| Manufacturer part number (MPN) | ESR5-NV3-300 |
| EAN / GTIN | 4015081684298 |
| Sales unit | pcs |
| Eaton catalogue number | 171858 |
| Depth | 114.5 mm |
| Height | 99 mm |
| Width | 45 mm |
| Weight | 0.472 kg |
| Mounting position | As required |
| Prooftest | 240 Months (High Demand); 19 Months (Low Demand) |
| Switching capacity | 3 A at 3600 O/h, AC-15 at 230 V, Outputs; 2.5 A at 3600 O/h, DC-13 at 24 V, Outputs; 0.4 W; In accordance with IEC 60947-5-1, Outputs; 4 A at 360 O/h, AC-15 at 230 V, Outputs |
| Vibration resistance | 10 - 150 Hz |
| Amplitude | 0.15 mm |
| Acceleration | 2 g, (IEC/EN 60068-2-6) |
| Air pressure | 795 - 1080 hPa (operation) |
| Altitude | Max. 2000 m |
| Ambient operating temperature - max | 55 °C |
| Ambient storage temperature - max | 70 °C |
| Ambient operating temperature - min | -20 °C |
| Ambient storage temperature - min | -40 °C |
| Climatic proofing | Cold to EN 60068-2-1; Dry heat to IEC 60068-2-2; Damp heat, constant, to IEC 60068-2-3 |
| Environmental conditions | Clearance in air and creepage distances according to EN 50178, UL 508, CSA C22.2 |
| No. 14-95; Condensation | Non-condensing |
| Operating temperature - max | 55 °C |
| Operating temperature - min | -20 °C |
| Relative humidity | < 75 % |
| Static heat dissipation, non-current-dependent Pvs | 5.43 W |
| Inrush current | 0.025 - 6 A |
| Rated control supply voltage (Us) at AC |
| 50 Hz - max | 230 V |
| Rated control supply voltage (Us) at AC |
| Rated control supply voltage (Us) at AC |
| 60 Hz - max | 26.4 V |
| Rated control supply voltage (Us) at AC |
| 60 Hz - min | 20.4 V |
| Rated control supply voltage (Us) at DC - max | 24 V |
| Rated control supply voltage (Us) at DC - min | 24 V |
| Rated insulation voltage (Ui) | 250 V |
| Rated operational voltage | Approx. 24 V DC at input, starting and feedback circuit; 230 V AC; 24 V DC (power supply) |
| Short-circuit protection | Non-time-delay 6-A fast-blow fuse, For output circuits, External; Time-delay 10-A gL/gG Neozed fuse, For output circuits, External |
| Short-circuit protection rating | 6 A (non-delayed), Output fuse, Output data; 10A gL/gG, NEOZED (delayed), Output fuse, External, Output data |
| Electric connection type | Screw connection |
| Features | Safe insulation; 3 Non-delayed enable current paths; Monitored reset; Automatic start; 6 kV between the enable current paths (13/14, 23/24, 33/34) and the remaining rungs, as well as between 13/14, 23/24, 33/34 in relation to each other; Manual start; Reinforced insulation; Basic insulation |
| Fitted with | Feedback circuit; Start input; Approval according to UL; Detachable clamps; Approval for TÜV |
| Functions | 1-channel; 2-channel |
| Connection type | M3 screw terminals |
| Current consumption | 155 mA, DC |
| Degree of protection | Installation location: ≥ IP54; Enclosure: IP20; Terminals: IP20; IP20 |
| Emitted interference | According to EN 61000-6-4 |
| Interference immunity | According to EN 61000-6-2 |
| LED indicator | Status indication of SmartWire-DT network: Green LED |
| Lifespan, mechanical | 10,000,000 Operations |
| Model | Basic device |
| Mounting method | Rail mounting possible; Top-hat rail fixing (according to IEC/EN 60715, 35 mm) |
| Mounting width | 45 mm |
| Overvoltage category | III |
| Pollution degree | 2 |
| Power loss | Normally 5.43 W |
| Product category | Electronic safety relays |
| Protection | Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274) |
| Rated impulse withstand voltage (Uimp) | 4000 V AC |
| Recovery time | 1000 ms |
| Safety parameter (EN ISO 13849-1) | PL e, Performance level; Cat. 4, Category; 300,000 switching cycles, B10d |
| Safety parameter (IEC 62061) | SILCL 3, Safety integrity level claim limit; 3.6 x 10-10, PFHd, Probability of failure per hour; Off-delay contacts, SILCL 2 as per IEC 62061; SIL 3, Safety integrity level, In accordance with IEC 61508; Cat. 4, Category; Non-time-delay contacts, SILCL 3 as per IEC 62061 and SIL 3 as per IEC 61508 |
| Stop category (IEC 60204) | 0 + 1 |
| Suitable for | Monitoring of emergency-stop circuits; Module used to safely interrupt electrical circuits; Monitoring of position switches; Safety relay for monitoring emergency stop and protective door switch |
| Switching frequency | Max. 0.5 Hz, Input data |
| Type | Emergency stop category 1; emergency switching off Light curtain Protective door |
| Voltage type | DC |
| Input | ∞ ms, Simultaneity for inputs 1/2 |
| Number of inputs | One- and two-channel |
| Number of outputs (safety related, delayed) with contact | 2 |
| Number of outputs (safety related, undelayed) with contact | 3 |
| Number of outputs (signaling function, delayed) with contact | 0 |
| Number of outputs (signaling function, undelayed) with contact | 1 |
| Off-delay | 0.2 - 300 s (± 40 %, K3, K4 adjustable) |
| Permissible total cable resistance | 22 Ω (input and starting circuits for UN) |
| Pick-up time | 600 ms typ. (at Uₑ in automatic mode); 70 ms typ. (at Uₑ in manual mode); 600 ms typ. (K1, K2 - for UN automatic mode); 70 ms typ. (K1, K2 - for UN manual operation) |
| Quadratic summation current | 55 A² (ITH² = I1² + I2² + I3² + I4² + I5²) |
| Reset time | 20 ms (non-delayed contacts) |
| Switching voltage | 250 V |
| Uninterrupted current | 6 A N/C, Limiting continuous current; 6 A N/O, Limiting continuous current |
| Screwdriver size | 2, Terminal screw, Pozidriv screwdriver; 3.5 x 0.6 mm, Terminal screw |
| Stripping length (main cable) | 7 mm |
| Terminal capacity | 1 x (0.2 – 2.5) mm², solid; 2 x (0.2 – 1) mm², solid; 2 x (0.25 – 1) mm², flexible with ferrule; 1 x (0.25 – 2.5) mm², flexible with ferrule; 24 - 12 AWG, solid or stranded |
| Tightening torque | 0.6 Nm, Screw terminals |
| Operating voltage DC | 24 V |
| Power consumption | 5.43 W |
| Supply voltage DC | 24 V |
| Rated switch current | 4 A |
| Control voltage 1 | 24 V |
| Control voltage 2 | 24 V |
| Type of control voltage 1 | DC |
| Type of control voltage 2 | AC |
| Suitable for monitoring of position switches | Yes |
| Suitable for monitoring of emergency-stop circuits | Yes |
| Suitable for monitoring of valves | No |
| Suitable for monitoring of tactile sensors | No |
| Suitable for monitoring of magnetic switches | No |
| Suitable for monitoring of proximity switches | No |
| Type of electric connection | Screw connection |
| Suitable for rail mounting | Yes |
| Rated control supply voltage AC 50 Hz | 0–230 V |
| Rated control supply voltage DC | 24 V |
| Voltage type for actuating | DC |
| With detachable clamps | Yes |
| Evaluation inputs | One- and two-channel |
| With start input | Yes |
| With muting function | No |
| With feedback circuit | Yes |
| Release-delay | 0.2–300 s |
| Number of outputs, safety related, undelayed, with contact | 3 |
| Number of outputs, safety related, delayed, with contact | 2 |
| Type of safety according to IEC 61496-1 | None |
| Stop category according to IEC 60204 | 0 + 1 |
| Performance level according to EN ISO 13849-1 | Level e |
| SIL according to IEC 61508 | 3 |
| With approval for BG BIA | No |
| With approval according to UL | Yes |
| Country of origin | Germany |