Schneider Electric Cam changeover switch, Harmony K, multifixing, 3 Poles, position 0, 30 degree, 20A, black marked 1-0-2 K2E003WLH

Schneider Electric · Switchgear & Protection · Disconnect Switches · France · se.com
Part Number
K2E003WLH  ·  HS 8536.50
Schneider Electric Cam changeover switch, Harmony K, multifixing, 3 Poles, position 0, 30 degree, 20A, black marked 1-0-2 K2E003WLH

Schneider Electric K2E003WLH Drei.Ret.Vend.3-Pole 0 Still.

Technical Specifications

Manufacturer part number (MPN)K2E003WLH
EAN / GTIN3389110244410
Sales unitpcs
Package quantity20 pcs
Range of productHarmony K
Product or component typeComplete cam switch
Component nameK2
[Ith] conventional free air thermal current20 A
Product mountingFront mounting
fixing modeMultifixing
Presentation of legendWith metallic legend, 1 - 0 - 2 black marking
Cam switch functionChangeover switch
Off positionWith Off position
Switching positions0-45°-315°
IP degree of protectionIP40 conforming to IEC 60529
[Ui] rated insulation voltage690 V (pollution degree 3) conforming to IEC 60947-1
[Ithe] conventional enclosed thermal current16 A
Electrical durability200000 cycles AC-23; 200000 cycles AC-3; 600000 cycles AC-15; 600000 cycles AC-21
Maximum operating rate2.5 cyc/mn AC-21; 2.5 cyc/mn AC-23; 2.5 cyc/mn AC-3; 8.333 cyc/mn AC-15
Short-circuit current10000 A
Short-circuit protection20 A cartridge fuse, type gG
[Uimp] rated impulse withstand voltage4 kV in isolating function; 6 kV conforming to IEC 947-1
Contact operationSlow-break
positive openingWith
Electrical connectionCaptive screw clamp terminals flexible, clamping capacity: 2 x 1.5 mm²; Captive screw clamp terminals solid, clamping capacity: 1 x 2.5 mm²
Mechanical durability1000000 cycles
StandardsIEC 60947-3 for power circuit; IEC 60947-5-1 for control circuit; CENELEC EN 50013
Product certificationsCSA 240 V 3 hp 3 phases 2 pole(s); UL 240 V 0.33 hp 1 phase 2 pole(s); CSA 240 V 1 hp 1 phase; UL 240 V 1 hp 3 phases
Protective treatmentTC
Ambient air temperature for operation-25…55 °C
Ambient air temperature for storage-40…70 °C
Shock resistance30 gn conforming to IEC 68-2-27
Vibration resistance5 gn conforming to IEC 68-2-6 (f = 10…150 Hz)
Electrical shock protection classClass II conforming to IEC 536; Class II conforming to NF C 20-030
Number of Units in Package 11
Number of Units in Package 240
Warranty (in months)18
ModelReverser
Rated permanent current Iu20 A
Number of poles3
Rated operation current Ie at AC-3, 400 V8 A
Degree of protection (IP), front sideIP40
Type of electrical connection of main circuitScrew connection
Type of control elementLong rotary handle
Suitable for floor mountingNo
Suitable for front mountingYes
Country of originCzechia