Can Open Gateway (XNE-GWBR-CANOPEN)

Eaton · Control & Automation · Fieldbus I/O · Ireland · eaton.com
Part Number
XNE-GWBR-CANOPEN  ·  HS 8538.90
Can Open Gateway (XNE-GWBR-CANOPEN)

Technical Specifications

Manufacturer part number (MPN)XNE-GWBR-CANOPEN
EAN / GTIN7640130120600
Sales unitpcs
Eaton catalogue number140044
Depth129 mm
Height75 mm
Width33.5 mm
Weight0.136 kg
CertificationscULus; IEC/EN 61000-6-2; IEC/EN 61131-2; Rated data for terminations according to IEC/EN 60947-7-1; CE; IEC/EN 6113-2; IEC/EN 61000-6-4
Catalog Notessupports up to 62 disc-type modules (XN, XNE)
Drop and toppleAccording to IEC 60068-2-31, free fall according to IEC 60068-2-32
Shock resistanceMechanical, According to IEC/EN 60068-2-27; Continuous according to IEC/EN 60068-2-29
Vibration resistanceAccording to IEC/EN 60068-2-6
Ambient operating temperature - max55 °C
Ambient storage temperature - max85 °C
Ambient operating temperature - min0 °C
Ambient storage temperature - min-25 °C
Environmental conditionsHarmful gasses - H2S: 1 ppm (relative humidity < 75%, no condensation); Harmful gasses - SO2: 10 ppm (relative humidity < 75%, no condensation)
Relative humidity5 - 95 % (indoor, Level RH-2, non-condensing for storage at 45°C)
AddressingAddress set via DIP switch; Address range: 1 - 63 decimal
Bus terminationVia DIP switch, Networking
Connection typePush-In spring-cage terminals, Field bus; Spring-cage terminals, Field bus/Supply voltage); Push-In spring-cage terminals, Connection design in TOP direction
Data transfer rate800 kBit/s; 50 kBit/s; 500 kBit/s, Networking; 800 kBit/s, Networking; 125 kBit/s, Networking; 250 kBit/s; 10 kBit/s, Networking; 1000 kBit/s, Networking; 1000 kBit/s; 20 kBit/s; Setting through DIP switch or automatically; 50 kBit/s, Networking; 250 kBit/s, Networking; 500 kBit/s; 125 kBit/s
Field voltage24 V DC (UL)
InterfacesPS/2 socket (Service interface); CANopen®, Field bus connection
ProtocolCANopen®; CAN; Other bus systems
Static heat dissipation, non-current-dependent Pvs6 W
Supply voltage4.7 - 5.3 V DC
Supply voltage at AC
Supply voltage at AC
Supply voltage at DC - max30 V
Supply voltage at DC - min18 V
Air dischargeAccording to EN 61100-4-2
Burst impulseAccording to IEC/EN 61000-4-4
Contact dischargeAccording to EN 61100-4-2
Electromagnetic fieldsAccording to IEC EN 61100-4-2
Emitted interference230 - 1000 MHz (radiated, high frequency, according to EN 55016-2-3); 30 - 230 MHz (radiated, high frequency, according to EN 55016-2-3)
Radiated RFIIEC/EN 61100-4-6
Surge ratingAccording to IEC/EN 61000-4-5 Level 4
Voltage dipsAccording to EN 61131-2 (Voltage fluctuations/voltage dips)
FeaturesFieldbus connection over separate bus coupler possible
Fitted withBus refreshing module; Potential separation
Accessories1 x end plate XN-ABPL and 2 x end bracket XN-WEW-32/2-SW included with supplied equipment.
Admissible range18 - 30 V DC, Networking
ConfigurationMaximum station configuration: 62 cards (XN
XNE) of slice design or max. length of station1 m
Degree of protectionIP20
Mounting methodRail mounting possible
Residual rippleAccording to EN 61131-2
TypeXI/ON ECO gateways XNE-Gateway with integrated supply
Voltage typeDC
Explosion safety category for dustNone
Explosion safety category for gasNone
Potential isolationThrough optocoupler: yes
Gauge pinA1 (according to IEC/EN 60947-1)
Stripping length (main cable)8 mm
Terminal capacity0.25 - 1.5 mm², with ferrules without plastic collar; 0.25 - 1.5 mm², solid; 0.25 - 1.5 mm², flexible without ferrule; 0.25 - 0.75 mm², with ferrules with plastic collar
Certified for UL hazardous location division 1No
Certified for UL hazardous location division 2No
Certified for UL hazardous location group A (acetylene)No
Certified for UL hazardous location group B (hydrogen)No
Certified for UL hazardous location group C (ethylene)No
Certified for UL hazardous location group D (propane)No
Certified for UL hazardous location group E (metal dusts)No
Certified for UL hazardous location class INo
Certified for UL hazardous location class IINo
Certified for UL hazardous location class IIINo
Supporting protocol for EtherCATNo
Supply voltage DC18–30 V
Supporting protocol for TCP/IPNo
Supporting protocol for PROFIBUSNo
Supporting protocol for CANYes
Supporting protocol for INTERBUSNo
Supporting protocol for ASINo
Supporting protocol for KNXNo
Supporting protocol for ModbusNo
Supporting protocol for Data-HighwayNo
Supporting protocol for DeviceNetNo
Supporting protocol for SUCONETNo
Supporting protocol for LONNo
Supporting protocol for SERCOSNo
Supporting protocol for PROFINET IONo
Supporting protocol for PROFINET CBANo
Supporting protocol for Foundation FieldbusNo
Supporting protocol for EtherNet/IPNo
Supporting protocol for AS-Interface Safety at WorkNo
Supporting protocol for DeviceNet SafetyNo
Supporting protocol for INTERBUS-SafetyNo
Supporting protocol for PROFIsafeNo
Supporting protocol for SafetyBUS pNo
Supporting protocol for other bus systemsNo
Radio standard BluetoothNo
Radio standard WLAN 802.11No
Radio standard GPRSNo
Radio standard eGPRSNo
Radio standard GSMNo
Radio standard LTENo
Mobile communications standard 3G (UMTS)No
IO link masterNo
System accessoryYes
With potential separationNo
Fieldbus connection over separate bus coupler possibleYes
Suitable for rail mountingYes
Wall mounting/direct mountingNo
Front built-in possibleNo
Rack-assembly possibleNo
Suitable for safety functionsNo
SIL according to IEC 61508None
Performance level according to EN ISO 13849-1None
Appendant operation agent (Ex ia)No
Country of originGermany

Properties

MOQ1

Cross-References

Attached Documents