| Manufacturer part number (MPN) | 13240 |
| EAN / GTIN | 0095969095884 |
| Sales unit | pcs |
| Manufacturer model | Fluke 177 |
| Voltage DC | Accuracy 1 ±(0.09% + 2) |
| Max. resolution | 0.1 mV |
| Maximum | 1000 V |
| Voltage AC | Accuracy 1 ±(1.0% + 3) |
| Current DC | Accuracy 1 ±(1.0% + 3) |
| Current AC | Accuracy 1 ±(1.5% + 3) |
| Resistance | Accuracy 1 ±(0.9% + 1) |
| Capacitance | Accuracy 1 ±(1.2% + 2) |
| Frequency | Accuracy 1 ±(0.1% + 1) |
| Operating temperature | -10°C to +50°C |
| Storage temperature | -30°C to +60°C |
| Humidity (without condensation) | 0% – 90% (0°C – 35°C) 0% – 70% (35°C – 50°C) |
| Overvoltage category | EN 61010–1 to 1000 V CAT III EN 61010–1 to 600 V CAT IV |
| Agency approvals | UL, CSA, TÜV listed and VDE Pending |
| Size | 43 x 90 x 185 mm |
| Current supply | Battery |
| Measured value memory | No |
| Indication | Digital |
| Measuring range selection | Manual/automatic |
| True RMS measurement | Yes |
| Continuity test | Yes |
| Interface | No |
| Capacitance measurement | Yes |
| Frequency measurement | Yes |
| With decibel measurement (dB) | No |
| Data hold | Yes |
| IR interface | No |
| Explosion-tested version | No |
| Analogue bar graph display | Yes |
| Bluetooth interface | No |
| Resistance test/diode test | Yes |
| Inductance measurement | No |
| Lowest resolution |
| DC voltage | 0.1 mV |
| Lowest resolution |
| DC current | 10 µA |
| Lowest resolution |
| AC voltage | 0.1 mV |
| Lowest resolution |
| AC current | 10 µA |
| Lowest resolution, resistance | 0.1 Ohm |
| With conductivity measurement | No |
| Max. voltage measuring range AC | 1000 V |
| Max. voltage measuring range DC | 1000 V |
| Max. current measuring range |
| AC | 10 A |
| Max. current measuring range |
| DC | 10 A |
| Max. resistance measuring range | 50 MOhm |
| Max. value storage | Yes |
| Multiple display | No |
| Measuring circuit category | CAT IV |
| Min. value storage | Yes |
| Nominal test voltage 100 V | No |
| Nominal test voltage 1000 V | No |