cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Fluke Norma 4000 Power Analyzers

Fluke · Safety & Detection · Tools · USA · fluke.com
Part Number
2539612  ·  HS 9030.84
Fluke Norma 4000 Power Analyzers

Fluke Norma Power Analyzers deliver precision measurements of 1 or 3 phase current and voltage, harmonics analysis, and Fast Fourier Transformation analysis.

Technical Specifications

Manufacturer part number (MPN)2539612
BrandFluke
CategoryTools
Number of Phases1 to 3
WeightApprox. 5 kg (11 lb)
Size150 x 237 x 315 mm
On-board PrinterNo
DisplayColor, 5.7 in / 144 mm - 320 x 240 pixel
BandwidthDC to 3 MHz or DC to 10 MHz depending on input module
Basic Accuracy0.2%, 0.1% or 0.03% depending on input modules
Sampling Rate0.33 MHz or 1 MHz depending on input modules
Voltage Input Range0.3 V to 1000 V
Current Input Range (direct, not via shunt)0.03 mA to 20 A depending on input module
Memory for Configurations4 MB
Memory for Settings0.5 MB
Fast Fourier Transformation (FFT)To the 40th harmonic
RS232/USB InterfaceStandard
Digital Oscilloscope (DSO)Simultaneous display of up to 3 measured values on sample level. Quick view of curve form and distortion.
Integration function (energy)Simultaneous display of up to 6 configurable numeric values. Start/Stop conditions and positive negative direction available.
Vector DisplayVector display of HO1 up to 6 signals. For easy testing of the right connection of the instrument and quick overview of the phase angle of each signal.
RecorderDisplay of average values over time for trend determination.
RAM data memoryStoring of sample and average values; setting of start and stop conditions.
ConfigurationSet up the analyzer to measure and display data in the format required.
Working Temperature Range5°C to 35°C (41°F to 95°F)
Storage Temperature Range-20°C to 50°C (-4°F to 122°F)
Housing MaterialFluke Norma Power Analyzers are extremely compact and equipped with a solid metal case to meet stringent EMC requirements.
Climatic ClassKYG DIN 40040, max. 85% relative humidity, non-condensing.
Power supply85 V AC to 264 V AC, 50 Hz to 60 Hz, DC 100 to 260 V, approx. 40 VA European plug with switch. Binding post for current available on some models.
Measuring InputsSafety sockets 4 mm, 2 for each input. External shunt connection over BNC socket.
OperationMembrane keyboard with cursor – function keys and direct functions.
ConnectionsRear panel of the 3-phase Analyzer
RangeDC and 0.2 Hz to sample rate
Accuracy±0.01% of measured value (reading)
OptionsIEEE 488.2 / 1 MBit/s
Electrical SafetyEN 61010-1 / 2nd Edition 1000 V CAT II (600V CAT III)
Maximum inputsFor voltage inputs Measurement range 1000 Veff, 2 kVpeak
Test voltage Net inputcase (protective conductor): 1.5 KV AC
Test voltage Net connectionMeasurement input: 5.4 kV AC
Test voltage Measurement inputsCase: 3.3 kV AC
Test voltage Measurement inputinput: 5.4 kV
Electromagnetic susceptibility EmissionIEC 61326-1, EN 50081-1, EN 55011 Class B
Electromagnetic susceptibility ImmunityIEC 61326-1 / Annex A (industrial sector), EN 50082-1
PP42 Accuracy0.2% (0.1% rd + 0.1% rg)
PP42 Current range20 A
PP42 Sampling rate341 kHz
PP42 Bandwidth3 MHz
PP50 Accuracy0.1% (0.05% rd + 0.05% rg)
PP50 Current range10 A
PP50 Sampling rate1 MHz
PP50 Bandwidth10 MHz
PP54 Accuracy0.1% (0.05% rd + 0.05% rg)
PP54 Current range10 A
PP54 Sampling rate341 kHz
PP54 Bandwidth3 MHz
PP64 Accuracy0.03% (0.02% rg + 0.01% rg)
PP64 Current range10 A
PP64 Sampling rate341 kHz
PP64 Bandwidth3 MHz
Continuous load (Imin) Range (Imax)0.3 A
Nominal current (calibration point)32 A
Basic accuracy at calibration point [%]± 0.03
Basic accuracy at nominal current [%]± 0.03
Nominal voltage drop [V]320 mV
Nominal resistance [Ohm]10 mΩ
Short time overrange (5s load 15s interval)100A/ 1s-5s
Angular accuracy [°/kHz]± 0.1
Temperature coefficient [ppm/K]≤10
Weight (kg / lbs)0.62 /1.36

Properties

MOQ1

Cross-References