A for signalling circuit Permissible current: 0.95 A at 38 |
| MOQ | 1 |