cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

nVent ERIFLEX UD2C9C1250AL Single Pole Distribution Block, 1250 A IEC / 950 A UL-CSA, 2 Cables Line, 9 Cables Load, Aluminum

Eriflex · Electrical Components · Busbar Systems
Part Number
UD2C9C1250AL  ·  HS 8536.90
nVent ERIFLEX UD2C9C1250AL Single Pole Distribution Block, 1250 A IEC / 950 A UL-CSA, 2 Cables Line, 9 Cables Load, Aluminum

Eriflex UD2C9C1250AL In: 2x185-400mm2 Out 9x10-95mm2.

Technical Specifications

Manufacturer part number (MPN)UD2C9C1250AL
EAN / GTIN0782856975434
Sales unitpcs
Rated current1250 A
Article Number569209
FinishTinned
Max Current Rating
IEC1250 A
Max Current Rating
UL/CSA950 A
Line Side Connection2 Cables
Load Side Connection9 Cables
MaterialAluminum; Thermoplastic
Line Side Max Conductor Size
IEC400 mm²
Line Side Max Conductor Size
UL750 kcmil
Load Side Max Conductor Size
IEC95 mm²
Load Side Max Conductor Size
UL3/0 AWG
Max Working Voltage
IEC (Ui)1000; 1500
Max Working Voltage
UL (Vin)1000
Short Term Withstand Current (Icw) 1s84 kA
Peak Short Circuit Current (Ipk)73.5 kA
Rated Conditional Short-Circuit Current (Icc)35 kA
Short Circuit Current Rating (SCCR)100 kA
Line Side Number of Connections2
Line Side Compact Stranded Wire Size185 - 400 mm²
Line Side Wire Size400 – 750
Load Side Number of Connections9
Load Side Compact Stranded Wire Size10 - 95 mm²
Load Side Stranded Wire Size - Ferrule#8 - #1
Load Side Wire Size#8 - 3/0
Enclosure RatingIP 20
Depth (D)195.6 mm
Height (H)112.1 mm
Width (W)70.5 mm
Unit Weight0.93 kg
Certification DetailsUL® 1953
Flammability RatingUL® 94V-0
Complies WithIEC® 60947-7-1
UPC782856975434
Standard Packaging Quantity1
Packing Quantity1
Core cross section400 mm²
With seal headNo
Number of poles1
Country of originChina

Properties

MOQ1

Cross-References

Attached Documents