| Manufacturer part number (MPN) | DIL-SWD-32-001 |
| EAN / GTIN | 4015081168309 |
| Sales unit | pcs |
| Package quantity | 5 pcs |
| Eaton catalogue number | 118560 |
| Depth | 72 mm |
| Height | 38 mm |
| Width | 45 mm |
| Weight | 0.04 kg |
| Certifications | CSA File No.: 2324643; CSA Class No.: 3211-07; CSA-C22.2 No. 14-05; UL; UL File No.: E29184; CSA; IEC/EN 61131-2; UL Category Control No.: NKCR; CE; EN 50178; IEC/EN 60947; IEC/EN 60947-4-1; UL 508 |
| Constant acceleration | 1 g, 8.4 - 150 Hz, according to IEC/EN 61131-2, Vibrations |
| Constant amplitude | 3,5 mm, 5 - 8.4 Hz, according to IEC/EN 61131-2, Vibrations |
| Drop and topple | 50 mm Drop height, Drop to IEC/EN 60068-2-31 |
| Height of fall (IEC/EN 60068-2-32) - max | 0.3 m |
| Mounting position | As DILM7 to DILM38 |
| Shock resistance | 15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 9 Impacts |
| Ambient operating temperature - max | 60 °C |
| Ambient storage temperature - max | 70 °C |
| Ambient operating temperature - min | -25 °C |
| Environmental conditions | Condensation: prevent with appropriate measures |
| Relative humidity | 5 - 95 % (non-condensing, IEC/EN 60068-2-30) |
| Addressing | Address set automatically |
| Connection to SmartWire-DT | Yes |
| Connection type | Push in terminals |
| Auxiliary contact; SWD | Plug, 8-pole; External device plug SWD4-8SF2-5, SmartWire-DT |
| LED indicator | Status indication of SmartWire-DT network: Green and orange LED |
| Station | SmartWire-DT slave, SmartWire-DT network |
| Number of auxiliary contacts | 2 |
| Static heat dissipation, non-current-dependent Pvs | 0.8 W |
| Rated operational voltage | 15 V DC (auxiliary contact) |
| Supply voltage at DC - max | 15 VDC |
| Supply voltage at DC - min | 15 VDC |
| Air discharge | 8 kV, according to IEC 61131-2, level 3, ESD |
| Burst impulse | 1 kV, Signal cable, according to IEC/EN 61131-2, Level 3; 1 kV, SmartWire-DT cable, according to IEC/EN 61131-2, Level 3 |
| Contact discharge | 4 kV, according to IEC/EN 61131-2, Level 2, ESD |
| Electromagnetic fields | 1 V/m at 2.0 - 2.7 GHz (according to IEC/EN 61131-2:2008); 10 V/m at 80 - 1000 MHz (according to IEC/EN 61131-2:2008); 3 V/m at 1.4 - 2 GHz (according to IEC/EN 61131-2:2008) |
| Radiated RFI | 10 V (IEC/EN 61131-2:2008, Level 3) |
| Radio interference class | Class A (EN 55011) |
| Electric connection type | Spring clamp connection |
| Features | Fieldbus connection over separate bus coupler possible; Fieldbus connection over separate bus coupler possible |
| Fitted with | Own supply |
| Functions | Contactor actuation; Display of Switch status Contactor, status of the digital inputs 1 and 2; For connecting the contactors to SmartWire-DT |
| Cable length | ≤ 2.8 m, Connection auxiliary contact |
| Current consumption | 40 mA, SmartWire-DT network |
| Degree of protection | IP20 |
| Input current at signal 1 | 3 mA |
| Number of inputs (digital) | 2 |
| Number of outputs (digital) | 1 |
| Output current | 0.5 A |
| Overvoltage category | II |
| Pollution degree | 2 |
| Product category | SmartWire-DT slave |
| Protocol | Other bus systems |
| Type | SWD contactor modules |
| Voltage type | DC |
| Pick-up current | 500 mA (for DILM 17-38); 188 mA (for DILM 12-15); 125 mA (for DILM 7-9) |
| Sealing current | 125 mA, SmartWire-DT network for DILM 7-9; 21 mA, SmartWire-DT network for DILM 17-38; 188 mA, SmartWire-DT network for DILM 12-15 |
| Power consumption | 3 W for DILM 7-9 (Pick-up power); 4.5 W for DILM 12-15 (Pick-up power); 4.5 W for DILM 12-15 (Sealing power); 12 W for DILM 17-38 (Pick-up power); 3 W for DILM 7-9 (Sealing power); 0.5 W for DILM 17-38 (Sealing power) |
| Explosion safety category for dust | None |
| Explosion safety category for gas | None |
| Potential isolation | Connection auxiliary contact: no |
| Terminal capacity | 0.2 - 1.5 mm² (24 - 16 AWG), solid; 0.25 - 1.5 mm², flexible with ferrule |
| Certified for UL hazardous location division 1 | No |
| Certified for UL hazardous location division 2 | No |
| Certified for UL hazardous location group A (acetylene) | No |
| Certified for UL hazardous location group B (hydrogen) | No |
| Certified for UL hazardous location group C (ethylene) | No |
| Certified for UL hazardous location group D (propane) | No |
| Certified for UL hazardous location group E (metal dusts) | No |
| Certified for UL hazardous location class I | No |
| Certified for UL hazardous location class II | No |
| Certified for UL hazardous location class III | No |
| Supporting protocol for EtherCAT | No |
| Supply voltage DC | 15 V |
| Number of digital inputs | 2 |
| Number of digital outputs | 1 |
| Digital inputs configurable | No |
| Digital outputs configurable | No |
| Permitted voltage at input | 15 V |
| Type of voltage (input voltage) | DC |
| Permitted voltage at output | 20.4–28.8 V |
| Type of output voltage | DC |
| Short-circuit protection, outputs available | No |
| Number of HW-interfaces other | 1 |
| With optical interface | No |
| Supporting protocol for TCP/IP | No |
| Supporting protocol for PROFIBUS | No |
| Supporting protocol for CAN | No |
| Supporting protocol for INTERBUS | No |
| Supporting protocol for ASI | No |
| Supporting protocol for KNX | No |
| Supporting protocol for Modbus | No |
| Supporting protocol for Data-Highway | No |
| Supporting protocol for DeviceNet | No |
| Supporting protocol for SUCONET | No |
| Supporting protocol for LON | No |
| Supporting protocol for PROFINET IO | No |
| Supporting protocol for PROFINET CBA | No |
| Supporting protocol for SERCOS | No |
| Supporting protocol for Foundation Fieldbus | No |
| Supporting protocol for EtherNet/IP | No |
| Supporting protocol for AS-Interface Safety at Work | No |
| Supporting protocol for DeviceNet Safety | No |
| Supporting protocol for INTERBUS-Safety | No |
| Supporting protocol for PROFIsafe | No |
| Supporting protocol for SafetyBUS p | No |
| Supporting protocol for other bus systems | Yes |
| Radio standard Bluetooth | No |
| Radio standard WLAN 802.11 | No |
| Radio standard GPRS | No |
| Radio standard GSM | No |
| Mobile communications standard 3G (UMTS) | No |
| IO link master | No |
| System accessory | Yes |
| Type of electric connection | Spring clamp connection |
| Time delay at signal change | 10–84 ms |
| Fieldbus connection over separate bus coupler possible | Yes |
| Suitable for rail mounting | No |
| Wall mounting/direct mounting | No |
| Front built-in possible | No |
| Rack-assembly possible | No |
| Suitable for safety functions | No |
| SIL according to IEC 61508 | None |
| Performance level according to EN ISO 13849-1 | None |
| Appendant operation agent (Ex ia) | No |
| Country of origin | Germany |