| Manufacturer part number (MPN) | EU2E-SWD-4DX |
| EAN / GTIN | 4015081712120 |
| Sales unit | pcs |
| Eaton catalogue number | 174726 |
| Depth | 98 mm |
| Height | 20.1 mm |
| Width | 56.9 mm |
| Weight | 0.085 kg |
| Certifications | UL; IEC/EN 61131-2; UL File No.: E170645; CSA |
| Constant acceleration | 1 g, 8.4 - 150 Hz, according to IEC/EN 61131-2, Vibrations |
| Constant amplitude | 3,5 mm, 5 - 8.4 Hz, according to IEC/EN 61131-2, Vibrations |
| Drop and topple | 50 mm Drop height, Drop to IEC/EN 60068-2-31 |
| Height of fall (IEC/EN 60068-2-32) - max | 0.3 m |
| Mounting position | As required |
| Shock resistance | 30 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 9 Impacts |
| Air pressure | 795 - 1080 hPa (operation) |
| Ambient operating temperature - max | 70 °C |
| Ambient storage temperature - max | 70 °C |
| Ambient operating temperature - min | -25 °C |
| Ambient storage temperature - min | -40 °C |
| Climatic proofing | Damp heat, constant, to IEC 60068-2-3; Dry heat to IEC 60068-2-2 |
| Environmental conditions | Condensation: permissible |
| Operating temperature - max | 70 °C |
| Operating temperature - min | -25 °C |
| Relative humidity | 5 - 95 % (non-condensing, IEC/EN 60068-2-30) |
| Connection to SmartWire-DT | Yes |
| Connection type | SWD-IN : M12 plug (A-keyed), 5 pole; 5-pin M12 socket (A-keyed) |
| Supply and I/O sensor; SWD-OUT | M12 socket (A-keyed), 5 pole |
| Data transfer rate | 2 MBit/s, SmartWire-DT; Setting automatically |
| LED indicator | Status indication of SmartWire-DT network: Green LED; Status indication of input: Yellow LED |
| Protocol | Other bus systems |
| Station | SmartWire-DT slave, SmartWire-DT network |
| Static heat dissipation, non-current-dependent Pvs | 1.7 W |
| Input current | 4 mA (at 24 V DC, Digital inputs) |
| Input current at signal 1 | 4 mA |
| Power loss | 1.7 W |
| Supply voltage at DC - max | 28.8 VDC |
| Air discharge | 8 kV, according to IEC 61131-2, level 3, ESD |
| Burst impulse | 1 kV, Signal cable, according to IEC/EN 61131-2, Level 3; 2 kV, Supply cable, according to IEC/EN 61131-2, Level 3; 1 kV, SmartWire-DT cable, according to IEC/EN 61131-2, Level 3 |
| Contact discharge | 4 kV, according to IEC/EN 61131-2, Level 2, ESD |
| Electromagnetic fields | 1 V/m at 2.0 - 2.7 GHz (according to IEC/EN 61131-2:2008); 3 V/m at 1.4 - 2 GHz (according to IEC/EN 61131-2:2008); 10 V/m at 80 - 1000 MHz (according to IEC/EN 61131-2:2008) |
| Radiated RFI | 10 V (IEC/EN 61131-2:2008, Level 3) |
| Radio interference class | Class A (EN 55011) |
| Surge rating | 0.5 kV, Surge power cables, Surge (IEC/EN 61131-2:2008, Level 1), EMC; 1 kV, Surge I/O cables, Surge (IEC/EN 61131-2:2008, Level 1), EMC |
| Electric connection type | Screw connection |
| Features | Fieldbus connection over separate bus coupler possible; Short-circuit protection (sensor supply); Overload protection (sensor supply); Fieldbus connection over separate bus coupler possible |
| Functions | For connection of digital I/O signals |
| Current consumption | 70 mA, Max. current consumption per M12 I/O plug, Sensor supply, SmartWire-DT network; 72 mA, SmartWire-DT network, 24 V, without sensor and without I/O supply |
| Degree of protection | IP69K |
| Mounting method | DIN rail; Screw fixing (M4); Mounting section (Clip M20); Wall mounting/direct mounting; Rail mounting possible |
| Overvoltage category | II |
| Pollution degree | 3 |
| Product category | SmartWire-DT slave |
| Type | Digital modules |
| Voltage type | DC |
| Input delay | < 0.2 ms |
| Limit value type 1 | Low: < 5 V DC; High: > 15 V DC |
| Number of inputs (digital) | 4 |
| Number of outputs (digital) | 0 |
| Explosion safety category for dust | None |
| Explosion safety category for gas | None |
| Potential isolation | Input to input: no; Inputs for SmartWire-DT: no |
| Certified for UL hazardous location division 1 | No |
| Certified for UL hazardous location division 2 | No |
| Certified for UL hazardous location group A (acetylene) | No |
| Certified for UL hazardous location group B (hydrogen) | No |
| Certified for UL hazardous location group C (ethylene) | No |
| Certified for UL hazardous location group D (propane) | No |
| Certified for UL hazardous location group E (metal dusts) | No |
| Certified for UL hazardous location class I | No |
| Certified for UL hazardous location class II | No |
| Certified for UL hazardous location class III | No |
| Supporting protocol for EtherCAT | No |
| Supply voltage DC | 0–28.8 V |
| Number of digital inputs | 4 |
| Digital inputs configurable | No |
| Digital outputs configurable | No |
| Permitted voltage at input | 20.4–28.8 V |
| Type of voltage (input voltage) | DC |
| Type of digital output | None |
| Permitted voltage at output | 20.4–28.8 V |
| Type of output voltage | DC |
| Short-circuit protection, outputs available | No |
| With optical interface | No |
| Supporting protocol for TCP/IP | No |
| Supporting protocol for PROFIBUS | No |
| Supporting protocol for CAN | No |
| Supporting protocol for INTERBUS | No |
| Supporting protocol for ASI | No |
| Supporting protocol for KNX | No |
| Supporting protocol for Modbus | No |
| Supporting protocol for Data-Highway | No |
| Supporting protocol for DeviceNet | No |
| Supporting protocol for SUCONET | No |
| Supporting protocol for LON | No |
| Supporting protocol for PROFINET IO | No |
| Supporting protocol for PROFINET CBA | No |
| Supporting protocol for SERCOS | No |
| Supporting protocol for Foundation Fieldbus | No |
| Supporting protocol for EtherNet/IP | No |
| Supporting protocol for AS-Interface Safety at Work | No |
| Supporting protocol for DeviceNet Safety | No |
| Supporting protocol for INTERBUS-Safety | No |
| Supporting protocol for PROFIsafe | No |
| Supporting protocol for SafetyBUS p | No |
| Supporting protocol for other bus systems | Yes |
| Radio standard Bluetooth | No |
| Radio standard WLAN 802.11 | No |
| Radio standard GPRS | No |
| Radio standard GSM | No |
| Mobile communications standard 3G (UMTS) | No |
| IO link master | No |
| System accessory | Yes |
| Time delay at signal change | 0–0.2 ms |
| Fieldbus connection over separate bus coupler possible | Yes |
| Suitable for rail mounting | Yes |
| Wall mounting/direct mounting | Yes |
| Front built-in possible | No |
| Rack-assembly possible | No |
| Suitable for safety functions | No |
| SIL according to IEC 61508 | None |
| Performance level according to EN ISO 13849-1 | None |
| Appendant operation agent (Ex ia) | No |
| Country of origin | Mexico |