Schneider Electric Residual current circuit breaker (RCCB), ACTI9 iID, 2P, 40A, A type, 100MA, double terminal A9Z22240

Schneider Electric · Electrical Components · RCDs & RCBOs · France · se.com
Part Number
A9Z22240  ·  HS 8536.20
Schneider Electric Residual current circuit breaker (RCCB), ACTI9 iID, 2P, 40A, A type, 100MA, double terminal A9Z22240

Schneider Electric A9Z22240 Residual current module Vigi iC60 4P 63A 300mA A.

Technical Specifications

Manufacturer part number (MPN)A9Z22240
EAN / GTIN3606480443022
Sales unitpcs
Package quantity6 pcs
Rated current40 A
Number of poles2P
RangeActi9
Product nameActi9 iID
Product or component typeResidual current circuit breaker (RCCB)
Device short nameiID
Poles description2P
Neutral positionLeft
[In] rated current40 A
Network typeAC
Earth-leakage sensitivity100 mA
Earth-leakage protection time delayInstantaneous
Earth-leakage protection classType A
Network frequency50/60 Hz
[Ue] rated operational voltage230...240 V AC 50/60 Hz
Residual current tripping technologyVoltage independent
Rated breaking and making capacityIdm 1500 A; Im 1500 A
Rated conditional short-circuit current10 kA
[Ui] rated insulation voltage500 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage6 kV
Contact position indicatorYes
Control typeToggle
mounting modeClip-on
Mounting support35 mm DIN rail
9 mm pitches4
Height91 mm
Width36 mm
Depth73 mm
Product weight210 g
ColourWhite (RAL 9003)
Mechanical durability20000 cycles
Electrical durability15000 cycles
Locking options descriptionPadlocking device
Connections - terminalsDouble terminal front 1…35 mm² rigid; Double terminal front 1…25 mm² flexible; Double terminal front 1…25 mm² flexible with ferrule; Double terminal back 1…25 mm² rigid; Double terminal back 1…16 mm² flexible; Double terminal back 1…16 mm² flexible with ferrule
Wire stripping length14 mm for top or bottom connection
Tightening torque3.5 N.m top or bottom
StandardsEN/IEC 61008-1; EN/IEC 61008-2-1
IP degree of protectionIP20 conforming to IEC 60529; IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
Electromagnetic compatibility8/20 µs impulse withstand, 250 A conforming to EN/IEC 61008-1
Ambient air temperature for operation-25…60 °C
Ambient air temperature for storage-40…85 °C
Warranty (in months)18
Mounting methodDIN rail
Voltage typeAC
Built-in depth44 mm
Rated voltage230 V
Rated insulation voltage Ui500 V
Rated fault current0.1 A
Leakage current typeA
Selective protectionNo
Short-circuit breaking capacity (Icw)1.5 kA
Surge current capacity0.25 kA
Width in number of modular spacings2
Short-time delayed trippingNo
RAL-number (similar)9003
Explosion-proofNo
Power loss3.8 W
Frequency50/60 Hz
Degree of protection (IP)IP20
Connectable conductor cross section solid-core1–35 mm²
Connectable conductor cross section multi-wired1–25 mm²
With interlocking deviceYes
Ambient temperature during operating-25–60 °C
Additional equipment possibleYes
Device width36 mm
Device height91 mm
Device depth73 mm
Rated impulse withstand voltage Uimp6 kV
Country of originSpain

Properties

MOQ1

Cross-References

Attached Documents