VOLTMET.VEND.FAS/FAS 0 Still. (K10D024MCH)

Schneider Electric · France · se.com
Part Number
K10D024MCH  ·  HS 8536.50
VOLTMET.VEND.FAS/FAS 0 Still. (K10D024MCH)

Schneider Electric K10D024MCH Cam Switch volt fas/fas 0 still.

Technical Specifications

Manufacturer part number (MPN)K10D024MCH
EAN / GTIN3389110076752
Sales unitpcs
Package quantity65 pcs
Range of productHarmony K
Product or component typeComplete cam switch
Component nameK10
[Ith] conventional free air thermal current10 A
Product mountingFront mounting
fixing modeØ 16 or 22 mm hole
Cam switch head typeWith front plate 30 x 30 mm
Type of operatorBlack handle
Rotary handle padlockingWithout
Presentation of legendWith metallic legend, 0 - L1L2 - L2L3 - L3L1 black marking
Cam switch functionVoltmeter switch
ReturnWithout
Type of measurementBetween 3 phases
Off positionWith Off position
Switching positionsRight: 270° - 315° - 0° - 45°
IP degree of protectionContact block: IP20; Operating head: IP65 conforming to IEC 60529
Switching angle45 °
[Ui] rated insulation voltage440 V (pollution degree 3) conforming to IEC 60947-1
Rated operational power in W1800 W AC-23A, 220/240 V 3 phases; 370 W AC-23A, 110/120 V 1 phase; 750 W AC-23A, 220/240 V 1 phase
Rated power in hp1 hp at 220/240 V AC, 3 phases; 0.33 hp at 110/120 V AC, 1 phase; 0.75 hp at 110/120 V AC, 3 phases; 0.75 hp at 220/240 V AC, 1 phase
[Ie] rated operational current AC10 A at 400 V AC-1; 10 A at 400 V AC-21A; 3 A at 240 V AC-15; 6 A at 120 V AC-15
[Ie] rated operational current DC10 A at 24 V resistive load; 0.3 A at 220 V resistive load; 0.7 A at 110 V resistive load
Electrical durability100000000 cycles
Short-circuit protection10 A cartridge fuse, type gG
[Uimp] rated impulse withstand voltage4 kV conforming to IEC 60947-1
Contact operationSlow-break
Electrical connectionCaptive screw clamp terminals, clamping capacity: 2 x 1.5 mm²
Mechanical durability1000000 cycles
CAD overall width30 mm
CAD overall height30 mm
CAD overall depth88 mm
Product weight0.045 kg
StandardsCENELEC EN 50013; EN/IEC 60947-3; EN/IEC 60947-5-1
Product certificationsCULus
Protective treatmentTC
Ambient air temperature for operation-20…55 °C
Ambient air temperature for storage-40…70 °C
Electrical shock protection classClass II conforming to IEC 60536
Number of Units in Package 11
Number of Units in Package 265
Warranty (in months)18
Measurement between phases possibleYes
Measurement between phase and neutral conductor possibleNo
With zero (off) positionYes
Device constructionFront installation
Suitable for distribution boardNo
With control elementYes
Degree of protection (IP)IP65
Country of originAustria

Properties

MOQ1

Cross-References