Schneider Electric Vertical distribution length, Canalis KSA250, aluminium, 160/250A, fixed length 0.8M, 1 outlet, 3L+N+PE, white RAL9001 KSA250ED4081

Schneider Electric · Electrical Components · Busbar Systems · France · se.com
Part Number
KSA250ED4081  ·  HS 8536.90
Schneider Electric Vertical distribution length, Canalis KSA250, aluminium, 160/250A, fixed length 0.8M, 1 outlet, 3L+N+PE, white RAL9001 KSA250ED4081

Schneider Electric KSA250ED4081 Ladders 250A 0,8M 1 outlet.

Technical Specifications

Manufacturer part number (MPN)KSA250ED4081
EAN / GTIN3606480004353
Sales unitpcs
Rated current250 A
RangeCanalis
Device short nameKSA
Offer typeRising main
Product or component typeBusbar trunking
Busbar descriptionVertical distribution length
Product compatibilityCanalis KSA busbar trunking 100…250 A
Conductors materialAluminium
Busbar trunking polarity3L + N + PE
Number of tap-off outlets1
[Ie] rated operational current250 A at 35 °C
IP degree of protectionIP55 conforming to IEC 60529
mounting modeBy screws
Dimension typeFix
Length0.8 m
ColourWhite (RAL 9001)
Number of poles4
Neutral positionRight
Mounting positionVertical
[Ue] rated operational voltage230...690 V
Network frequency50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
[Ui] rated insulation voltage690 V
[Icw] rated short-time withstand current10 kA
[Ipk] rated peak withstand current28 kA
Electrical connectionLubricated sliding contact
Width54 mm
Height146 mm
Product weight6.5 kg
Radiated magnetic field0.69 µT
Thermal stress limit100000 kA².s
THDI0…15 % 250 A; 15…33 % 200 A; 33…100 % 160 A
Maximum voltage drop<0.034 V with power factor = 1 at 50 Hz with 1A for 100 m long; <0.036 V with power factor = 0.9 at 50 Hz with 1A for 100 m long; <0.035 V with power factor = 0.8 at 50 Hz with 1A for 100 m long; <0.034 V with power factor = 0.7 at 50 Hz with 1A for 100 m long
StandardsIEC 61439-1; IEC 61439-6
IK degree of protectionIK08 conforming to IEC 62262
Ambient air temperature for operation35 °C (without derating); 55 °C (with derating factor)
Number of Units in Package 11
Number of Units in Package 220
Warranty (in months)18
Number of conductors (without earthing)4
Rated current AC 50 Hz250 A
Rated voltage AC 50 Hz230–690 V
Number of tap-off units1
Expansion equalizationNo
Fireproof bulkheadNo
RAL-number9001
Degree of protection (IP)IP55
Country of originFrance