cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Digital module 2 in/out (EU1E-SWD-2DD)

Eaton · Control & Automation · I/O Modules · Ireland · eaton.com
Part Number
EU1E-SWD-2DD  ·  HS 8537.10
Digital module 2 in/out (EU1E-SWD-2DD)

Technical Specifications

Manufacturer part number (MPN)EU1E-SWD-2DD
EAN / GTIN4015081712014
Sales unitpcs
Eaton catalogue number174715
Depth85.6 mm
Height20.1 mm
Width56.9 mm
Weight0.07 kg
CertificationsUL; UL File No.: E170645; IEC/EN 61131-2; CSA
Constant acceleration1 g, 8.4 - 150 Hz, according to IEC/EN 61131-2, Vibrations
Constant amplitude3,5 mm, 5 - 8.4 Hz, according to IEC/EN 61131-2, Vibrations
Drop and topple50 mm Drop height, Drop to IEC/EN 60068-2-31
Height of fall (IEC/EN 60068-2-32) - max0.3 m
Mounting positionAs required
Shock resistance30 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 9 Impacts
Air pressure795 - 1080 hPa (operation)
Ambient operating temperature - max70 °C
Ambient storage temperature - max70 °C
Ambient operating temperature - min-25 °C
Ambient storage temperature - min-40 °C
Climatic proofingDry heat to IEC 60068-2-2; Damp heat, constant, to IEC 60068-2-3
Environmental conditionsCondensation: permissible
Operating temperature - max70 °C
Operating temperature - min-25 °C
Relative humidity5 - 95 % (non-condensing, IEC/EN 60068-2-30)
Connection to SmartWire-DTYes
Connection type5-pin M12 socket (A-keyed)
Supply and I/O sensor; SWD-INM12 plug (A-keyed)
5 pole; SWD-OUTM12 socket (A-keyed), 5 pole
Data transfer rateSetting automatically; 2 MBit/s, SmartWire-DT
LED indicatorStatus indication of input: Yellow LED; Status indication of SmartWire-DT network: Green LED; Status indication of display outputs: Yellow LED
ProtocolOther bus systems
StationSmartWire-DT slave, SmartWire-DT network
Static heat dissipation, non-current-dependent Pvs1.4 W
Input current4 mA (at 24 V DC, Digital inputs)
Input current at signal 14 mA
Output current0.5 A
Power loss1.4 W
Short-circuit protectionOutputs are short-circuit proof
Short-circuit tripping currentMax. 1.2 A over 3 ms, Digital semi-conductor outputs
Supply voltage at DC - max28.8 VDC
Air discharge8 kV, according to IEC 61131-2, level 3, ESD
Burst impulse2 kV, Supply cable, according to IEC/EN 61131-2, Level 3; 1 kV, Signal cable, according to IEC/EN 61131-2, Level 3; 1 kV, SmartWire-DT cable, according to IEC/EN 61131-2, Level 3
Contact discharge4 kV, according to IEC/EN 61131-2, Level 2, ESD
Electromagnetic fields10 V/m at 80 - 1000 MHz (according to IEC/EN 61131-2:2008); 1 V/m at 2.0 - 2.7 GHz (according to IEC/EN 61131-2:2008); 3 V/m at 1.4 - 2 GHz (according to IEC/EN 61131-2:2008)
Radiated RFI10 V (IEC/EN 61131-2:2008, Level 3)
Radio interference classClass A (EN 55011)
Surge rating0.5 kV, Surge power cables, Surge (IEC/EN 61131-2:2008, Level 1), EMC; 1 kV, Surge I/O cables, Surge (IEC/EN 61131-2:2008, Level 1), EMC
Electric connection typeScrew connection
FeaturesDigital inputs configurable; Short-circuit protection (sensor supply); Fieldbus connection over separate bus coupler possible; Digital outputs configurable; Overload proof (with diagnostics); Overload protection (sensor supply); Fieldbus connection over separate bus coupler possible
FunctionsFor connection of digital I/O signals; Short-circuit protection, outputs available
Current consumption70 mA, Max. current consumption per M12 I/O plug, Sensor supply, SmartWire-DT network; 55 mA, SmartWire-DT network, 24 V, without sensor and without I/O supply
Degree of protectionIP69K
Mounting methodRail mounting possible; Mounting section (Clip M20); Wall mounting/direct mounting; Screw fixing (M4); DIN rail
Overvoltage categoryII
Pollution degree3
Product categorySmartWire-DT slave
TypeDigital modules
Voltage typeDC
InputMax. 2 Freely configurable inputs/outputs
Input delay< 0.2 ms
Lamp load≤ 3 W (at RLL)
Limit value type 1Low: < 5 V DC; High: > 15 V DC
Number of inputs (digital)2
Number of outputs (digital)2
OutputMax. 2 Freely configurable inputs/outputs; Max. 2 Transistor Outputs
Switching capacityIEC/EN 60947-5-1, utilization category DC-13, Digital outputs
Explosion safety category for dustNone
Explosion safety category for gasNone
Potential isolationInputs for SmartWire-DT: no; Output to output: no; Between Outputs to SmartWire-DT: no; Output to input: no; Input to input: no
Certified for UL hazardous location division 1No
Certified for UL hazardous location division 2No
Certified for UL hazardous location group A (acetylene)No
Certified for UL hazardous location group B (hydrogen)No
Certified for UL hazardous location group C (ethylene)No
Certified for UL hazardous location group D (propane)No
Certified for UL hazardous location group E (metal dusts)No
Certified for UL hazardous location class INo
Certified for UL hazardous location class IINo
Certified for UL hazardous location class IIINo
Supporting protocol for EtherCATNo
Supply voltage DC0–28.8 V
Number of digital inputs2
Number of digital outputs2
Digital inputs configurableYes
Digital outputs configurableYes
Permitted voltage at input20.4–28.8 V
Type of voltage (input voltage)DC
Permitted voltage at output20.4–28.8 V
Type of output voltageDC
Short-circuit protection, outputs availableYes
With optical interfaceNo
Supporting protocol for TCP/IPNo
Supporting protocol for PROFIBUSNo
Supporting protocol for CANNo
Supporting protocol for INTERBUSNo
Supporting protocol for ASINo
Supporting protocol for KNXNo
Supporting protocol for ModbusNo
Supporting protocol for Data-HighwayNo
Supporting protocol for DeviceNetNo
Supporting protocol for SUCONETNo
Supporting protocol for LONNo
Supporting protocol for PROFINET IONo
Supporting protocol for PROFINET CBANo
Supporting protocol for SERCOSNo
Supporting protocol for Foundation FieldbusNo
Supporting protocol for EtherNet/IPNo
Supporting protocol for AS-Interface Safety at WorkNo
Supporting protocol for DeviceNet SafetyNo
Supporting protocol for INTERBUS-SafetyNo
Supporting protocol for PROFIsafeNo
Supporting protocol for SafetyBUS pNo
Supporting protocol for other bus systemsYes
Radio standard BluetoothNo
Radio standard WLAN 802.11No
Radio standard GPRSNo
Radio standard GSMNo
Mobile communications standard 3G (UMTS)No
IO link masterNo
System accessoryYes
Time delay at signal change0–0.2 ms
Fieldbus connection over separate bus coupler possibleYes
Suitable for rail mountingYes
Wall mounting/direct mountingYes
Front built-in possibleNo
Rack-assembly possibleNo
Suitable for safety functionsNo
SIL according to IEC 61508None
Performance level according to EN ISO 13849-1None
Appendant operation agent (Ex ia)No
Country of originMexico

Properties

MOQ1

Cross-References

Attached Documents