| Manufacturer part number (MPN) | UDF-500A # 569060 |
| EAN / GTIN | 8711893042696 |
| Sales unit | pcs |
| Rated current | 500 A |
| Article Number | 569060 |
| Finish | Tinned |
| Max Current Rating |
| IEC | 500A |
| Max Current Rating |
| UL/CSA | 335A |
| Line Side Connection | Flat Conductor |
| Load Side Connection | 11 Cables |
| Material | Copper;Thermoplastic |
| Line Side Max Conductor Size |
| IEC | 185 mm² |
| Line Side Max Conductor Size |
| UL | 185 mm² |
| Load Side Max Conductor Size |
| IEC | 35 mm² |
| Load Side Max Conductor Size |
| UL | #1 |
| Max Working Voltage |
| IEC (Ui) | 1000 |
| Max Working Voltage |
| UL (Vin) | 600 |
| Short Term Withstand Current (Icw) 1s | 24.5kA |
| Peak Short Circuit Current (Ipk) | 51kA |
| Rated Conditional Short-Circuit Current (Icc) | 24.3kA |
| Short Circuit Current Rating (SCCR) | 10kA |
| Line Side Number of Connections | 1 |
| Load Side Number of Connections | 11 |
| Load Side Compact Stranded Wire Size | (2) 6 - 35 mm²;(4) 2,5 - 10 mm²;(5) 2,5 - 16 mm² |
| Load Side Stranded Wire Size - Ferrule | (2) 6 - 25 mm²;(4) 2,5 - 10 mm²;(5) 2,5 - 16 mm² |
| Load Side Wire Size | (2) #10 - #1;(5) #14 - #4;(4) #14 - #6 |
| Enclosure Rating | IP 20 |
| Depth (D) | 1.99" / 50mm |
| Height (H) | 3.79" / 96 mm |
| Width (W) | 1.93" / 49 mm |
| Unit Weight | 0.82 lb / 0.37 kg |
| Certification Details | UL® 1059 |
| Flammability Rating | UL® 94V-0 |
| Complies With | IEC® 60947-7-1 |
| UPC | 782856594246 |
| Standard Packaging Quantity | 1 |
| Packing Quantity | 1 |
| Number of poles | 1 |
| Conductor cross section solid (solid, stranded) | 2.5–35 mm² |
| Max. rated current | 500 A |
| With N-rail | No |
| With PE-rail | No |
| Country of origin | China |