cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-08
sales@cballast.com
cballast.com

Schneider Electric A9L1C602 ACTI9 IPRD1 C25R/F25R Replacement Cartridge, Type 1+2, Neutral-Earth (N-PE)

Schneider Electric · Switchgear & Protection · Surge Protectors · France · se.com
Part Number
A9L1C602  ·  HS 8536.90
Schneider Electric A9L1C602 ACTI9 IPRD1 C25R/F25R Replacement Cartridge, Type 1+2, Neutral-Earth (N-PE)

Schneider Electric A9L1C602 is a replacement plug-in protection cartridge for the Acti9 iPRD1 C25r/F25r combined Type 1 + Type 2 surge protective device (3P and 3P+N). It restores neutral-to-earth (N-PE) overvoltage protection after cartridge end-of-life, which the host device signals through its mechanical status window and remote signalling contact. The 18 mm cartridge is replaced from the front without disturbing the installed conductors. Conforms to IEC 61643-11 / EN 61643-11:2012+A11:2018.

Technical Specifications

Manufacturer part number (MPN)A9L1C602
EAN / GTIN3606486819593
Product typeActi9 iPRD1 C25r/F25r replacement protection cartridge
Protection modeNeutral-Earth (N-PE)
SPD classType 1 + Type 2 (combined)
Compatible host deviceiPRD1 C25r/F25r, 3P and 3P+N
Cartridge width18 mm (1 module)
Mountingfront-plug into iPRD1 base
Conforms toIEC 61643-11:2011, EN 61643-11:2012+A11:2018
HS code8536.90
Sales unitpcs
Package quantity16 pcs
range of productActi9
Product or component typeCartridge
Device short nameiPRD1 C25r
Range compatibilityActi9 iPRD1 C25r; Acti9 iPRD1 F25r
Surge arrester typeElectrical distribution network
StandardsIEC 61643-11:2011; EN 61643-11:2012; EN 61643-11:2018/A11
Product certificationsCE
Quality labelsVDE
Surge arrester class typeType 1 + 2
Surge arrester technologyGDT
Product destinationSurge protection device iPRD1 C25r 3P + N; Surge protection device iPRD1 F25r 3P + N
Earthing systemTT; TN-S
[Ue] rated operational voltage240 V AC 50/60 Hz
Nominal discharge currentCommon mode: 100 kA (N/PE)
Maximum discharge currentCommon mode: 150 kA N/PE
[Iimp] impulse currentCommon mode: 100 kA N/PE 50 A.s
[Uc] maximum continuous operating voltageCommon mode: 305 V N/PE
Maximum [Up] voltage protection levelCommon mode 1.5 kV N/PE
[Ut] temporary overvoltage1200 V N/PE 200 ms withstand
[Ifi] follow current100 kA
Local signallingOperating state: flag (green); Fault indication: flag (red)
mounting modePlug-in
Mounting supportInto SPD module
9 mm pitches2
Height45 mm
Width18 mm
Depth73.5 mm
Product weight115 g
ColourWhite (RAL 9003)
MaterialThermoplastic
Response time< 100 ns
IP degree of protectionIP20
Relative humidity5…95 %
Operating altitude0...2000 m
Ambient air temperature for storage-40…85 °C
Country of originSI
Warranty (in months)18

Properties

IP ratingIP20
Primary standardIEC 61643-11
MOQ1

Standards

Cross-References

Attached Documents