| Manufacturer part number (MPN) | 197216 |
| EAN / GTIN | 4015080892779 |
| Sales unit | pcs |
| Eaton catalogue number | 197216 |
| Depth | 58 mm |
| Height | 90 mm |
| Width | 72 mm |
| Weight | 0.25 kg |
| Compliances | Eaton supports the product until its end of life |
| Catalog Notes | Accuracy of the real-time clock depending on ambient air temperature - fluctuations of up to ± 5 s/day (± 0.5 h⁄year) are possible |
| Drop and topple | 50 mm Drop height, Drop to IEC/EN 60068-2-31 |
| Height of fall (IEC/EN 60068-2-32) - max | 0.3 m |
| Mounting position | Horizontal; Vertical |
| Shock resistance | 15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 18 Impacts |
| Vibration resistance | According to IEC/EN 60068-2-6; 10 - 57 Hz, 0.15 mm constant amplitude; 57 - 150 Hz, 2 g constant acceleration |
| Cable length | 100 m (max. permissible per input I7 to I8), Digital inputs 115/230 V AC; 40 m (max. permissible per input I1 to I6), Digital inputs 115/230 V AC |
| Cable type | Ethernet: CAT5 |
| Air pressure | 795 - 1080 hPa (operation) |
| Ambient operating temperature - max | 55 °C |
| Ambient storage temperature - max | 70 °C |
| Ambient operating temperature - min | -25 °C |
| Ambient storage temperature - min | -40 °C |
| Environmental conditions | Clearance in air and creepage distances according to EN 50178, EN 61010-2-201, UL61010-2-201 |
| CSA-C22.2 NO. 61010-2-201; Condensation | prevent with appropriate measures |
| Relative humidity | 5 - 95 % (IEC 60068-2-30, IEC 60068-2-78) |
| Connection type | Screw terminal; Ethernet: RJ45 plug, 8-pole |
| Data transfer rate | 10/100 MBit/s |
| LED indicator | Status indication of Ethernet: LED; Status indication of Power/RUN |
| Equipment heat dissipation, current-dependent Pvid | 4 W |
| Static heat dissipation, non-current-dependent Pvs | 4 W |
| Conventional thermal current Ith of auxiliary contacts (1-pole, open) | 8 A |
| Inrush current | 12.5 A (for 6 ms) |
| Power consumption | 4 W |
| Power loss | 10 W |
| Rated breaking capacity | 300000 Operations at AC-15, 250 V AC, 3 A (600 Ops./h); 200000 Operations at DC-13, 24 V DC, 1 A (500 Ops./h) |
| Rated insulation voltage (Ui) | 240 V |
| Rated operational voltage | 110/120 V DC (power supply); Max. 300 V DC; Max. 300 V AC; 100/110/115/120/230/240 AC (-15 %/+10 %); 85 - 264 V AC; 240 V AC |
| Supply frequency | 50/60 Hz (± 5%) |
| Supply voltage at AC |
| 50 Hz - max | 264 VAC |
| Supply voltage at AC |
| 50 Hz - min | 85 VAC |
| Supply voltage at DC - max | 264 VDC |
| Supply voltage at DC - min | 85 VDC |
| Uninterrupted current | 8 A AC, at 240 V AC (UL/CSA); 1 A DC, at R 300 (UL/CSA); 8 A DC, at 24 V DC (UL/CSA); 5 A AC, max. thermal continuous current cos ϕ = 1 at B 300 (UL/CSA) |
| Air discharge | 8 kV |
| Burst impulse | 2 kV, Supply cable; According to IEC/EN 61000-4-4; 2 kV, Signal cable |
| Contact discharge | 6 kV |
| Electromagnetic fields | 1 V/m at 2.0 - 2.7 GHz (according to IEC EN 61000-4-3); 10 V/m at 0.8 - 1.0 GHz (according to IEC EN 61000-4-3); 3 V/m at 1.4 - 2 GHz (according to IEC EN 61000-4-3) |
| Immunity to line-conducted interference | 10 V (according to IEC/EN 61000-4-6) |
| Radio interference class | Class B (EN 61000-6-3) |
| Surge rating | According to IEC/EN 61000-4-5, power pulses (Surge), EMC; 1 kV, Supply cables, symmetrical, power pulses (Surge), EMC; 2 kV, Supply cables, asymmetrical, power pulses (Surge), EMC |
| Voltage dips | 10 ms |
| Features | Expandable; Networkable (Ethernet) |
| Fitted with | Timer; Real time clock; Relay output |
| Indication | LCD-display used as status indication of Digital inputs 115/230 V AC |
| Degree of protection | IP20 |
| Display temperature - max | 55 °C |
| Display temperature - min | 0 °C |
| Input frequency | 50/60 Hz (Digital inputs, at 115/230 V AC); 50/60 Hz (Digital inputs, at 24 V DC) |
| Insulation resistance | According to EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201 |
| Lifespan, mechanical | 1,000,000 Operations |
| Mounting method | Front build in possible; Top-hat rail fixing (according to IEC/EN 60715, 35 mm); Wall mounting/direct mounting; Rail mounting possible; Screw fixing using fixing brackets ZB4-101-GF1 (accessories) |
| Overvoltage category | III |
| Pollution degree | 2 |
| Product category | Control relays easyE4 |
| Protection | B16 circuit breaker or 8 A (T) fuse, Protection of an Output relay |
| Protocol | MODBUS; TCP/IP |
| Rated impulse withstand voltage (Uimp) | Relay outputs: 6 kV (contact-coil) |
| Residual ripple | ≤ 5 % |
| Resolution | 1 min (Range H:M) 1 s (Range M:S) 5 ms (Range S) |
| Software | EASYSOFT-SWLIC/easySoft |
| Switching frequency | 10 Hz, Relay outputs; 2 Hz, Resistive load/lamp load, Relay outputs; 0.5 Hz, Inductive load, Relay outputs |
| Type | easyE4 base device |
| Used with | easyE4 |
| Utilization category | B 300 Light Pilot Duty, UL/CSA Control Circuit Rating Codes AC; R 300 Light Pilot Duty, UL/CSA Control Circuit Rating Codes DC |
| Voltage type | AC |
| Accuracy | ± 1 %, Repetition accuracy of timing relays (of values); ± 2 s/day, Real-time clock to inputs (± 0.2 h⁄Year) |
| Input current | 6 x 0.5 mA (I1 - I6, at 230 V AC, 50 Hz, at signal 1); 2 x 4 mA (I7 - I8, at 115 V AC, 60 Hz, at signal 1); 6 x 0.25 mA (I1 - I6, at 115 V AC, 60 Hz, at signal 1); 2 x 6 mA (I7 - I8, at 230 V AC, 50 Hz, at signal 1); 6 x 0.25 mA (I1 - I8, at 115 V AC, 60 Hz, at signal 1) |
| Input voltage | Condition 0: 0 - 40 V AC, Digital inputs |
| 115/230 V AC); Condition 1 | 79 - 264 V AC, Digital inputs, 115/230 V AC) |
| Making/breaking capacity | 28/28 VA (DC, at R 300); 3600/360 VA (AC, at B 300) |
| Number of inputs (analog) | 0 |
| Number of inputs (digital) | 8 |
| Number of outputs (analog) | 0 |
| Number of outputs (digital) | 4 |
| Output | Relay outputs in groups of 1; 4 Relay Outputs; > 500 mA (Relay outputs |
| Recommended for load | 12 V AC/DC); Voltage; Current |
| Parallel switching | Not permitted |
| Explosion safety category for dust | None |
| Explosion safety category for gas | None |
| Protection against polarity reversal | Yes, for supply voltage (Siemens MPI optional) |
| Safe isolation | 300 V AC, Between coil and contact, According to EN 50178; 300 V AC, Between two contacts, According to EN 50178 |
| Short-circuit protection | ≥ 1A (T), Fuse, Power supply |
| Screwdriver size | 3.5 x 0.8 mm, Terminal screw |
| Terminal capacity | 0.2 - 2.5 mm² (22 - 12 AWG), flexible with ferrule; 0.2 - 4 mm² (AWG 22 - 12), solid |
| Tightening torque | 0.6 Nm, Screw terminals |
| Certified for UL hazardous location division 1 | No |
| Certified for UL hazardous location division 2 | Yes |
| Certified for UL hazardous location group A (acetylene) | Yes |
| Certified for UL hazardous location group B (hydrogen) | Yes |
| Certified for UL hazardous location group C (ethylene) | Yes |
| Certified for UL hazardous location group D (propane) | Yes |
| Certified for UL hazardous location group E (metal dusts) | No |
| Certified for UL hazardous location class I | Yes |
| Certified for UL hazardous location class II | No |
| Certified for UL hazardous location class III | No |
| Supporting protocol for EtherCAT | No |
| Supply voltage AC 50 Hz | 85–264 V |
| Supply voltage AC 60 Hz | 85–264 V |
| Supply voltage DC | 85–264 V |
| Switching current | 8 A |
| Number of digital inputs | 8 |
| Number of digital outputs | 4 |
| With relay output | Yes |
| Number of HW-interfaces industrial Ethernet | 1 |
| Number of HW-interfaces other | 1 |
| With optical interface | No |
| Supporting protocol for TCP/IP | Yes |
| Supporting protocol for PROFIBUS | No |
| Supporting protocol for CAN | No |
| Supporting protocol for INTERBUS | No |
| Supporting protocol for ASI | No |
| Supporting protocol for KNX | No |
| Supporting protocol for Modbus | Yes |
| Supporting protocol for Data-Highway | No |
| Supporting protocol for DeviceNet | No |
| Supporting protocol for SUCONET | No |
| Supporting protocol for LON | No |
| Supporting protocol for PROFINET IO | No |
| Supporting protocol for PROFINET CBA | No |
| Supporting protocol for SERCOS | No |
| Supporting protocol for Foundation Fieldbus | No |
| Supporting protocol for EtherNet/IP | No |
| Supporting protocol for AS-Interface Safety at Work | No |
| Supporting protocol for DeviceNet Safety | No |
| Supporting protocol for INTERBUS-Safety | No |
| Supporting protocol for PROFIsafe | No |
| Supporting protocol for SafetyBUS p | No |
| Supporting protocol for other bus systems | No |
| Radio standard Bluetooth | No |
| Radio standard WLAN 802.11 | No |
| Radio standard GPRS | No |
| Radio standard GSM | No |
| Mobile communications standard 3G (UMTS) | No |
| IO link master | No |
| Redundancy | No |
| With display | No |
| Basic device | Yes |
| Expandable | Yes |
| Expansion device | No |
| With time switch clock | Yes |
| Suitable for rail mounting | Yes |
| Wall mounting/direct mounting | Yes |
| Front built-in possible | Yes |
| Rack-assembly possible | No |
| Suitable for safety functions | No |
| SIL according to IEC 61508 | None |
| Performance level according to EN ISO 13849-1 | None |
| Appendant operation agent (Ex ia) | No |
| Country of origin | Estonia |