| Manufacturer part number (MPN) | A9C15424 |
| EAN / GTIN | 3606480430626 |
| Sales unit | pcs |
| Package quantity | 108 pcs |
| range of product | Acti9 |
| Device short name | iATL24 |
| Product or component type | Control and indication auxiliary |
| Signal contacts composition | 1 NO |
| Signalling circuit voltage | 24 V DC: +/- 20 % 0.002...0.1 A |
| [Uc] control circuit voltage | 230 V AC 50/60 Hz impulse >= 200 ms; 24 V DC falling edge; 24 V DC rising edge |
| [Us] rated supply voltage | 230 V AC at 50/60 Hz |
| Control type | Remote control |
| [Ui] rated insulation voltage | 250 V AC 50/60 Hz |
| [Uimp] rated impulse withstand voltage | 8 kV |
| Power consumption in W | 1 W |
| mounting mode | Fixed, on the left of CT |
| Mounting support | DIN rail |
| Comb busbar and distribution block compatibility | Bottom: YES; Top: NO |
| Electrical durability | 250000 cycles conforming to IEC 60947-5-1 |
| Immunity to microbreaks | 10 ms |
| Undervoltage behaviour | No opening if loss of 24 V DC |
| 9 mm pitches | 2 |
| Height | 81 mm |
| Width | 18 mm |
| Depth | 68 mm |
| Colour | White |
| Connections - terminals | Power supply: tunnel type terminals 1 cable(s) 0.5…10 mm² - rigid; Power supply: tunnel type terminals 1 cable(s) 0.5…6 mm² - flexible; Power supply: tunnel type terminals 1 cable(s) 0.5…4 mm² - flexible with ferrule; Input: tunnel type terminals 2 cable(s) 0.5…2.5 mm² - rigid; Input: tunnel type terminals 2 cable(s) 0.5…2.5 mm² - flexible; Input: tunnel type terminals 2 cable(s) 0.5…2.5 mm² - flexible with ferrule; Ti24 interface: spring-loaded terminal Ti24 2 cable(s) 0.5…1.5 mm² - rigid; Ti24 interface: spring-loaded terminal Ti24 1 cable(s) 0.5…1.5 mm² - flexible |
| Wire stripping length | Power supply: 9 mm for bottom connection; Input: 9 mm for bottom connection; Ti24 interface: 10 mm for top connection |
| Tightening torque | Power supply: 1 N.m bottom; Input: 1 N.m bottom |
| Range compatibility | Acti9 iTL; Acti9 iTLi; Acti9 iTLs; Acti9 iTLc |
| Product compatibility | Acti 9 Smartlink; ITL (32 A) - 230/240 V 50 Hz; ITL (16 A) - 230/240 V 50 Hz |
| Overvoltage category | IV |
| IP degree of protection | IP20 conforming to IEC 60529; IP40 (modular enclosure) conforming to IEC 60529 |
| Pollution degree | 3 conforming to IEC 60439-1 |
| Tropicalisation | 2 conforming to IEC 60947-5-1 |
| Relative humidity | 93 % at 40 °C conforming to IEC 60068-2 |
| Ambient air temperature for operation | -25…60 °C |
| Ambient air temperature for storage | -40…80 °C |
| Quality labels | CE |
| Standards | IEC 60947-1 appendix S |
| Number of Units in Package 1 | 1 |
| Number of Units in Package 2 | 108 |
| Warranty (in months) | 18 |
| Function | Remote drive |
| Voltage type | DC |
| Rated voltage | 24 V |
| Installed at the factory | No |
| Width in number of modular spacings | 1 |
| Rated switch current | 0.002 A |
| Device fitting | Contactor/relay |
| Additional equipment | Remote drive |
| Voltage type for actuating | DC |
| Number of contacts as normally open contact | 1 |
| With auto test for earth leakage function | No |
| Suitable for max. number of poles main contact unit (total) | 4 |
| Suitable for max. current main contact unit | 32 A |
| Country of origin | Spain |