| Manufacturer part number (MPN) | A9C15924 |
| EAN / GTIN | 3606480430619 |
| Sales unit | pcs |
| Package quantity | 108 pcs |
| Voltage | 230 V AC |
| Range | Acti9 |
| Product or component type | Control and indication auxiliary |
| Device short name | iACT24 |
| Signal contacts composition | 1 NO |
| Signalling circuit voltage | 24 V DC: - 20...20 % 0.002...0.1 A |
| [Uc] control circuit voltage | 230 V AC 50/60 Hz maintained >= 200 ms; 24 V DC falling edge; 24 V DC rising edge |
| Control type | Remote control |
| [Us] rated supply voltage | 230 V AC at 50/60 Hz |
| mounting mode | Fixed, on the left of CT |
| Mounting support | DIN rail |
| Comb busbar and distribution block compatibility | Bottom: YES; Top: NO |
| 9 mm pitches | 2 |
| Height | 81 mm |
| Width | 18 mm |
| Depth | 68 mm |
| Colour | White |
| Overvoltage category | III |
| [Uimp] rated impulse withstand voltage | 4 kV |
| [Ui] rated insulation voltage | 440 V |
| Immunity to microbreaks | 10 ms |
| Undervoltage behaviour | No opening if loss of 24 V DC |
| Standards | IEC 60947-1 annex S |
| Quality labels | CE |
| Electrical durability | 250000 cycles conforming to IEC 60947-5-1 |
| Connections - terminals | Control circuit: tunnel type terminals 2 cable(s) 2.5 mm² flexible; Control circuit: tunnel type terminals 2 cable(s) 1.5 mm² rigid; Auxiliary supply: tunnel type terminals 2 cable(s) 2.5 mm² flexible; Auxiliary supply: tunnel type terminals 2 cable(s) 1.5 mm² rigid; Control circuit: spring-loaded terminal Ti24 2 cable(s) 0.25…0.75 mm² flexible; Control circuit: spring-loaded terminal Ti24 1 cable(s) 0.5…1.5 mm² flexible |
| Wire stripping length | Control circuit: 10 mm for bottom connection; Auxiliary supply: 10 mm for bottom connection; Control circuit: 10 mm for top connection |
| Tightening torque | Control circuit: 1 N.m bottom; Auxiliary supply: 1 N.m bottom |
| Product compatibility | ICT 230/240 V 50 Hz; With PLC; ICT 220 V 50 Hz; Acti 9 Smartlink; ICT 220/240 V 50 Hz |
| Market segment | Residential; Small commercial |
| Compatibility code | IACT24 |
| IP degree of protection | IP20 conforming to IEC 60529; IP40 (modular enclosure) conforming to IEC 60529 |
| Pollution degree | 3 conforming to IEC 60439-1 |
| Tropicalisation | 2 conforming to IEC 60947-5-1 |
| Relative humidity | 93 % at 40 °C conforming to IEC 60068-2 |
| Ambient air temperature for operation | -25…60 °C |
| Ambient air temperature for storage | -40…80 °C |
| Number of Units in Package 1 | 1 |
| Number of Units in Package 2 | 108 |
| Warranty (in months) | 18 |
| Voltage type | AC |
| Rated voltage | 24 V |
| Installed at the factory | No |
| Width in number of modular spacings | 1 |
| Rated switch current | 0.002 A |
| Device fitting | Contactor/relay |
| Voltage type for actuating | AC |
| Number of contacts as normally open contact | 1 |
| With auto test for earth leakage function | No |
| Suitable for max. number of poles main contact unit (total) | 3 |
| Suitable for max. current main contact unit | 63 A |
| Country of origin | Spain |