| Manufacturer part number (MPN) | LVS04552 |
| EAN / GTIN | 3606481870537 |
| Sales unit | pcs |
| Dimensions | 120x10 mm |
| Range | Linergy |
| Range of product | Linergy |
| Product or component type | Busbar |
| Product name | Linergy BS |
| Range compatibility | PrismaSeT PrismaSeT P enclosure |
| Busbar description | Flat bar |
| Quantity per set | Set of 1 |
| Installation direction | Vertical, operating position: lateral; Horizontal, operating position: top; Horizontal, operating position: bottom |
| installation description | Cubicle - width 650 mm; Cubicle - width 650 + 150 mm; Cubicle duct - width 300 mm; Cubicle duct - width 400 mm |
| [Ie] rated operational current | 1880 A at 35 °C |
| [Icw] rated short-time withstand current | 60 kA (1 s) for 2 supports (horizontal position); 85 kA (1 s) for 3 supports (horizontal position); 40 kA (1 s) (horizontal position); 85 kA (1 s) for 2 supports (horizontal position); 50 kA (1 s) (horizontal position) |
| Permissible current | 1880 A at 35 °C: <= IP31; 1670 A at 35 °C: IP31 |
| Busbar cross section | 120 x 10 mm |
| Length | 2000 mm |
| Width | 120 mm |
| Depth | 10 mm |
| Product weight | 21.9 kg |
| Colour | Natural |
| Type of busbar connection | Without hole |
| Standards | IEC 61439-2; IEC 61439-1 |
| Product certifications | ASTA |
| Number of Units in Package 1 | 1 |
| Number of Units in Package 2 | 18 |
| Warranty (in months) | 18 |
| Model | Flat |
| Height | 10 mm |
| Flexible | No |
| Surface protection | Untreated |
| Rated current In | 3760 A |
| Country of origin | Italy |