cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Fluke 80I-2010S AC/DC Current Clamps

Fluke · Safety & Detection · Tools · USA · fluke.com
Part Number
5125579  ·  HS 9030.33
Fluke 80I-2010S AC/DC Current Clamps

The Fluke 80i-2010s AC/DC Current Clamps are used to measure up to 2,000A AC and/or DC on large conductors with 0.8% accuracy.

Technical Specifications

Manufacturer part number (MPN)5125579
BrandFluke
CategoryTools
Modules80i-2010s
Dimensions110 mm x 270 mm x 46mm
Weight0.710 kg (1.6 lbs), including battery
Output Cable1.5 m (60 in) Shielded Coaxial cable with BNC plug
Maximum Conductor Size52.0 mm (2.05 in)
Maximum Jaw Opening81.5 mm
Output to ZeroAuto adjustment with Zero button
Temperature Operating-10 °C to 50 °C (14 °F to 122 °F)
Storage (battery removed)-30 °C to +60 °C (-22 °F to +140 °F)
Operating Humidity≤ 90 % RH (at 10 °C to 30 °C) ≤ 75 % RH (at 30 °C to 40 °C) ≤ 45 % RH (at 40 °C to 50 °C)
Operating Altitude2,000 m (6560 ft)
Storage Altitude12,000 m (40,000 ft)
Demagnetize ClampOpen and close the Clamp jaws several times with soft click, use of the clamp on uninsulated conductors is limited to 1000 Vac rms or DC and frequencies 1 kHz or less.
SafetyIEC 61010-1, Pollution Degree 2
IEC 61010-2-032CAT III 1000 V /CAT IV 600 V
Ingress ProtectionIEC 60529, IP40
Power Supply Type2 x AA alkaline battery, IEC LR6
Battery Life150 hours (typically)
Low battery indicatorYes
Current Range2000 A ac rms, ± 2000 A dc
Output Sensitivity01 mV/A
Accuracy± 0.8 % of reading ± 0.2 % of range
Bandwidth for Accuracy SpecificationDC to 400 Hz
Load impedance>1 MΩ and <10 pF
Frequency Response (small signal)DC to 20 kHz (-3 dB)
Temperature Coefficient0.1 x specified accuracy for each degree C above 28 °C or below 18 °C
Working Voltage1000 V AC RMS or DC

Properties

MOQ1

Cross-References