cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

R. STAHL 8118/132-542-2 Ex e Terminal Box, GRP IP66, 145×145×71 mm (Art. 202996)

R. Stahl Scandinavia As · Hazardous Area Equipment · Ex Terminal Boxes
Part Number
8118/132-542-2  ·  HS 8536.90
Image not available for this product

R. STAHL Series 8118 increased-safety (Ex e) terminal box, type 8118/132-542-2, article number 202996. Enclosure in glass-fibre reinforced polyester resin (GRP), dark grey, degree of protection IP66. Fitted with 1x WAGO 2002-1407, 7x WAGO 2002-1401, 2x M25 x 1.5 Polyamide stopping plug, 4x Ø 25 mm, 1x Mounting rail 35 x 85 mm. Rated for use in Zones 1, 2, 21 and 22. Enclosure dimensions 145×145×71 mm; weight 0.89 kg; rated operational voltage 550 V AC; ambient temperature -50 °C. +40 °C (T6). Explosion protection ATEX II 2 G Ex eb IIC T6 / T5 Gb and II 2 D Ex tb IIIC T80 °C / T95 °C Db (PTB 99 ATEX 3103), IECEx PTB 06.0026, with DNV ship approval. STAHL article 202996.

Technical Specifications

ManufacturerR. STAHL
Product type8118/132-542-2
Article number202996
EnclosureGlass-fibre reinforced polyester resin (GRP), dark grey
Dimensions (W×H×D)145×145×71 mm
Weight0.89 kg
Degree of protectionIP66 (IEC 60529)
Terminals / components1x WAGO 2002-1407, 7x WAGO 2002-1401, 2x M25 x 1.5 Polyamide stopping plug, 4x Ø 25 mm, 1x Mounting rail 35 x 85 mm
Application zones1, 2, 21, 22
ATEX marking (gas)II 2 G Ex eb IIC T6 / T5 Gb
ATEX marking (dust)II 2 D Ex tb IIIC T80 °C / T95 °C Db
CertificatesATEX PTB 99 ATEX 3103, IECEx PTB 06.0026
Ambient temperature-50 °C ... +40 °C (T6)
Rated operational voltage550 V AC
Ship approvalDNV
Additional certificationBrazil (ULB), India (PESO), Korea (KTL)
FlammabilityIEC/EN 60695

Properties

MaterialGlass-fibre reinforced polyester resin (GRP), dark grey
Temperature range-50 °C ... +40 °C (T6)
IP ratingIP66
Primary standardIEC/EN 60079-0, IEC/EN 60079-7 (Ex e), IEC/EN 60079-31 (Ex t), IEC 60529 (IP)
MOQ1

Standards

Approvals

Attached Documents