Technical Specifications

Manufacturer part number (MPN)4692778
BrandFluke
CategoryTools
600.0 mV Resolution0.1 mV
600.0 mV Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts)±(1% + 3)
600.0 mV Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts)±(2% + 3)
6.000 Vi Resolution0.001 V
6.000 Vi Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts)±(1% + 3)
6.000 Vi Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts)±(2% + 3)
60.00 V Resolution0.01 V
60.00 V Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts)±(1% + 3)
60.00 V Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts)±(2% + 3)
1000 V Resolution1 V
1000 V Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts)±(2% + 3)
1000 V Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts)±(2% + 3)¹
600.0 mV Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts)+(2% + 3), -(6% - 3)
6.000 V Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts)+(2% + 3), -(6% - 3)
1000 V Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts)+(2% + 3), -(6% - 3)
Range ResolutionAccuracy ±(% of Rdg + Counts)
6.000 V dc 0.001 V±(0.09% + 2)
60.00 V dc 0.01 V±(0.09% + 2)
600.0 V dc 0.1 V±(0.09% + 2)
1000 V dc 1 V±(0.09% + 2)
Input impedance10 MΩ (nominal), <100 pF
Normal mode rejection ratio>60 dB @ 50 Hz or 60 Hz
Common mode rejection ratio>120 dB @ dc, 50 Hz or 60 Hz (1 k unbalance)
600.0 mVdc 0.1 mV±(0.1% + 1)
Range400 mA
Resolution0.1 mA
Accuracy ±(% of Rdg+Counts)±(1.5% + 2)¹
Burden voltage (Typical)2 mV/mA
Overload600 mA for 2 minutes maximum
Fuse protection for mA input0.44 mA, 1000 V, IR 10 kA
AC conversionInputs are ac-coupled and calibrated to the rms value of its wave input
600.0 Ω 0.1 Ω±(0.9% + 2)
6.000 kΩ 0.001 kΩ±(0.9% + 2)
60.00 kΩ 0.01 kΩ±(0.9% + 2)
600.0 kΩ 0.1 KΩ±(0.9% + 2)
6.000 MΩ 0.001 MΩ±(0.9% + 2)
50.0 MΩ ² 0.01 MΩ±(1.5% + 3)
Overload protection1000 V rms or dc
Open circuit test voltage<8.0 V dc
Short circuit current<1.1 mA
Diode test indicationDisplay voltage drop: 0.6 V at1.0 mA nominal test current:
Accuracy±(2% + 3)
Continuity indicationContinuous audible tone for testresistance below 25 Ω and off above 100 Ω. Maximum Reading; 1000 Ω
Open circuit voltage<8.0 V
Response time>1 m sec
99.99 Hz 0.01 Hz±(0.1% + 1)
999.9 Hz 0.1 Hz±(0.1% + 1)
9.999 kHz 0.001 kHz±(0.1% + 1)
99.99 kHz 0.01 kHz±(0.1% + 1)
600.0 mV ac V ac Sensitivity (RMS Its Wave)¹ 5 Hz to 20 kHz100.0 mV
V ac Sensitivity (RMS Its Wave)¹ 20 kHz to 100 kHz150.0 mV
6.0 V V ac Sensitivity (RMS Its Wave)¹ 5 Hz to 20 kHz1.0 V
6.0 V V ac Sensitivity (RMS Its Wave)¹ 20 kHz to 100 kHz1.5 V
6.0 V DC Trigger Levels¹ to 20 kHz²-400.0 mV and 2.5 V
60.0 V V ac Sensitivity (RMS Its Wave)¹ 5 Hz to 20 kHz10.0 V
60.0 V V ac Sensitivity (RMS Its Wave)¹ 20 kHz to 100 kHz36.0 V
60.0 V DC Trigger Levels¹ to 20 kHz²1.2 V and 4.0 V
600.0 V V ac Sensitivity (RMS Its Wave)¹ 5 Hz to 20 kHz100.0 V
600.0 V DC Trigger Levels¹ to 20 kHz²12.0 V and 40.0 V
1000.0 V V ac Sensitivity (RMS Its Wave)¹ 5 Hz to 20 kHz300.0 V
1000.0 V DC Trigger Levels¹ to 20 kHz²12.0 V and 40.0 V
1000 nF 1 nF±(1.2% + 2)
10.00 μF 0.01 μF±(1.2% + 2)
100.0 μF 0.1 μF±(1.2% ±90 counts)
9999 μF 1 μF±(1.2% ±90 counts)
-40 ° C to 537 ° C 0.1 °C±(1% + 10 counts)
-40 ° F to 998 ° F 0.1 °F±(1% + 18 counts)
Measurement range0.01 MΩ to 2 GΩ
Test voltages50, 100, 250, 500, 1000 V
Test voltage accuracy+20%, -0%
Short-circuit test current1 mA nominal
Auto dischargeDischarge time <0.5 second for C = 1 μF or less
Live circuit detectionInhibit test if terminal voltage > 30 V prior to initialization of test
Maximum capacitive loadOperable with up to 1 μF load
50 V (0% to +20%) Display range0.01 to 6.00 MΩ
50 V (0% to +20%) Resolution0.01 MΩ
50 V (0% to +20%) Test current1 mA @ 50 kΩ
50 V (0% to +20%) Resistance accuracy ±(% of Rdg + Counts)±(3% + 5 counts)
100 V (0% to +20%) Display range0.01 to 6.00 MΩ
100 V (0% to +20%) Resolution0.01 MΩ
100 V (0% to +20%) Test current1 mA @ 100 kΩ
100 V (0% to +20%) Resistance accuracy ±(% of Rdg + Counts)±(3% + 5 counts)
250 V (0% to +20%) Display range0.1 to 60.0 MΩ
250 V (0% to +20%) Resolution0.1 MΩ
250 V (0% to +20%) Test current1 mA @ 250 kΩ
250 V (0% to +20%) Resistance accuracy ±(% of Rdg + Counts)±(1.5% + 5 counts)
500 V (0% to +20%) Display range0.1 to 60.0 MΩ
500 V (0% to +20%) Resolution0.1 MΩ
500 V (0% to +20%) Test current1 mA @ 500 kΩ
500 V (0% to +20%) Resistance accuracy ±(% of Rdg + Counts)±(1.5% + 5 counts)
1000 V (0% to +20%) Display range0.1 to 60.0 MΩ
1000 V (0% to +20%) Resolution0.1 MΩ
1000 V (0% to +20%) Test current1 mA @ 1 MΩ
1000 V (0% to +20%) Resistance accuracy ±(% of Rdg + Counts)±(1.5% + 5 counts)
Maximum voltage applied to any terminal and common1000 V
Storage temperature-40 °C to 60 °C (-40 °F to 140 °F)
Operating temperature-20 °C to 55 °C (-4 °F to 131 °F)
Temperature coefficient0.05 x (specified accuracy) per °C for temperatures 28 °C (82 °F)
Relative humidityNoncondensing
VibrationRandom, 2 g, 5-500 Hz per MIL-PRF-28800F, Class 2 instrument
Radio frequency communication2.4 GHz ISM Band
Radio frequency certificationFCC: T68-FBLE
IC6627A-FBLE
InternationalIEC 61326-1:Portable Electromagnetic Environment; IEC 61326-2-2 CISPR 11: Group 1, Class A
Korea (KCC)Class A Equipment (Industrial Broadcasting & Communication Equipment)
USA (FCC)47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103.
Enclosure protectionIEC 60529: IP40 (non-operating)
IEC 61010-1Pollution Degree 2
IEC 61010-2-033CAT IV 600 V / CAT III 1000 V
BatteriesFour AA batteries (NEDA 15A or IEC LR6)
Battery lifeMeter use 1000 hours; Insulation test use: Meter can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 MΩ with a duty cycle of 5 seconds on and 25 seconds off.
Size (H x W x L)5.0 x 10.0 x 20.3 cm (1.97 x 3.94 x 8.00 in)
Weight550 g (1.2 lb)
Altitude Operating2000 m
Altitude Storage12,000 m
Over-range capability110% of range except for capacitance which is 100%
Frequency overload protection<107 V Hz
Nominal current range400 A
Continuous current range1 A - 400 A
Maximum non-destructive current1000 A
Lowest measurable current1 A
Basic accuracy2% + 0.06 A
Useable frequency5 Hz - 20 kHz
Output level(s)1 mA/A
SafetyCAT IV 600 V, CAT III, 1000 V
Maximum voltage1000 V AC rms from earth to ground, in compliance with EN61010
Warranty1 year
Maximum conductor diameter32 mm (1.25 in)
Maximum conductor size (busbar)750 MCM
Output cable length1.5 m (59 in)
Shrouded banana plugsYes
Temperature range-30 °C to 650 °C (-22 °F to 1202 °F)
Response time (95%)<300 ms (95% of reading)
Spectral response8 to 14 microns
Emissivity0.10 to 1.00
Optical resolution12:1 (calculated at 90% energy)
Display resolution0.1 °C (0.2 °F)
Repeatability of readings±0.5% of reading or <±0.5 °C (1 °F), whichever is greater
PowerAA battery
Physical specifications Weight255 g (8.99 oz)
Physical specifications Size175 x 85 x 75 mm (6.88 x 3.34 x 2.95 in)
Physical specifications Operating temperature0 °C to 50 °C (32 °F to 122 °F)
Physical specifications Storage temperature-20 °C to 60 °C (-4 °F to 140 °F), (without battery)
Physical specifications Operating humidity10 % to 90 % RH non-condensing at 30 °C (86 °F)
Physical specifications Operating altitude2000 m above mean sea level
Physical specifications Storage altitude12,000 m above mean sea level
Physical specifications IP ratingIP 54 per IEC 60529
Physical specifications Drop test3 m
Physical specifications Vibration and shockIEC 68-2-6 2.5 g, 10 to 200 Hz, IEC 68-2-27, 50 g, 11 ms
Physical specifications EMCEN 61326-1:2006 EN 61326-2:2006
Standards and agency approval ComplianceEN/IEC 61010-1: 2001
Standards and agency approval Laser safetyFDA and EN 60825-1 Class II

Properties

MOQ1

Cross-References

Attached Documents