| Manufacturer part number (MPN) | A9W21463 |
| EAN / GTIN | 3606480443565 |
| HS code | 8536.90 |
| Sales unit | pcs |
| Package quantity | 17 pcs |
| Rated current | 63 A |
| Number of poles | 4P |
| Range | Acti9 |
| Product name | Acti9 Vigi iC60 |
| Product or component type | Add-on residual current device |
| Device short name | Vigi iC60 |
| Poles description | 4P |
| [In] rated current | 63 A |
| Earth-leakage sensitivity | 30 mA |
| Earth-leakage protection time delay | Instantaneous |
| Earth leakage protection type | Type A |
| Network type | AC |
| Network frequency | 50/60 Hz |
| [Ue] rated operational voltage | 400/415 V AC 50/60 Hz conforming to IEC 61009-1; 400/415 V AC 50/60 Hz conforming to EN 61009-1 |
| Standards | IEC 61009-1; EN 61009-1 |
| 9 mm pitches | 7 |
| Device location in system | Outgoer |
| Residual current tripping technology | Voltage independent |
| [Ui] rated insulation voltage | 500 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
| Range compatibility | Acti9 iC60 |
| Product compatibility | Double terminal |
| Lo |