| Manufacturer part number (MPN) | SMT10020 |
| EAN / GTIN | 3606489906269 |
| Sales unit | pcs |
| Package quantity | 14 pcs |
| Range | PowerLogic |
| Range of product | PowerLogic HeatTag |
| Product or component type | Heat detector |
| Range compatibility | PrismaSeT wireless panel server; EcoStruxure data concentrator; PowerLogic PowerTag |
| Device application | Electrical switchboard |
| Function available | Overheating detection of cables and wire connections; Overheating detection based on the analyse of gas and particles in the air; 3 levels of alert according to the severity of the situation; Environment auto-learning to avoid false alerts; Wireless communication with all EcoStruxure data concentrators |
| sensor technology | Electronic |
| Type of measurement | Temperature, range: - 15...70 °c, accuracy: +/- 1.1 °C; Humidity, range: 15...90 % PURE WHITE, accuracy: +/- 9 %; Air quality index, range: 0...10 AQI |
| transmission period | 30 s (by default); > 30 s (high data traffic) |
| alarm level | Air quality index >= 10 |
| Communication network type | Wireless - 2.4 GHz |
| Standards | IEC 61010-1; IEC 61010-2-201; IEC 61326-1; ETSI EN 300 328; ETSI EN 301 489-1; ETSI EN 301 489-17; IEEE 802.15.4; FCC part 15 Subpart B; FCC part 15 Subpart C; UL 61010-1; CSA C22.2 No 61010-1 |
| [Us] rated supply voltage | 110...277 V AC at 50/60 Hz, single phase |
| Supply voltage limits | 110…277 V (+/- 15 %) |
| Maximum supply current | 0.1 A |
| Overvoltage category | III |
| Control type | 1 push-button (sensor pairing/alert acknowledgement) |
| Local signalling | Network status: 1 LED (green, orange and red); Operating: 1 LED (green, orange and red) |
| Device location in system | Top of the switchboard; Non forced air ventilated switchboard |
| Mounting support | DIN rail |
| Protection type | Circuit breaker 2 A curve C |
| Electrical connection | 2 pin(s)removable spring terminal block 2.5 mm² rigid or flexible |
| Quantity per set | 1 |
| Height | 107 mm |
| Width | 108 mm |
| Depth | 55 mm |
| Product weight | 0.27 kg |
| Ambient air temperature for storage | -20…85 °C |
| Ambient air temperature for operation | -15…70 °C |
| Operating altitude | 0...2000 m |
| Relative humidity | 15…90 % |
| IP degree of protection | IP20 |
| IK degree of protection | IK06 |
| Pollution degree | 3 |
| Electromagnetic compatibility | EMC immunity conforming to IEC 61326-1 |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 6.300 cm |
| Package 1 Width | 9.500 cm |
| Package 1 Length | 11.600 cm |
| Package 1 Weight | 292.800 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 14 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 4.399 kg |
| Country of origin | FR |
| Warranty (in months) | 18 |
| Bus system KNX Secure | No |
| Bus system KNX Secure-RF (Radio Frequency) | No |
| Power consumption | 27.7 W |
| Bus system KNX | No |
| Bus system KNX-RF (Radio Frequency) | No |
| Bus system radio frequency | Yes |
| Bus system LON | No |
| Bus system Powernet | No |
| Radio frequency bidirectional | Yes |
| Model | Multiple sensor |
| Mounting method | DRA (DIN-rail adaptor) |
| With bus connection | Yes |
| With DCF77 | No |
| Acoustic signal | No |
| With heating | Yes |
| Colour | White |
| RAL-number (similar) | 9001 |
| Analogue input | No |
| Weather station | No |
| Degree of protection (IP) | IP20 |