cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-08
sales@cballast.com
cballast.com

Schneider Electric A9L1C625 ACTI9 IPRD1 C25R Surge Arrester, Type 1+2, 3P+N, 275 V, 25 kA, Remote Signalling

Schneider Electric · Switchgear & Protection · Surge Protectors · France · se.com
Part Number
A9L1C625  ·  HS 8536.30
Schneider Electric A9L1C625 ACTI9 IPRD1 C25R Surge Arrester, Type 1+2, 3P+N, 275 V, 25 kA, Remote Signalling

Schneider Electric A9L1C625 is an Acti9 iPRD1 C25r combined Type 1 + Type 2 surge protective device (SPD) for 3P+N TN-S distribution boards. It diverts transient overvoltages from direct and indirect lightning and switching surges: lightning impulse current Iimp (10/350 µs) 25 kA, nominal discharge current In (8/20 µs) 25 kA, maximum discharge current Imax (8/20 µs) 65 kA, voltage protection level Up ≤ 1.5 kV, response time < 25 ns. Maximum continuous operating voltage Uc 275 V AC per protected mode. The compact format occupies 18 mm per pole on the DIN rail and is protected by an external gG backup fuse. Front-replaceable pluggable cartridges, a mechanical status window and a remote signalling changeover contact report cartridge end-of-life. Conforms to IEC 61643-11 / EN 61643-11:2012+A11:2018.

Technical Specifications

Manufacturer part number (MPN)A9L1C625
EAN / GTIN3606486808580
Product typeActi9 iPRD1 C25r surge protective device
SPD classType 1 + Type 2 (combined)
Poles3P+N
Earthing / networkTN-S
Nominal voltage Un230/400 V AC, 50/60 Hz
Max. continuous operating voltage Uc275 V AC
Lightning impulse current Iimp (10/350 µs)25 kA
Nominal discharge current In (8/20 µs)25 kA
Max. discharge current Imax (8/20 µs)65 kA
Voltage protection level Up≤ 1.5 kV
Response time< 25 ns
Backup fuseexternal gG, upstream
Status indicationmechanical window + remote signalling contact
Protection cartridgesfront-replaceable, pluggable
MountingDIN rail (clip-on)
Conforms toIEC 61643-11:2011, EN 61643-11:2012+A11:2018
Sales unitpcs
Package quantity14 pcs
Range of productIPRD1
Product nameActi9 iPRD1
Product or component typeSurge arrester with pluggable cartridge
Device short nameiPRD1 C25r
Device applicationDistribution
StandardsIEC 61643-11:2011; EN 61643-11:2012; EN 61643-11:2018/A11
Product certificationsCE
Quality labelsVDE
Poles description3P + N
Remote signallingWith
Surge arrester typeElectrical distribution network
Earthing systemTT; TN-S
Surge arrester class typeType 1 + 2
Surge arrester technologyGDT
[Ue] rated operational voltage230/400 V AC at 50/60 Hz
Nominal discharge currentDifferential mode: 25 kA (L/N); Common mode: 100 kA (N/PE)
Maximum discharge currentDifferential mode: 65 kA L/N; Common mode: 150 kA N/PE
[Iimp] impulse currentDifferential mode: 25 kA L/N 12.5 A.s; Common mode: 100 kA N/PE 50 A.s
[Uc] maximum continuous operating voltageDifferential mode: 275 V L/N; Common mode: 305 V N/PE
Maximum [Up] voltage protection levelDifferential mode <1.5 kV L/N; Common mode <1.5 kV N/PE
[Ut] temporary overvoltage442 V L/N 120 min withstand; 1200 V N/PE 200 ms withstand
[Ifi] follow current50 kA L/N; 100 kA N/PE
Short-circuit withstand50 kA
Disconnector device typeAssociated fuse gG 315 A
Local signallingOperating state: flag (green); Fault indication: flag (red)
Signalling circuit voltage1 A/250 V AC; 1 A/125 V AC; 0.5 A/48 V DC; 0.5 A/24 V DC; 0.5 A/12 V DC
Mounting modeClip-on (DIN rail)
9 mm pitches8
Height105 mm
Width72 mm
Depth86 mm
Product weight691 g
Quantity per setSet of 1
ColourWhite (RAL 9003)
MaterialThermoplastic
Cable cross section0.25…1.5 mm² solid cable for remote control; 6…35 mm² solid stranded cable for power terminals; 6…25 mm² flexible cable for power terminals; 16…35 mm² solid stranded cable for earthing terminal; 16…25 mm² flexible cable for earthing terminal
Wire stripping lengthRemote control: 10 mm; Power terminals: 18 mm; Earthing terminal: 18 mm
Tightening torquePower circuit: 4.5 N.m
Impulse current25 kA
Targeted countryGermany
IP degree of protectionIP20 with cartridges fitted and device wired
IK degree of protectionIK05
Relative humidity5…95 %
Operating altitude0...2000 m
Ambient air temperature for operation-40…85 °C
Country of originSI
Warranty (in months)18
Mounting methodDIN rail (top hat rail) 35 mm
Lightning impulse current (10/350 µs)25 kA
Number of poles4
Construction size4 modular spacing
Voltage protection level1.5 kV
Follow current extinguishing capability50 kA
Max. continuous voltage AC275 V
Nominal voltage AC240 V
Test classType 1 + 2
Voltage protection level L-N1.5 kV
Signalling at the deviceOptical
Degree of protection (IP)IP20
Voltage protection level N-PE1.5 kV
Max. conductor cross section solid (solid, stranded)35 mm²
Max. conductor cross section flexible (fine-strand)25 mm²
Specific energy (W/R)156.2 kJ/Ohm
Max. overcurrent protection device, series connection (fuse)315 A

Properties

IP ratingIP20
Primary standardIEC 61643-11
MOQ1

Standards

Cross-References

Attached Documents