ISO.OVERV. MOTORVIKL. IM9-OL (IMD-IM9-OL)

Schneider Electric · France · se.com
Part Number
IMD-IM9-OL  ·  HS 9030.39
ISO.OVERV. MOTORVIKL. IM9-OL (IMD-IM9-OL)

Insulation monitoring of vikling in elektromotorer. Pot.fri alarm contact.

Technical Specifications

Manufacturer part number (MPN)IMD-IM9-OL
EAN / GTIN3606480321665
Sales unitpcs
Package quantity36 pcs
RangeVigilohm
Device short nameIM9-OL
Product or component typeInsulation monitoring device
Type of IMDAC IMD
Earthing systemTT; TN-S; IT
ApplicationOff-line application
Electrical circuit typeOffline device
Type of network1P + N; 3P; 3P + N
Network rated voltage0…690 V - AC at 45...440 Hz (device connected to neutral)
Alarm threshold settingPre-alarm: 0.5...10 MOhm; Alarm: 0.25...2 MOhm
Type of measurementStator insulation resistance, range: 250 kOhm...10 MOhm, accuracy: +/- 15 %
Configurable filtering time2 s
Response time2 s 100 %
Self-testManual
Overvoltage categoryIII
IP degree of protectionCase: IP20; Front face: IP40
MaterialThermoplastic
Type of installationIndoor
Operating altitude<= 3000 m
Relative humidity0…92 %
Ambient air temperature for operation-25…55 °C
Ambient air temperature for storage-40…70 °C
Pollution degree2
Mounting modeClip-on (DIN rail); Flush-mounted (panel)
Mounting positionHorizontal; Vertical
Connections - terminalsTunnel type terminals 0.2…2.5 mm²
Product weight0.2 kg
Cut-out dimensions66 x 72.5 mm
Height90 mm
Width71 mm
Depth67.5 mm
Display typeWithout display
Signal contacts composition1 C/O standard; 1 C/O fail-safe
Signalling circuit voltage250 V - AC at 6 A; 12...24 V - DC at 6 A
Communication port protocol-
Communication of dataHMI: test reports
[Us] rated supply voltage110...415 V AC 50/60/400 Hz tolerance: +/- 15 %; 125...250 V DC tolerance: +/- 15 %
Power consumption in VA7 VA
Power consumption in W3 W
Overcurrent protection1 A
StandardsIEC 61557-8; UL 61010-1; IEC 61010-1; IEC 61326-2-4
Product certificationsEAC; DNV; CE; RCM; EU-RO MR TA
Environmental characteristicExposure to damp heat not in service conforming to IEC 60068-2-30; Exposure to damp heat in service conforming to IEC 60068-2-56; Salt mist conforming to IEC 60068-2-52; Long-term storage class 1K22 conforming to IEC 60721-3-1; Transport class 2K11 conforming to IEC 60721-3-2; Stationary use at weather protected locations class 3K24 conforming to IEC 60721-3-3
Mechanical robustnessLong-term storage class 1M11 conforming to IEC 60721-3-1; Transport class 2M4 conforming to IEC 60721-3-2; Stationary use class 3M11 conforming to IEC 60721-3-3
Number of Units in Package 11
Number of Units in Package 236
Warranty (in months)18
Operating voltage AC 50 Hz0–690 V
Operating voltage AC 60 Hz0–690 V
External power supply requiredNo
Supply voltage AC 50 Hz110–415 V
Supply voltage AC 60 Hz110–415 V
Supply voltage DC125–250 V
Rated operating frequency45–440 Hz
Voltage measuring range0–690 V
Voltage type (operating voltage)AC
Type of electric connectionScrew connection
Voltage type for actuatingAC
With detachable clampsNo
FunctionFor mixed system
Line capacity60 µF
Response value impedance 1500–10000 kOhm
Response value impedance 2250–2000 kOhm
Indication of insulation valueNo
Error registration possibleNo
Number of contacts as change-over contact1
Country of originIndia

Properties

MOQ1

Cross-References