| Manufacturer part number (MPN) | A9L16311 |
| EAN / GTIN | 3606480387142 |
| Sales unit | pcs |
| Package quantity | 12 pcs |
| range of product | Acti9 |
| Product or component type | Cartridge |
| Device short name | C20-350 |
| Range compatibility | Acti9 iQuick PRD20r |
| Surge arrester type | Electrical distribution network |
| Standards | IEC 61643-1; EN 61643-11 |
| Product certifications | KEMA-KEUR; NF |
| Surge arrester class type | Type 2 |
| Surge arrester technology | MOV |
| Product destination | Surge protection device iQuick PRD20r 1P + N; Surge protection device iQuick PRD20r 3P; Surge protection device iQuick PRD20r 3P + N |
| Earthing system | TT; TN |
| [Ue] rated operational voltage | 230 V AC 50 Hz |
| Nominal discharge current | 5 kA |
| Maximum discharge current | 20 kA |
| [Uc] maximum continuous operating voltage | 350 V |
| Maximum [Up] voltage protection level | 1.2 kV type 2 |
| Local signalling | Flag (white/red) |
| mounting mode | Plug-in |
| Mounting support | Into SPD module |
| 9 mm pitches | 1.3 |
| Height | 50 mm |
| Width | 12 mm |
| Depth | 57 mm |
| Colour | White (RAL 9003) |
| Material | PBT (polybutylene terephthalate) |
| Response time | < 25 ns |
| IP degree of protection | IP20 front face: |
| Relative humidity | 5…95 % |
| Operating altitude | 0...2000 m |
| Ambient air temperature for operation | -25…60 °C |
| Ambient air temperature for storage | -40…70 °C |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 2.000 cm |
| Package 1 Width | 6.700 cm |
| Package 1 Length | 9.500 cm |
| Package 1 Weight | 60.000 g |
| Unit Type of Package 2 | BB1 |
| Number of Units in Package 2 | 12 |
| Package 2 Height | 8.500 cm |
| Package 2 Width | 11.000 cm |
| Package 2 Length | 26.500 cm |
| Package 2 Weight | 804.000 g |
| Unit Type of Package 3 | S03 |
| Number of Units in Package 3 | 108 |
| Package 3 Height | 30.000 cm |
| Package 3 Width | 30.000 cm |
| Package 3 Length | 40.000 cm |
| Package 3 Weight | 7.949 kg |
| Country of origin | HU |
| Warranty (in months) | 18 |
| System configuration | TN |
| System configuration DC | No |
| System configuration IT | No |
| System configuration TN | Yes |
| System configuration TN-C | No |
| System configuration TT | Yes |
| System configuration other | No |
| Nominal discharge surge current (8/20) | 15 kA |
| Max. discharge surge current (8/20) | 20 kA |
| Short-circuit-proof | No |
| Nominal voltage AC | 230 V |
| Max. continuous voltage AC | 350 V |
| Voltage protection level | 1.2 kV |
| Voltage protection level L-N | 1.2 kV |
| Voltage protection level N-PE | 1.2 kV |
| Integrated short-circuit protection | No |
| Integrated backup fuse | No |
| Leakage-current free | No |
| Mounting method | On basic element |
| With remote signalling contact | No |
| Signalling at the device | Optical |
| Category type 2 | Yes |
| Degree of protection (IP) | IP20 |